}

Repair Replacement And Maintenance To Stps Valve Pumps Motors Lt Starter Panels Connected Pipe Lines Valve Chambers Cleaning To Ug Oh Water Sumps And Other Allied Misc Works At Age E M No Ii Under Garrison Engineer Utility Ii Visakhapatnam, Garrison Engineer Utility-II Visakhapatnam-Andhra Pradesh

Military Engineer Services-MES has published Repair Replacement And Maintenance To Stps Valve Pumps Motors Lt Starter Panels Connected Pipe Lines Valve Chambers Cleaning To Ug Oh Water Sumps And Other Allied Misc Works At Age E M No Ii Under Garrison Engineer Utility Ii Visakhapatnam. Submission Date for this Tender is 17-02-2021. Starter Tenders in Garrison Engineer Utility-II Visakhapatnam Andhra Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

26674583
Corrigendum : Repair Replacement And Maintenance To Stps Valve Pumps Motors Lt Starter Panels Connected Pipe Lines Valve Chambers Cleaning To Ug Oh Water Sumps And Other Allied Misc Works At Age E M No Ii Under Garrison Engineer Utility Ii Visakhapatnam
Open Tender
Indian
Andhra Pradesh
Garrison Engineer Utility-II Visakhapatnam
17-02-2021

Tender Details

Repair Replacement And Maintenance To Stps Valve Pumps Motors Lt Starter Panels Connected Pipe Lines Valve Chambers Cleaning To Ug Oh Water Sumps And Other Allied Misc Works At Age E M No Ii Under Garrison Engineer Utility Ii Visakhapatnam

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 04-Feb-2021 CORRIGENDUM Technical Bid 10-02-2021
2 10-Feb-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 17-02-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 90000.0 /-
Tender Value
INR 45 Lakhs /-

BOQ Items

Name of Work: REPAIR/REPLACEMENT AND MAINTENANCE TO STPs, VALVE, PUMPS, MOTORS, LT STARTER PANELS, CONNECTED PIPE LINES VALVE CHAMBERS, CLEANING TO UG, OH WATER SUMPS AND OTHER ALLIED MISC WORKS AT AGE E/M NO. II UNDER GARRISON ENGINEER (UTILITY-II) VISAKHAPATNAM.
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Material and labour for PCC (1:3:6) type C1 using 20 mm graded stone aggregate as a surface hard standing/ base foundation for the pipelines/Chlorine plant including necessary form work complete all as specified. (Note:- Quoted rates is inclusive levelling surface as per direction of EIC complete) 2 Cum
2 2 M & L for Brickwork with subclass 'B' old size bricks, straight or curved on plan exc 6m mean radius built in Cement mortar 1:4 complete all as specified and directed. 3 Cum
3 3 M & L for 15 mm thick rendering in cement mortar 1:4 on fair faces of concrete or brick surface mixed with water proofing compound as per manufacturer's instruction finished even and fair without using extra cement complete all as specified and directed. 2 Sqm
4 4 M & L for preparation of newly plastered surfaces/old surface of ceiling/Wall and applying two coats of whitewash complete all as specified and directed. 20 Sqm
5 5 Labour only for attending break down of 300/250/200 mm dia CI/DI/MS pipe pipe line bursting / cracks and including cleaning / removal of broken pipe pieces of various lengths through gas cutting / manual cutting as per site requirement and including inserting necessary specials such as pipes, CI / DI Collar / mechanical Joints etc as per site requirement, testing for leakages of lead joints, testing and necessary dewatering complete all as specified and directed by Engr-in-Charge, for the following sizes:- \nNote 1 :- The quoted rate is deemed to be include the following:-\n(i) Arrangement of suitable Pump sets for dewatering at the time of attending break down. (ii) Necessary Earth Work, labour/trade men for attending break down. (iii) Labour element required for fixing CI/DI/MS pipes, specials, fittings etc.\nNote 2 :- M & L Lead joints, Supply only CI/ DI/ MS pipes, specials, fittings will be measured and paid seperately under relevant items. 12 Job
6 6 All as per SL item No.5 above but of 150/100/80 mm dia. 12 Job
7 7 Supply only Jointing with flexible rubber gaskets push on type joints Ductile Iron pipe class K 9 ISI marked as per IS 8329-2000 with centrifugally lined with cement mortar complete in trenches of size 80 mm dia of make Electro steel/Jindal/Lanco 6 RM
8 8 All as per SL item No.7 above but of size 100 mm dia. 6 RM
9 9 All as per SL item No.7 above but of size 150 mm dia. 6 RM
10 10 All as per SL item No.7 above but of size 200 mm dia. 6 RM
11 11 All as per SL item No.7 above but of size 250 mm dia. 6 RM
12 12 All as per SL item No.7 above but of size 300 mm dia. 6 RM
13 13 Material and labour for run lead joint for spigot and socket pipes (CI/DI) and fittings of size 80 mm complete all as specified and directed by Engr-in-Charge. 1 Each
14 14 All as per Sl. Item No 13 above but of size 100 mm bore. 2 Each
15 15 All as per Sl. Item No 13 above but of size 150 mm bore. 5 Each
16 16 All as per Sl. Item No.13 above but of size 200 mm bore. 4 Each
17 17 All as per Sl. Item No.13 above but of size 250 mm bore. 4 Each
18 18 All as per Sl. Item No.13 above but of size 300 mm bore. 1 Each
19 19 Supply only DI Specials (any type radius and angle) tapers any type straight increasing decreasing or double socket and ''Y junction double branch ,Collar, cross (all sockets or socket and spigot)caps and plugs upto 300 mm bore. 300 Kg
20 20 M & L for replacement of battery lead set two suitable for 180 to100 AH capacity 1.5 mtr long including GM terminals one end copper lug and other including 0.5 mtr connecting both end with gun metal terminals. 6 Each
21 21 M & L for replacement of push button switch for starting the DG Set upto 500 KVA Make: Lucas or equivalent as directed by the Engr-in-Charge. 4 Each
22 22 Supply and replacement of selector switch rotary type for checking / reading 3 phase voltage / Amps meter. 4 Each
23 23 M & L for Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground vertically to a depth not less than 2.25 metres below ground level with top edge of earth plate at a depth not less than 1.5 metre below ground level, connected to galvanised iron or steel, earth strip 32 x 6 mm size by means of nuts, bolts check nuts and washers made of galvanised iron or steel, earth wire protected by galvanised iron pipe 15mm bore, medium grade and connected to main switch board or main control board/DG Set (Approx length of GI strip from earth plate to DG set 5 Mtrs) as directed and including concrete pit in PCC (1:3:6) type C1, pre-cast RCC cover slab 30 cm x 30 cm x 10 cm with one lifting handle made of 8 mm dia MS bar funnel wire mesh, 20 mm bore galvanised iron or steel pipe medium grade for watering charcoal or coke and salt in alternate layers, necessary excavation and earth work in any type of soil complete all as shown in electrical Plate No 3 of MES Schedule Part- I and testing on completion . (Concrete pit shall be 20 cm to 30 cm away from main pit). 4 Each
24 24 M&L for rewinding the submersible motor PVC insulated copper conductor of same gauge and same number of turns as that of existing including tieing the winding and connecting the coils and bringing the connections as that of existing complete all as specified for submersible motor of 2.0 to7.5 HP capacity 2 Job
25 25 M&L for rewinding the submersible motor PVC insulated copper conductor of same gauge and same number of turns as that of existing including tieing the winding and connecting the coils and bringing the connections as that of existing complete all as specified for submersible motor of 25 HP capacity 1 Job
26 26 Opening the submersible pump set of 25 HP for inspection, repairs and reassembling the pump and motor as per the original assembly after repairs / replacing the worn out unserviceable parts with new parts as ordered, including cleaning replacing the minor items like packing bolts, nuts washers and MS clamps etc and applying one coat of approved hammertene spray paint on exposed steel surface, making the pump and motor fully serviceable including lathework etc and testing the same for satisfactory operation on its full load all as specified and directed by Engineer - in - Charge. Note: The rate is inclusive of spares required for replacement such as Thurst bearing set, Stage casing, Impeller etc.. 1 Job
27 27 Repair/servicing of monoblock pump set of 3 HP to7. 5 HP complete including strip opening and reassembling the pump and motor as per the original assembly after repairs / replacing the worn out unserviceable parts, remetalling the wornout shaft including lathe work, replacing the wornout bearings, gland packing bolts, nuts washers, water seal etc, incl varnishing the motor windings and applying one coat of approved synthetic paint on exposed steel surface, making the pump and motor fully serviceable and testing the same for satisfactory operation on its full load all as specified and directed by Engineer - in - Charge. 1 Job
28 28 All as per sl Item No 27 above but for 10 HP to 25 HP complete all as specified and directed by Engineer - in - Charge. 1 Job
29 29 M & L for dismantling of motor of following capacities pumpset from installed position after disconnecting the coupling and electric connections and transporting the motor to the work shop, strip opening of the motor complete incl dismanlting stator, rotor assembly and cleaning the complete assemblies by taking out perished glass sleeve of connecting leads from common termination to terminal block,and washing with carbon tetra chloride, decarbonising and cleaning the rotor with CTC solution.Replacing the glass sleeve of connecting leads from common termination to terminal block, binding the loose coils with binding cloth, varnishing the coils complete and applyng bectol on the excitor coils, stator coils and heating complete, reassembling the unit and testing with megger for insualtion value and re-assembling, aligning with pump, re-inserting shims where necessary, refixing with coupling, tightening with torque wrench to required level, re-connecting the electric cable etc and check for drawing current testing, commissioning etc all as directed by Engineer-in-Charge.
30 29.01 90 HP to 125 HP 1 Each Job
31 29.02 30 HP to 50 HP 1 Each Job
32 29.03 10 HP to 25 HP 1 Each Job
33 29.04 5 HP to 7.5 HP 1 Each Job
34 30 M & L for dismantling the pump of following capacity, checking the worn out parts like impeller, shaft, stuffing box, shaft sleeve using Micrometer and transporting to workshop for repairs, check for condition of bearings, removing scales from impeller and pump housing, building the worn out metal of transmission shaft to required level, machining to the required size on lathe machine, grinding and finishing to match the sleeve, and fixing into the housing, re-assembling, transport back to the installation, installing in position, check for alignment with dial gauge, inserting shims where necessary, refixing with coupling, tightening with torque wrench to required level, re-connecting the flanged pipe connections of suction/ delivery including replacement of rubber insertion etc complete, all as directed by Engineer-in-Charge.
35 30.01 NOTE :- Cost of Spares such as shaft, ball bearing, metal coupling and gland packing etc is included in above coated rate.
36 30.02 90 HP to 125 HP 1 Each Job
37 30.03 30 HP to 50 HP 1 Each Job
38 30.04 10 HP to 25 HP 1 Each Job
39 30.05 5 HP to 7.5 HP 1 Each Job
40 31 M&L for dismantling the defective induction motor of any capacity/make/class of insulation from foundation bed, duly coupled with pump/compressor, trasnporting to workshop removing burnt out winding from stator/rotor, rewinding with suitable gauge of super enamelled copper wire of approved make and replacing DE /NDE bearings, insulation materials, varnishing , heating etc complete, re-assembling, testing and commissioning of following capacity motors all as directed. Note : The cost of repair is inclusive of cost of DE/NDE bearing Terminal block, Bearings of motor etc
41 31.01 90 to 125 HP 1 Job
42 31.02 30 HP to 50 HP 1 Job
43 31.03 10 HP to 25 HP 1 Job
44 31.04 5 HP to 7.5 HP 1 Job
45 32 S & F rubber bush coupling for the following capacities of pumpsets complete all as directed:-
46 32.01 90 to 125 HP 1 Each
47 32.02 30 HP to 50 HP 1 Each
48 32.03 10 HP to 25 HP 1 Each
49 33 M & L for repairs to pump shaft of any make with necessary metal filling and machining suitable for the following capacity of pump sets
50 33.01 90 to 125 HP 1 Each
51 33.02 30 HP to 50 HP 1 Each
52 33.03 10 HP to 25 HP 1 Each
53 33.04 5 HP to 7.5 HP 1 Each
54 34 Servicing/maintenance of dial type water level indicator by replacing wornout central movement plate, counter weight, centre diving wheels etc., and applying two coats of synthetic enamel paint over a coat of primer complete all as specified and as directed. 1 Job
55 35 M & L for arresting water leakage from sluice valve of 80 mm bore, by refacing, regrinding of sluice Valve, Repacking stuffing box of sluice valve spindle including taking apart and reassembling the same including replaceing old check nuts with new one made out of MS/CI material, with and including replacing perished gland packing, rubber gasket, bolts and nuts complete all as directed by Engineer-in-charge. 1 Each
56 36 All as per Sl. Item No.35 above but 100 mm bore 1 Each
57 37 All as per Sl. Item No.35 above but 150 mm bore 1 Each
58 38 All as per Sl. Item No.35 above but 200 mm bore 1 Each
59 39 All as per Sl. Item No.35 above but 250 mm bore 1 Each
60 40 All as per Sl. Item No.35 above but 300 mm bore 1 Each
61 41 Dismantling unserviceable valves and Supply, fixing,testing and commissioning of butterfly valves incl cutting, welding etc complete and painting with two coats of synthetic enamel paint over a coat of red oxide primer complete all as directed
62 41.01 80 mm bore 1 Each
63 41.02 100 mm bore 1 Each
64 41.03 150 mm bore 1 Each
65 41.04 200 mm bore 1 Each
66 41.05 300 mm bore 1 Each
67 42 Supply and replace CI sluice valves , 300 mm dia , PN 1.6, conforming to IS -14846 Flanged end complete with iron wheel head and stainless steel spindle including flanged joints, replacement of perished nuts, bolts washers and rubber gasket etc. complete all as specified and directed by Engineer-in-charge Make: Kirloskar/Venus/Shakti /Upadhyaya/ Jash Engineering 1 Each
68 43 All as per item No.42 above but 250 mm dia 1 Each
69 44 All as per item No.42 above but 200 mm dia 2 Each
70 45 All as per item No.42 above but 150 mm dia 1 Each
71 46 All as per item No.42 above but 100 mm dia 1 Each
72 47 All as per item No.42 above but 80 mm dia 1 Each
73 48 Supply & laying MS ERW pipe of 100 mm dia heavy grade for inserting in position, making leak proof joints including testing the pipe line for leakage, taking down unserviceable including painting with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed by Engineer-in-Charge. \n 18 RM
74 49 All as per SL item No.48 hereinbefore but 150 mm dia 36 RM
75 50 All as per SL item No.48 hereinbefore but 200 mm dia 80 RM
76 51 All as per SL item No.48 hereinbefore but 250 mm dia 18 RM
77 52 All as per SL item No.48 hereinbefore but 300 mm dia 24 RM
78 53 S&F in repair MCCB 4 Pole, 415 V, fixed type, 63 to 125 Amps with breaking capacity 16 KA Make: GE /L&T//Havells/C&S 1 Each
79 54 S&F in repair MCCB 3Pole, 415 V, 160 Amps with breaking capacity 36 KA Make: GE /L&T//Havells/C&S 1 Each
80 55 S&F in repair MCCB 4 Pole, 415 V, 200 Amps with breaking capacity 36 KA Make: GE /L&T//Havells/C&S 1 Each
81 56 S&F in repair MCCB 4 Pole, 415 V, 250 Amps with breaking capacity 36 KA Make: GE /L&T//Havells/C&S 1 Each
82 57 S&F in repair MCCB 4 Pole, 415 V, 320-350 Amps with breaking capacity 36 KA Make: GE /L&T//Havells/C&S 1 Each
83 58 S&F in repair MCCB 4 Pole, 415 V, 400 Amps with breaking capacity 36 KA Make: GE /L&T//Havells/C&S 1 Each
84 59 S&F in repair MCCB 4 Pole, 415 V, 630 Amps with breaking capacity 50 KA Make: GE /L&T//Havells/C&S 1 Each
85 60 S & F MPCB 63 Amps Make:Complete all as specified and directed by Engr in Charge. Model No. MOG-H2 (rotary type) CAT No. ST41922OOOO of L&T or its equivalent in ABB, BCH, Siemens , C&S Electric Ltd, Schneider as approved by GE. 1 Each
86 61 S & F LCD Multifunctional meter with CTs Complete all as specified and directed Make:CAT No. WC441010OOOO of L&T or its equivalent in Legrand/ ABB/ Siemens/ GE/ C&S Electric Ltd/ Schneider as approved by GE. 1 Each
87 62 S & F LED Multifunctional meter with CTs Complete all as specified and directed Make:CAT No. WL411010OOOO of L&T or its equivalent in Legrand/ ABB/ Siemens/ GE/ C&S Electric Ltd/ Schneider as approved by GE. 1 Each
88 63 S & F Indication Lamp (LED type) Set of 3 Complete all as specified and directed by Engr in-Charge. Make L&T or its equivalent in Legrand/ ABB/ Siemens/ GE/ C&S Electric Ltd/ Schneider as approved by GE. 3 Set of 3
89 64 Dismantling the existing unserviceable LT UG cable and Supply & lay LT UG cable 19238XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 4 sq. mm, 4 core
90 64.01 Note: 1. Exacavation, earth work, sand, bricks and PCC will be measured and paid under relevant items.
91 64.02 4 sqmm 4 core 12 RM
92 64.03 10 sqmm 4 core 40 RM
93 65 Excavation in trenches n.exc 1.5 mtr wide and n.exc 1.5 mtr depth for laying of cables / pipes etc and getting out in hard/dense soil. complete all as specified. 165 CUM
94 66 Returning, filling in including spreading levelling watering and well ramming in layers not exc 25 cm in any type of soil. 139 CUM
95 67 Removing excavated material to a distance n.exc 50 mtr and depositing where directed at a level n.exc 1.5 mtr above the starting point all as directed. 26 CUM
96 68 Supply and spread river sand to required width at bottom and top for cable cushioning all as directed by Engr-in-Charge. 4 CUM
97 69 Supply and lay burnt bricks of class 'B' laid dry across in trenches for cable protection Complete all as directed by Engr-in-Charge. 240 Each
98 70 Dismantling unserviceable Steel Tubular/ PCC Poles of any description and any size including demolition of Cement Concrete (as/if required) and made good disturbed Ground, complete all as specified and as directed.\nNOTE: Unserviceable Poles will be dismantled at Ground Level and disturbed ground will made good as directed for which Earthwork, demolition of Cement Concrete, etc. will not be measured and paid separately. 6 EACH
99 71 Dismantling Stay Assembly of any description and any size including Mild Steel Clamps with Bolts, Nuts and Washers etc., complete all as specified and as directed. \nNOTE: Unserviceable Stay Assembly will be dismantled at Ground Level and disturbed ground will made good as directed for which Earthwork, demolition of Cement Concrete, etc. will not be measured and paid separately. 2 EACH SET
100 72 Dismantling Cross-Arms of Mild Steel Channel or Angle Sections, etc, including Mild Steel Bolts, Nuts, Washers, etc., complete all as specified and as directed. 0.25 QUINTAL
101 73 Dismantling Insulators like Pin type, Shackle type from existing Street/ Security Light Pole of any description and any size, seggregating Seviceable Insulators and keep in safe custody for re-use, complete all as specified and as directed. 30 EACH
102 74 Dismantling ACSR or AAC Conductors from the Disturbed Span including Line Spacer, etc., complete all as specified and as directed. 2 QUINTAL
103 75 M&L Cement Concrete 1:4:8 (40mm graded aggregate) as Lean Concrete in Foundation of Poles, Stay Assembly, etc., including Form-work (as/if required), complete all as specified and as directed. 0.3 CUBIC METRE
104 76 M&L Cement Concrete 1:3:6 (40mm graded aggregate) as in Foundation of Poles, Stays, etc. including Formwork (as/if required) complete all as specified and as directed. 0.3 CUBIC METRE
105 77 M&L Cement Concrete 1:2:4 (20mm graded aggregate) as in Coping of Poles, etc. and finishing the Concrete surfaces Fair and Even including necessary Formwork required at Site(s), complete all as specified and as directed. 0.75 CUBIC METRE
106 78 Supply & Erecting Steel Tubular Swaged Pole Type 410-SP-31 (9.0 METRE long) including Cast Iron Base Plate, Finial Taper Plug, Cap, Mild Steel Bolts, Nuts, Screws including apply -ing two coats of Black Bituminous Paint Inter -nally and Externally from bottom End of Pole upto PCC Coping and applying with two coats of Aluminium Painting over a coat of Alumi-nium Primer (Externally from Top of Coping) including writing MES Pole No. with synthetic Enamel Paint (First Grade/quality), complete all as specified and as directed.\nNOTE: Earthwork, Cement Concrete, etc. will be measured and paid under approprite Items. 6 EACH
107 79 M&L Stay Assembly complete with Accessories as show in Electrical Plate No. 1 of MES Schedule Part-I, diameter of Stay Rod 16mm, size of Plate 230x230x6mm including 7/3.15 mm Galvanised Stay Strand, complete all as specified and as directed.\nNOTE: Earthwork, Cement Concrete, Mild Steel Stay Clamps with Bolts, Nuts, etc., Loop Insulator, etc. will be measured and paid under approprite Items. 2 EACH SET
108 80 M&L Cross-arms, Bracings, Supports, Clamps and Back Plates fabricated from Structural Steel Sections including Nuts, Bolts, Washer, welding, bending cold or hot, drilling holes for Bolts, in any shape or size as indicated/ direct-ed and inclusive of one coat of Aluminium Primer one Under Coat and One Finishing Coat of Aluminium Paint, complete all as specified and as directed. 1 QUINTAL
109 81 Refixing only Cross-arms, Bracings, Supports, Clamps and Back Plates (serviceable materials i.e. Structural Steel Sections obtained from Item No. 7 here-in-before) including Nuts, Bolts, Washer, welding, bending cold or hot, drilling holes for Bolts, in any shape or size as indicated/ directed and inclusive of one coat of Aluminium Primer one Under Coat and One Finishing Coat of Aluminium Paint, complete all as specified and as directed. 3 QUINTAL
110 82 S&F Insulator Pin type Porcelain, Vitreous, White, Brown or Green including one Galvanised Mild Steel Spindle, Two Galvanised Iron Washers and One Galvanised Iron Nut, 100mm Height, 65mm dia for 1100 Volt grade complete all as specified and as directed. 36 EACH
111 83 Fixing only Insulator Pin type Porcelain, Vitreous including one Galvanised Mild Steel Spindle Two Galvanised Iron Washers and One Galvanised Iron Nut, 100mm Height, 65mm dia for 1100 Volt grade (Serviceable Insulator obtained from Item No. 8 here-in- before) complete all as specified and as directed. 60 EACH
112 84 S&F Shackle type, Porcelain, Vitreous, White or Brown Insulator of size 100mm height 115mm dia including Galvanised Mild Steel 31x5mm Strap, 14mm dia Insulator Bolts, Nuts, Washers, etc. for Working Pressure 1100 Volt, complete all as specified and as directed. 12 EACH
113 85 Fixing only Shackle type Porcelain, Vitreous of size 100mm height 115mm dia including Galvanised Mild Steel 31x5mm Strap, 14mm dia Insulator Bolts, Nuts, Washers, etc. for Working Pressure 1100 Volt grade (Serviceable Insulator obtained from Item No.8 here-in-before), complete all as specified and as directed. 18 EACH
114 86 S&F Loop Type Insulator Vitreous White, Brown or Green, large size with overall dimensions 90x65mm, clearance of hole 16mm dia, complete all as specified and as directed. 12 EACH
115 87 S&F Aluminium Conductor Steel Reinforced (ACSR) (sizes as ordered) with permissible Sags and providing Jumper, etc., fixing on Electric Poles and binding to Insulators with Aluminium Binding Wire as in OH Conductors including stringing, tightening, etc., complete all as specified and as directed.\nNOTE: Cost of Binding Wire is deemed to be included in the QUOTED UNIT RATE.\n 3 QUINTAL
116 88 Re-stringing to OH Line ACSR Conductor on existing Lines by un-binding from the Insulator of any description, re-fixing after stretching the Conductor, removing excess Sag, maintaining proper distance between Conductors as ordered, complete all as specified and as directed.\nNOTE :– Cost of Binding Wire is deemed to be included in the QUOTED UNIT RATE. 2 QUINTAL
117 89 S & F in replacement operating Handle for LT panel change over Switch of rateing 63 Amps-100 Amps. Complete all as specified and as directed by Engr-in-Charge. 1 Each
118 90 S & F in replacement operating Handle for LT panel change over Switch of rateing 125 Amps-200 Amps. Complete all as specified and as directed by Engr-in-Charge. 2 Each
119 91 S & F in replacement operating Handle for LT panel change over Switch of rateing 250 Amps-315 Amps. Complete all as specified and as directed by Engr-in-Charge. 2 Each
120 92 Supply and fixing switch 5 Amp piano 230 volts, one way flush type. 25 Each
121 93 Supply and fixing switch socket combination 5 pin 6/15 Amp piano 230 volts, one way flush type. 5 Each
122 94 Supply and fixing lamp holder PVC/Polycarbonate type with back plate suitable for batten fitting 4 Each
123 95 S & F switch socket combination 3Pin 5 AMPs flush type complete all as specified and as directed 3 Each
124 96 Supply & Fix ceiling rose surface bakelite 65 x 35 mm three terminals PVC/polycarbonate. complete all as specified andas directed. 10 Each
125 97 Supply ,fixing and replacement of sheet metal enclouser disribution board for MCBs to be fixed 240 volts, SPN, 4 ways double door having 200 rated copper bus bar with neutral link , complete mounting on PVC board in suitable size minium one inch thick or concelled in Wall complete all as specified and directed. 3 Each
126 98 Supply and fxing MCB , SPN , 40Amps, 10 KA, 240 volts complete. 3 Each
127 99 Supply and fxing MCB , SP, 6 to 32 Amps, 10 KA , 240 volts complete. 6 Each
128 100 Supply , Lay & Jointing with flexible rubber gaskets push on type joints Ductile Iron pipe class K 9 ISI marked with centrifugally lined with cement mortar complete in trenches of size 200 mm dia of make Electro steel/Jindal/Lanco 22 RM
129 101 Supply , Lay & Jointing with flexible rubber gaskets push on type joints Ductile Iron pipe class K 9 ISI marked with centrifugally lined with cement mortar complete in trenches of size 150 mm dia of make Electro steel/Jindal/Lanco 26 RM
130 102 Supply , Lay & Jointing with flexible rubber gaskets push on type joints Ductile Iron pipe class K 9 ISI marked as per IS 8329-2000 with centrifugally lined with cement mortar complete in trenches of size 100 mm dia of make Electro steel/Jindal/Lanco 98 RM
131 103 S&F PVC/Fibre Separator for LT Lines 1100 Volts OH Conductor 2/3/4 Wire system for horizontal spacing of Conductor, fixing with Nuts, Bolts, Washers, etc., complete all as specified and as directed. 50 EACH
132 104 Supply and fixing ON LOAD Change over switch 4 Pole, 800 Amps suitable for 415 Volts, 80 KA including disconnecting and taking down existing unserviceable complete all as specified and directed by Engr-in-Charge. 1 Each
133 105 Supply and fixing ACB 4 Pole, 415 V, Manual Drawout type with microprocessor release of capacity 800 Amps including disconnecting and taking down existing unserviceable complete all as specified and directed by Engr-in-Charge. 1 Each
134 106 Supply and replace LED post top light fitting of 40 Watt capacity with IP 65 protection, 6000 K, suitableitable for pole dia upto 75 mm complete all as directed by Engineer-in-charge. Make: CAT No.LHEVBBP7IN6J040 of Havells India Ltd or its equivalent in Philips/ Surya Roshini / Wipro/ GE/ Bajaj.Note the Rate is enclusive of all necessary items required for fitting at site. 2 Each
135 107 Supply and replace LED street light fitting of 60 Watt capacity with IP 66 protection, 6500 K, with accessories suitable for pole dia upto 40 mm complete all as directed by Engineer-in-charge. \nMake: Havells India Ltd or its equivalent in Philips/ Surya Roshini / Wipro/ GE/ Bajaj. 8 Each
136 108 M&L for taking out existing airblower of 15 to 20 HP capacity for servicing and repair by disconnecting motor and blower from pipe line and removing of all parts like bearing, bushes, impeller, shaft etc., cleaning all surfaces and scales/ sludge/ dirt/ formed inside/out side pumpset/blower etc,lubricating/ greasing at proper places and re-fixing in position with all serviceable parts including painting with one coat of anti corrosive paint over red oxide primer and writing MES /SM No and testing and commissioning complete all as directed by Engineer-in-charge.\nNOTE :- Cost of Spares such as shaft, ball bearing, metal coupling and gland packing etc is included in above coated rate. 1 Job
137 109 Supply and replacement of 20 mm dia high density polythene pipe (HDPE) of pressure rating 6 Kg/ Sqcm , laid in trenches etc, including making leak proof joints complete all as specified and directed by Engineer-in-Charge. 24 RM
138 110 All as per SL item No.109 above but of 25 mm dia 30 RM
139 111 All as per SL item No.109 above but of 40 mm dia 30 RM
140 112 All as per SL item No.109 above but of 50 mm dia 30 RM
141 113 M&L for structural steel work such as beams, angles, channels, flats etc., bent to shape and MS sheet for chamber covers including nuts, bolts and necessary including dismantling complete all as directed. 350 KG
142 114 Supply and lay in replacement PVC insulated PVC unsheathed cable wire armoured, electric control cables with stranded copper conductor of size 185 Sqmm single core. 62 RM
143 115 Supply and replace notice board of overall size shall be 1200mm long, 75mm deep and 600mm high, 25mmx75mm particle board frame of commercial face with 6mm thick MDF edging alround shall be provided, 19mm thick soft wood board shall be fixed in side the frame over which best quality green baize cloth shall be fixed, Aluminum flat of 63mmx 3.25mm shall be provided alround at the back of the board, on front side 22mmx10mm aluminum channel shall be provided in side of particle board frame to house 4mm thick glass shutter (sliding type with necessary fittings) complete all as specified and directed by Engr-in-Charge. 10 Each
144 116 S & F cable junction box oop in loop out box thermoplastic poly carbonate IP 66/67 weather proof of size 205x255x112 mm, 3mm thick and including provision of backlite terminal blocks 3 phase 32 Amps and MCB SP 6 amps -01 No. with suitable pole mounding brackets as per site requirement, fixing arrangements with glands suitable size of UG cable up to the size 10 to 25 Sqmm 3.5/4 core complete all as specified and directed by Engr-in-charge. Make: Hensel / Schnider / Emitter. 2 Each
145 117 S & F HN HRC fuse Link of rating 630 Amps, size III, 415 V, 50/60 Hz. Complete all as specified and as directed. Make L & T Cat part No SF94437OOO or its equivalent 3 Each
146 118 S & F HB 800 fuse Base of rating 800 Amps, 500 V AC Single pole, Complete all as specified and as directed. Make L & T Cat part No SK91051OOOO or its equivalent 3 Each
147 119 Supply, install, testing and commissioning of cubical housing cabinet type LT feeder pillar box Outdoor type, plinth mounted, totally enclosed dust and vermin proof openable from both front and rear side made out of 3.15 mm thick CRCA mild steel Sheet overall size to accomodate the following and built upon suitable size angle iron frame work, having front and rear hinged doors, lifting lugs (2 Nos), earthing strips at rear side , bottom detachable gland plate complete with suitable size zinc plated and passivated nut, bolts, spring and washers and apply spray paint with powder coated painting, panel should be suitable for 415 volts, 50 Hz, 3 phase 4 wire system and shall be completed with 1200 amps capacity solid aluminium bus bar having 1100 volts grade sleaving and internal connection should be provided with aluminium strips of suitable size and to accomodate and including the following MCCBs, necessary foundation work including taking down old one complete all as specified and as directed. 1 Each Job
148 119.01 The rate is deemed to be inclusive of necessary Bus Bar, Volt meter, Ammeter, control wiring, CT, instrument fuse holder, LED indication lamps etc.
149 119.02 (a) Incomming :-
150 119.03 (I) ON- LOAD change over switch 1200 Amps, operated panel mounting type, 415 Volts, 50 Hz - 01 No, Make L & T or its equivalent to ABB/Legrand (II) ACB 1000 Amps, 4 pole, 440V micro processer based - 01 Nos Make L&T/ ABB/ Legrand/Scheneider (ii) LCD Multi function meters.- 01 Nos Make L&T, ABB/ Legrand/Scheneider (iii) Indiacator lamp and holder LED Type (RYB) suitable for panel complete
151 119.04 (b) Outgoing :-
152 119.05 (i) ACB 800 Amps, 4 pole, 440V micro processer based - 03 Nos Make L&T/ ABB/ Legrand/Scheneider
153 119.06 (II) MCCB 4 pole 630 Amps 50 KA (Incoming) - 01 No
154 119.07 (III) MCCB 4 pole 400 Amps 36 KA (outgoing) - 01 Nos
155 119.08 (IV) MCCB 4 pole 250 amps 16 KA (outgoing) - 01 No
156 119.09 (V) MCCB 4 pole 63 amps 16 KA (outgoing) - 02 No
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail