Repair Replacement Of Ht Switchgears Cables And Allied Works Including Repair To Plumbing Sanitary Fittings Footpath Hardstanding Plinth Protection Drain Etc In Sewage Treatment Plant At Gms Under Ge I Gos, GOPALPUR MILITARY STATION-Odisha

Military Engineer Services-MES has published Repair Replacement Of Ht Switchgears Cables And Allied Works Including Repair To Plumbing Sanitary Fittings Footpath Hardstanding Plinth Protection Drain Etc In Sewage Treatment Plant At Gms Under Ge I Gos. Submission Date for this Tender is 17-02-2021. Switch Gear Tenders in GOPALPUR MILITARY STATION Odisha. Bidders can get complete Tender details and download the document.




Tender Notice

26673581
Corrigendum : Repair Replacement Of Ht Switchgears Cables And Allied Works Including Repair To Plumbing Sanitary Fittings Footpath Hardstanding Plinth Protection Drain Etc In Sewage Treatment Plant At Gms Under Ge I Gos
National Competitive Bid
Indian
Odisha
GOPALPUR MILITARY STATION
17-02-2021

Tender Details

Repair Replacement Of Ht Switchgears Cables And Allied Works Including Repair To Plumbing Sanitary Fittings Footpath Hardstanding Plinth Protection Drain Etc In Sewage Treatment Plant At Gms Under Ge I Gos

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 01-Feb-2021 AMENDMENT Other 08-02-2021
2 06-Feb-2021 AMENDMENT1 Other 08-02-2021
3 08-Feb-2021 DATE AMEND Date 15-02-2021
4 15-Feb-2021 AMEND4 Date 17-02-2021
5 17-Feb-2021 AMEND5 Other 17-02-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 90000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: REPAIR REPLACEMENT OF HT SWITCHGEARS CABLES AND ALLIED WORKS INCLUDING REPAIR TO PLUMBING SANITARY FITTINGS FOOTPATH HARDSTANDING PLINTH PROTECTION DRAIN ETC IN SEWAGE TREATMENT PLANT AT GMS UNDER GE I GOS
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Taking up or down steel tubing and connections including cleaning if refixing required for 15 mm bore of pipe complete all as specified and directed. 35 RM
2 2 Taking up or down steel tubing and connections including cleaning if refixing required for 20 mm bore of pipe complete all as specified and directed. 45 RM
3 3 S&F GI tubes medium grade (ISI marked) with all fittings laid in trenches of 15 mm bore of pipe complete all as specified and directed. 10 RM
4 4 S&F GI tubes medium grade (ISI marked) with all fittings laid in trenches of 20 mm bore of pipe complete all as specified and directed. 15 RM
5 5 S & F 15 mm bore 3 layer PP-R pipes SDR 7.4 & SDR 11 UV stablised and anti microbial welded having thermal stability for hot & cold water supply including all PP-R plain & brass threaded PP-R fittings complete to walls, ceilings or in floors complete all as specified and directed. 15 RM
6 6 S & F 20 mm bore 3 layer PP-R pipes SDR 7.4 & SDR 11 UV stablised and anti microbial welded having thermal stability for hot & cold water supply including all PP-R plain & brass threaded PP-R fittings complete to walls, ceilings or in floors complete all as specified and directed. 20 RM
7 7 Making connection of PPR distrubtion bracnch with PPR main of following outer dia of pipe 16 to 40mm size by providing and fixing tee including cutting and making fusion joint etc complete all as specified and directed. 10 Each
8 8 Refixing old steel tubing and connections in new or old position (wall, floor, ceiling etc) of 15 mm bore of pipe complete all as specified and directed. 10 RM
9 9 Refixing old steel tubing and connections in new or old position (wall, floor, ceiling etc) of 20 mm bore of pipe complete all as specified and directed. 10 RM
10 10 Taking down bib tap / wash basin tap/ pillar tap/ stop cock/ mixture tap and refixing the same after repair and replacement of washer 15 mm bore size complete all as specified and directed. Note: spindle where required will be measured and paid separately 15 Each
11 11 S&F in repairs brass spindle short body of 15 mm bore complete all as specified and directed 5 Each
12 12 S&F in repairs brass spindle long body of 15 mm bore complete all as specified and directed 5 Each
13 13 S&F in repairs bib taps cast copper alloy with crutch or butterfly handle fancy type, screwed down, screwed for iron pipe or for brass ferrule of 15 mm bore of pipe complete all as specified and directed. 6 Each
14 14 S&F in repair Chromoium plated angle cock, cast copper alloy with crutch or butterfly handle screwed down, screwed for iron pipe or brass ferrule, 15 mm bore complete all as specified and directed. 5 Each
15 15 S&F in repairs Stop valves cast copper alloy, screwed down, high pressure with crutch or butterfly handle chromium plated fancy type screwed both ends for iron pipe or for unions for 15 mm bore of pipe complete all as specified and directed. 5 Each
16 16 S&F in repairs for 15mm bore of pipe pillar taps cast copper alloy, with capstan head chromium plated screwed down high pressure with or without lettered 'Hot' or 'cold' with long screwed shanks and fly nuts, screwed for iron pipe complete all as specified and directed. 2 Each
17 17 S&F in repair PVC waste pipe for urinal/WHB etc complete all as specified and directed. 5 Each
18 18 S&F in repairs CP 32 mm bore waste coupling of (half or full threaded) etc complete all as specified and directed. 3 Each
19 19 S&F in repairs Chromium plated grating doom 100 m dia fixed in floor in CM 1:3 complete all as specified and directed 5 Each
20 20 S&F in repairs ball valves for 20 mm bore of pipe high pressure of PTMT with Epoxy coated aluminium rod and high density plastic ball screwed for iron pipe (minimum weight 210 gms) complete all as specified and directed. 3 Each
21 21 S&F in repairs ball valves for 25 mm bore dia of pipe high pressure of PTMT with Epoxy coated aluminium rod and high density plastic ball screwed for iron pipe (minimum weight 455 gms) complete all as specified and directed. 3 Each
22 22 S&F in repairs PVC connection 15 mm size with PTMT nuts of length 450 mm complete all as specified and directed. 5 Each
23 23 S&F in repairs PVC 10 litres capacity valveless ,syphonic action type low level flushing cistern ,white including flush pipe, cantilever brackets ,inlet, ball valve, float and handle, PVC connection 15mm dia etc complete all as specified and directed. 2 Each
24 24 S & F in repairs internal fitting (syphon) for low level flushing cistern complete all as specified and directed. 2 Each
25 25 S&F in repairs flush pipe 32 mm dia of polyethylene of low or high density or PVC, for low level cistern complete all as specified and directed. 1 Each
26 26 S & F in repair PVC Tank cover for 500 Ltr capacity fixed in position with nuts and bolt complete all as specified and directed 3 Each
27 27 S & F in repair PVC Tank cover for 1000 Ltr capacity fixed in position with nuts and bolt complete all as specified and directed 2 Each
28 28 S&F in repairs Looking mirror 5.5 mm thick of selected quality glass of size 600 x 450 mm bevelled edge ,mounted on 6 mm thick AC building board or commercial plywood and fixed to wooden plug with chromium plated brass screw and cup washers including aluminium anodized frame complete all as specified and directed. 4 Each
29 29 S & F in repairs sheet Glass Shelf assembly consisting of 5.5 mm glass sheet shelf 12 cm wide with cromium plated bracket guard and railing