Addn Altn To Lt Panel Provn Of Fire Alarm System At Ns 97 And Fire Fighting System At Ns 88 At Mo Mb Ghatkopar Under Ge Nw Bhandup, GHATKOPAR-Maharashtra

Military Engineer Services-MES has published Addn Altn To Lt Panel Provn Of Fire Alarm System At Ns 97 And Fire Fighting System At Ns 88 At Mo Mb Ghatkopar Under Ge Nw Bhandup. Submission Date for this Tender is 17-02-2021. Fire Alarm Systems Tenders in GHATKOPAR Maharashtra. Bidders can get complete Tender details and download the document.




Tender Notice

26674561
Corrigendum : Addn Altn To Lt Panel Provn Of Fire Alarm System At Ns 97 And Fire Fighting System At Ns 88 At Mo Mb Ghatkopar Under Ge Nw Bhandup
Open Tender
Indian
Maharashtra
GHATKOPAR
17-02-2021

Tender Details

Addn Altn To Lt Panel Provn Of Fire Alarm System At Ns 97 And Fire Fighting System At Ns 88 At Mo Mb Ghatkopar Under Ge Nw Bhandup

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 02-Feb-2021 AMDT IN DATE 1 Date 10-02-2021
2 03-Feb-2021 AMDT IN BOQ BOQ 10-02-2021
3 10-Feb-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 17-02-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 87000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: ADDN / ALTN TO LT PANEL, PROVN OF FIRE ALARM SYSTEM AT NS-97 AND FIRE FIGHTING SYSTEM AT NS-88 AT MO (MB) GHATKOPAR UNDER GE (NW) BHANDUP
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Supply and fixing, install, test and commissioning of LT Feeder pillar box outdoor type totally enclosed with front and rear opening hinged doors with canopy sloped top projected and raised platform of suitable sizes weather dust vermin proof made out of 3 mm thick stainless steel sheet, factory made powder coated as approved colour, aluminum bus bar suitable for 3 phase 4 wire LT, AC, 50Hz, 433 volts, 1000 Amps rating capacity RYBN insulated with sleeved insulation complete with multifunctional meter LED type by showing Amps, volts, frequency etc along with suitable size of CT on outgoing, indicating lamp RYB , complete internal wiring with suitable size of PVC insulated copper conductor cable, including cable glands and lugs for incoming and out going cables as per required sizes, PCC platform made out of 1:2:4 type B1 and pedestal of 30 cm height from GL with suitable nut, bolts, washers etc., all as specified and directed for suitable to accommodate the following items including supply and fix following items and all as specified and directed by dismantling existing unserviceable LT panel complete with LT panel made by CPRI approved manufacturer Location : Deltic Sub Stn\nIncoming\n[a] Air Circuit Breaker 630 Amp, 4P MDO 50 KA draw out type, LCD Display, 4Nos auxiliary contact (2No +2NC)+1Nos fault Trip indicator, shunt trip control, under voltage coil, mechanical inter locking with lock and key arrangements of make Legrand cat No DMX3 028730 frame 1 or equivalent in Siemans, Schneider\n(i) Neutral protection settable 0-50-100% of Ir. (ii) Individual LED indication for faults (L, S, I) \n(iii) Current Metering. (iv) Over load pre alarm and overload alarm at 0.9Ir and 1.05 Ir\n(v) Inbuilt thermal memory. (vi) Over temperature protection to protect the release with first alarm (75%) and then tripping (95%). (vii) Last tripping and data and last 20 trip data\n(viii) Date & time stampping for backup. (ix) RS 485 communicating part\n(x) Release shall be with battery backup. (xi) Drawout padlocking arrangements\n(xii) Inbuilt logic selecting/zone selecting to assit selectivity between ACB-ACB as well as Schneider/Siemens.-02 Nos.\n 1 1 Each Job
2 1.01 Outgoing\n[a] MCCB 4 pole630 Amps with breaking capacity 36KA TM Buscoupler adjustable type with extended terminals - 01No's \nMake: Legrand/Schneider/siemens.\n[b] MCCB 4 pole 500 Amps with breaking capacity 36KA adjustable type with extended terminals- 03No's \nMake: Legrand/Schneider/siemens.\n[c] MCCB 4 pole 63 Amps with breaking capacity 16KA adjustable type with extended terminals- 06 No's\nMake :Legrand/Schneider/siemens.\n[d] MCCB 4 pole 40 Amps with breaking capacity 16 KA adjustable type with extended terminals- 02 No's \nMake : Legrand/Schneider/siemens.\n(e) 600/5Current Transformers-06 Nos\n(f) Change over switch 500 Amp Make : Havells/Schneider/siemens\n(g) Multi functional Meter-02 (h) LED RYB indicator lamps-02 Sets (06 Nos)\n
3 2 Supply and fixing, install, test and commissioning of LT Feeder pillar box outdoor type totally enclosed with front and rear opening hinged doors with canopy sloped top projected and raised platform of suitable sizes weather dust vermin proof made out of 3 mm thick stainless steel sheet, factory made powder coated as approved colour, aluminum bus bar suitable for 3 phase 4 wire LT, AC, 50Hz, 433 volts, 600 Amps rating capacity RYBN insulated with sleeved insulation complete with multifunctional meter LED type by showing Amps, volts, frequency etc along with suitable size of CT on outgoing, indicating lamp RYB , complete internal wiring with suitable size of PVC insulated copper conductor cable, including cable glands and lugs for incoming and out going cables as per required sizes, PCC platform made out of 1:2:4 type B1 and pedestal of 30 cm height from GL with suitable nut, bolts, washers etc., all as specified and directed for suitable to accommodate the following items including supply and fix following items and all as specified and directed by dismantling existing unserviceable LT panel complete with LT panel made by CPRI approved manufacturer Location : Opp NS-9\nIncoming\n[a] MCCB 4 pole 320 Amps with breaking capacity 36KA adjustable type with extended terminals- 01No's Make: Legrand/Schneider/siemens.\nOutgoing\n[a] MCCB 4 pole160 Amps with breaking capacity 36KA adjustable type with extended terminals- 01No's Make: Legrand/Schneider/siemens.\n[b] MCCB 4 pole 100 Amps with breaking capacity 25 KA adjustable type with extended terminals- 06 No's Make : Legrand/Schneider/siemens.\n[c] MCCB 4 pole 40 Amps with breaking capacity 16 KA adjustable type with extended terminals- 02 No's Make : Legrand/Schneider/siemens.\n(d) 320/5Current Transformers-03 Nos\n(e) Multi functional Meter-01 (f) LED RYB indiacator lamps-01 Set (03 Nos)\n\n 1 Each Job
4 3 Supply and fixing, install, test and commissioning of LT Feeder pillar box outdoor type totally enclosed with front and rear opening hinged doors with canopy sloped top projected and raised platform of suitable sizes weather dust vermin proof made out of 3 mm thick stainless steel sheet, factory made powder coated as approved colour, aluminum bus bar suitable for 3 phase 4 wire LT, AC, 50Hz, 433 volts, 500 Amps rating capacity RYBN insulated with sleeved insulation complete with multifunctional meter LED type by showing Amps, volts, frequency etc along with suitable size of CT on outgoing, indicating lamp RYB , complete internal wiring with suitable size of PVC insulated copper conductor cable, including cable glands and lugs for incoming and out going cables as per required sizes, PCC platform made out of 1:2:4 type B1 and pedestal of 30 cm height from GL with suitable nut, bolts, washers etc., all as specified and directed for suitable to accommodate the following items including supply and fix following items and all as specified and directed by dismantling existing unserviceable LT panel complete with LT panel made by CPRI approved manufacturer Location: Logo office.\nIncoming:\nMCCB 4 pole 250 Amp with breaking capacity 36 KA adjustable type with exended terminals -01 No\nOutgoing\n[a] MCCB 4 pole 160 Amps with breaking capacity 25KA adjustable type with extended terminals- 01 No Make: Legrand/Schneider/siemens.\n[b] MCCB 4 pole 100 Amps with breaking capacity 16 KA adjustable type with extended terminals- 06 Nos, Make : Legrand/Schneider/siemens.\n[c] MCCB 4 pole 63 Amps with breaking capacity 16 KA adjustable type with extended terminals- 02 Nos Make : Legrand/Schneider/siemens.\n(d) 320/5Current Transformers-03 Nos.\n(e) Multi functional Meter-01 \n(f) LED RYB indiacator lamps-01 Set (03 Nos) 1 Each Job
5 4 Supply and fixing, install, test and commissioning of LT Feeder pillar box outdoor type totally enclosed with front and rear opening hinged doors with canopy sloped top projected and raised platform of suitable sizes weather dust vermin proof made out of 3 mm thick stainless steel sheet, factory made powder coated as approved colour, aluminum bus bar suitable for 3 phase 4 wire LT, AC, 50Hz, 433 volts, 600 Amps rating capacity RYBN insulated with sleeved insulation complete with multifunctional meter LED type by showing Amps, volts, frequency etc along with suitable size of CT on outgoing, indicating lamp RYB , complete internal wiring with suitable size of PVC insulated copper conductor cable, including cable glands and lugs for incoming and out going cables as per required sizes, PCC platform made out of 1:2:4 type B1 and pedestal of 30 cm height from GL with suitable nut, bolts, washers etc., all as specified and directed for suitable to accommodate the following items including supply and fix following items and all as specified and directed by dismantling existing unserviceable LT panel complete with LT panel made by CPRI approved manufacturer Location: Near Security bldg Main Gate.\nIncoming:\nMCCB 4 pole320 Amp with breaking capacity 36 KA adjustable type with exended terminals -01 No Make: Legrand/Schneider/siemens.\nOutgoing\n[a] MCCB 4 pole 160 Amps with breaking capacity 25KA adjustable type with extended terminals- 04 Nos Make: Legrand/Schneider/siemens.\n[b] MCCB 4 pole 100 Amps with breaking capacity 25 KA adjustable type with extended terminals- 02 Nos Make : Legrand/Schneider/siemens.\n(c) 320/5Current Transformers-03 Nos\n(d) Multi functional Meter-01\n(e) LED RYB indiacator lamps-01 Set (03 Nos)\n\n 1 Each Job
6 5 Supply and fixing, install, test and commissioning of LT Feeder pillar box outdoor type totally enclosed with front and rear opening hinged doors with canopy sloped top projected and raised platform of suitable sizes weather dust vermin proof made out of 3 mm thick stainless steel sheet, factory made powder coated as approved colour, aluminum bus bar suitable for 3 phase 4 wire LT, AC, 50Hz, 433 volts, 500 Amps rating capacity RYBN insulated with sleeved insulation complete with multifunctional meter LED type by showing Amps, volts, frequency etc along with suitable size of CT on outgoing, indicating lamp RYB , complete internal wiring with suitable size of PVC insulated copper conductor cable, including cable glands and lugs for incoming and out going cables as per required sizes, PCC platform made out of 1:2:4 type B1 and pedestal of 30 cm height from GL with suitable nut, bolts, washers etc., all as specified and directed for suitable to accommodate the following items including supply and fix following items and all as specified and directed by dismantling existing unserviceable LT panel complete with LT panel made by CPRI approved manufacturer Location : Opp NMC Bldg\nIncoming:\nMCCB 4 pole 250Amp with breaking capacity 36 KA adjustable type with exended terminals -01 No Make: Legrand/Schneider/siemens.\nOutgoing\n[a] MCCB 4 pole 63 Amps with breaking capacity 25KA adjustable type with extended terminals- 04 Nos Make: Legrand/Schneider/siemens.\n[b] MCCB 4 pole 40 Amps with breaking capacity 16 KA adjustable type with extended terminals- 01 No Make : Legrand/Schneider/siemens.\n(c) 320/5Current Transformers-02 Nos\n(d) Multi functional Meter-01 \n(e) LED RYB indiacator lamps-01 Set (03 Nos)\n\n 1 Each Job
7 6 Supply installation, testing and commissioning of FAST ELECTRODE maintenance free Chemical Earthing of Dual Pipe Technology, each of 3 Meter long with Outer Pipe Diameter of 88mm (galvanized for 80-120 micron and wall thickness 1.80mm) and Inner Pipe diameter 48mm (galvanized for 80-120 micron and wall thickness 2.60mm). There shall be terminal of size 75 x 5.20mm for connection with two holes of 14mm diameter. FAST ELECTRODE shall be duly filled with the highly conductive, Non Magnetic, Non Corrosive material and duly sealed at both ends with lead terminal of 75x5.2mm at top. The ELECTRODE shall be of 'make' having approval of CPRI (Central Power Research Institute), Govt of India for a minimum short circuit current of 42 KArms for 1 Second with initial pick of 88.2 KA. The FAST ELECTRODE Earth Enhancing Compound (minimum 25Kg) shall be pored on alround the electrode. The chemical compound to be used shall be as per the manufacturer's instructions of 'Electrode' and as also certified by any BIB (Bureau of Indian Standards) accredited laboratory. Make : Fast Electrode or equivalent as approved by the GE.\nNotes:- (i) The contractor shall procure the above materials either directly from the manufacturer(s) or their authorized dealers only and shall produce the original purchase vouchers alongwith original manufacturer's test certificates and other authenticated documents in compliance of the provisions as mentioned in the above item. Also all the requisite testing as specified above, in relevant IS and as directed by the GE shall be got done by the contractor. Cost of all the above elements shall be deemed to be included in the contractor's quoted rates.(ii) Any additional quantity of Earth Enhancing Compound in case required to obtain the desired results, the same also be provided by the contractor without any additional cost to the Govt. and quoted rates of above item shall be deemed to include the above element also. 10 Each Job
8 7 Excavation in trenches n. exc 1.5 mtr wide and n. exc 1.5 mtr depth for laying underground cable and getting out in hard / dense soil complete all as specified and directed including road cutting and making good. 8 Cum
9 8 Returning and re-filling including spreading, levelling, watering and well ramming in layers n. exc 25cm, complete all as specified and directed 6 Cum
10 9 Removal of excavated material / soil n. exc 50 mtr and depositing where directed at a level not exc. 5m above from starting point, complete all as specified and directed 1 Cum
11 10 Supplying and providing plain cement concrete in foundations, filling and mass concrete with type C2 1:3:6 ( 40 mm graded aggregate) and finishing the surface even and smooth without using extra cement, complete all as specified and directed. 1 Cum
12 11 Supply, Installation, Testing and commissioning of Microprocessor based Multi-loop, True Peer-to-Peer Networkable Addressable Fire Alarm Control Panel for 4 loop with 2 loop card with minimum 600 characters LCD display, 4000 event plus 1000 alarm log history events, QWERTY keypad for programming. The panel shall be equipped with sufficient numbers of loops considering 20% spare capacity in each loop. Each loop shall have a capacity of minimum 300 analog addressable devices. The panel shall work in degrade mode in case of CPU failure. Four access levels, flash EPROM, 240 volts AC power supply, automatic battery charger, 2 x 12 Volts, DC sealed lead acid batteries sufficient for 48 hours normal working and 02 hrs in alarm condition. The fire alarm system shall comply with requirements of NFPA Standard 72 for Protected Premises Signaling Systems unless modified and specified otherwise in these tender documents. The system shall be electrically supervised and monitor the integrity of all conductors. Panel and detector shall be of same make as approved by the GE and all sensor shall be battery backed up. Panel shall be Underwriters Laboratories listed, semi flush type and / or surface mount type as per requirement all as directed, Make : Notifier\nNOTE : FOR ITEM NO 5 AND OTHER RELEVANT ITEMS OF DETECTORS : THE PANEL AND DETECTORS SHALL BE OF SAME MAKE AS APPROVED BY THE GE.\n 1 Each
13 12 Supply, installation testing and commissioning of additional loop card of 300 point for above panel (Item No-11) all as specified and directed card shall be underwriters laboratories listed. \nMake: APOLLO/NOTIFIER/EDWARD. 2 Each
14 13 Programming & commissioning of Graphics User Interface for Monitoring & Control of complete Fire. The GUI based main network software shall network with other panels on True Peer-to-Peer network. It shall be capable of graphically representing each facility being monitored with floor plans and icons depicting the actual locations of the various systems and / or sensors’ locations. It shall have the facility to change the sensitivity of any detector. 1 Each Job
15 14 Supply, installation, testing and commissioning of Addressable Multi-criteria Photo-Thermal Detector with sensitivity range of 0.5 to 4.0% obs/ft. The intelligent multi criteria detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the event of a fire situation. It shall also include the inherent ability to distinguish between a fire condition and a false alarm condition by examining the characteristics of the thermal and smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena. The detector shall have twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal switches. The detector shall be designed to meet UL268, 7th Edition Make : Notifier 19 Each
16 15 Supply, installation, testing and commissioning Addressable Manual Call Point (Pull down / Break Glass Type). The device shall have an LED which shall blink in normal state & get steady on activation to monitor the health status of the device and shall be Underwriters Laboratories Listed, semi flush type, Make: Notifier 5 Each
17 16 Supply, installation, testing and commissioning Addressable Sounder cum Strobe rated at 75 dB at 3 metre for Audible annunciation and 75cd flashing at 1 Hz for visual indication, Device shall be Underwriters Laboratories listed. Make Notifier 5 Each
18 17 Supply, installation, testing and commissioning of addressable type Hooter cum Flasher outdoor weather proof type, rated at 75 dB at 3 metre for Audible annunciation and 75cd flashing at 1 Hz for visual indication with and including Control Module, complete all as specified and directed, Make of Hooter : FCG/ Baliga, Make of Control Module : Notifier\nNotes for item No 15 : (i) The hooter shall be Central Mining Research Institute and Petroleum & Explosives Safety Organization approved.\n(ii) The Control Module shall be UL Listed.\n 1 Each
19 18 Supply & Laying 32mm dia HDPE Pipes (PE-03 grade) (class-3) of pressure rating 06 Kgf/cm2 in trenches etc for cable protection etc, complete all as specified and directed.\nNote : Excavation and earth work shall be measured and paid for separately. \n 450 RM
20 19 Supply and Laying of 6 Core Multi Mode Optic Fiber Cable Full armoured in the trenches/ fixed along wall/ floor/ ceiling with and including GI saddles, clamps, Nylon cable ties, complete all as specified and directed, Make : Polycab/ Finolex/ Havells\nNote : Excavation and earth work, protection pipes shall be measured and paid for separately.\n 450 RM
21 20 Supply and Laying of 2 Core 1.5 Sqmm copper conductor, GI armoured, FRLS cable confirming to IS : 1554 (Part-I) in trenches/ fixing along wall/ floor/ ceiling with and including GI saddles, Clamps, Nylon cable ties etc, complete all as specified and directed, Make : Polycab/ Finolex/ Havells\nNotes : (i) Excavation and earth work, protection pipes shall be measured and paid for separately.\n(ii) Cable shall be as per Fire Norms & red in colour.\n 1150 RM
22 21 Supply and Laying of 4 Core 1.5 Sqmm copper conductor, GI armoured, FRLS cable confirming to IS : 1554 (Part-I) in trenches/ fixing along wall/ floor/ ceiling with and including GI saddles/ clamps, Nylon cable ties etc, complete all as specified and directed, Make : Polycab/ Finolex/ Havells\nNotes : (i) Excavation and earth work, protection pipes shall be measured and paid for separately.\n(ii) Cable shall be as per Fire Norms & red in colour.\n 250 RM
23 22 Supply and installation of perforated cable tray made of 2mm thick GI sheet, 150mm x 15mm hight width on walls near panels, complete all as specified and directed, Make: Profab, Legrand, Tecnofab or any other ISI Marked as approved by the GE 20 RM
24 23 Supply and Laying of 40mm bore GI pipe, medium grade, with and including GI fittings, in trenches for cable protection (for road crossing etc), complete all as specified and directed. \nNote : Excavation and earth work shall be measured and paid for separately.\n 6 RM
25 24 Supply and fixing Fire Exit Signages, complete all as specified and directed, Make : Prolite Autoglow or equivalent as approved of the GE. 4 Each
26 25 Providing and fixing in position the signages " FIRE ORDER", on 3mm thick "Opaque" PVC foam board of size 3' x 4'. On the board, PVC non-reflective self adhesive vinyl painted matter as per below shall be pasted. (A) ALERT THE SECURITY AT SECURITY ROOM BY ACTUATING MANUAL CALL POINT LOCATED AT STRATEGIC LOCATION. (B) EVACUATE THE OCCUPANTS BY USING THE FIRE EXITS & EMERGENCY EXITS ONLY ASSEMBLE AT VARIOUS ASSEMBLY POINTS. (C) IF POSSIBLE TRY TO EXTINGUISH THE FIRE BY USING THE NEAREST/SUITABLE PORTABLE EXTINGUISHER OR WATER FROM NEAREST WET RISER. (D) BE CALM, DO NOT GIVE ANY ROOM FOR PANIC, WALK, DO NOT RUN. (E) IF YOU ENCOUNTER SERIOUS DIFFICULTY IN EVACUATION, STAY IN YOUR PLACE AND TRY TO ATTRACT ATTENTION OF RESCUE TEAM, Make : Prolite Autoglow Or equivalent as approved by the GE. 1 Each Job
27 26 Supply, installation, testing and commissioning of Isolator module to electrically isolate different section of detetor loop with and necessary back box & accessories, complete all as specified and directed, The isolator module shall be UL Listed, Make :- Notifier.. 4 Each Job
28 27 Supply and providing of electrical earthing (instrumentation ground) for Fire Alarm Panel, complete all as specified and directed. 2 Each
29 28 Supply and fixing Electrically driven pump set as per specification. Motor TEFC type, 2900 rpm, 415V, 50 cycle frequency 3 phase class ‘F’ insulation, I.P. 55 protection, 15kW, starting on star delta starter. The Pump shall be horizontal, end suction, top discharge. The pump shall have cast iron casing, bronze impeller, steel shaft with common base frame capable of discharging 1620 LPM at 40 meter head, complete all as specified and directed. 1 Each Set
30 29 Supply and fixing Cast Iron Butterfly isolation valve (PN:1.6) as per specification with necessary flanges, nut, bolts & washers, painting, etc. complete as required of size 150 mm dia, complete all as specified and directed. 7 Each
31 30 All as above but 80 mm bore, complete all as specified and directed 2 Each
32 31 Supply and fixing C.I. Non-return valves as per IS:5312( PN 1.6) Dual Plate C&G Make type with required flanges, nuts, bolts and gaskets etc. of size 150 mm dia, complete all as specified and directed. 2 Each
33 32 All as above but 80 mm bore, complete all as specified and directed 1 Each
34 33 Supply and fixing Gun metal Fire yard Hydrant single landing valve with 80 mm N.B. flanged inlet, brass spindle controlled 63 mm dia female instantaneous outlet type. G.M. coupling, blank cap, chain, twist release type lug & all accessories conforming to IS:5290. Including fixing with anchor fastener and flanged tapping from wet riser and providing pressure gauge with gun metal ball valve complete as required. 7 Each
35 34 Hose cabinet consists of 2 Nos RRL Type-A hoses of 63mm Dia x 15 meters long with heavy quality Stainless steel male coupling as per IS: 903 combined with 1 No of nozzle and 1 No of branch pipe. The hose cabinet shall be of reputed manufacturer with MS sheet (16 SWG thick) of size 750x600x250 with glass fronted door, painted in red out side and white in inside, hose boxes along with GI support arrangements as per specifications 7 Each
36 35 Providing & fixing swinging type First Aid hose reel in red colour drum with 36 mts long and 20 mm dia heavy duty "DUNLOP" rubber water hose, 20 mm dia globe valve stop cock, terminating with G.M. coupling & nozzle of 6mm outlet with shut off valve confirming to IS 8090 - 1976 complete with MS socket for tap-off, drum and brackets (including painting) for fixing on wall with anchor fastener, bolts & nuts conforming to IS:884-1969 complete as required. 6 Each
37 36 Gun metal fire brigade connection (suction collecting head) consisting of 2 nos. 63 mm dia instantaneous type male coupling with built-in check valves, 1 no. 150 mm dia sluice valve, 1 no. 150 mm dia non-return valve and 150 mm dia flanged outlet complete with bolts, nuts and rubber inserting as required and as per IS 904 1963. 1 Lot
38 37 Gun-metal Fire brigade suction hose coupling (draw-out connection) with nut for female coupling as per IS 902-1974 complete with 80mm dia GI suction pipe and 80 mm dia foot valve (to be connected to static tank). Provision of GI drop pipe and foot valve shall be made in all the fire water static storage tank (4 nos) (GI pipe to be paid separately through appropriate item while cost of foot valve to be included.) 1 Lot
39 38 M& L for MS Heavy 'C' Class pipes conforming to IS 3589 for 200NB & above and IS 1239 for 150NB & below with necessary joints and fittings (heavy class forged fittings of IS standards) including cutting the pipes to correct length, providing and welding flanges to pipe, etc as per specifications of the following diameters. Rate shall be inclusive of 1 coat of primer over that 2 coats red enamel paint as per Fire authorities requirement over all above ground pies and also inclusive of making hole in the wall, chasing, chipping, making good with plastering after completion of work, pipe sleeve of suitable higher size, sealing the sleeves with glass wool & fire sealant, etc. Cost of Steel supports for piping clamps, tie rods, brackets, nuts and bolts etc shall also be included in the quoted rate of size 150 mm dia, complete all as specified and directed. 100 RM
40 39 All as above but 100 mm dia, complete all as specified and directed. 20 RM
41 40 All as above but 80 mm dia, complete all as specified and directed. 20 RM
42 41 Supply, installation of MS Frication works for wall support in pipes, complete all as specified and directed. 250 Kg
43 42 Supply and fixing Fire pump panel, cubicle type, made out of 2 mm thick stainless steel sheet factory made powder coated as approved colour, totally enclosed IP 42,Fully automatic star/ Delta starter of suitable rating for 415V, 50 Hz, 3 Phase main electrical fire pump (APP ONE PUMP 50hp). The starter shall have ON, OFF push button, On, OFF indication lamp, complete with all accessories and internal wiring required for automatic and manual operation. INSTRUMENTS: 1 No of Three phase Digital volt Meter, ACC class 1, 1 No of Three phase digital ammeter, ACC class 1, 1 set of phase indicating lamps, LED type RYB. 1 Set of ON, OFF indicating lamps, LED type, @ set of 2A 10 KA curve cast resin CT for metering. 1 Each
44 43 Supply and fixing PVC insulated and PVC sheathed / XLPE Power cable of 1.1KV grade FRLS Aluminium / Copper conductor armoured/unarmoured cables. The cables shall be laying on the existing cable trench in ground / existing hume pipe / existing Masonry cable duct / existing cable tray and partially laid on wall/ceiling with suitable clamps & necessary fixing accessories etc. as required. Rate shall inclusive of Double compression cable gland and suitable Copper crimping sockets/lugs, crimping paste, sleeves, ferrules etc., as required
45 43.01 Supply and fixing 4 Core 10 Sqmm XLPE Aluminium Armoured Cable, complete all as specified and directed. 100 RM
46 43.02 Supply and fixing 3 Core 2.5 Sqmm PVC Copper Armoured Cable, complete all as specified and directed. 50 RM
47 44 Design, supply and laying of 40 x 6 mm GI flat run along the cable tray, complete all as specified and directed. 50 RM
48 45 Material and labour 8 gauge bare copper wires for Gland earthing, loop earthing in the existing surface/recessed steel conduit, pump earths and other equipment body earthing as required. 35 RM
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail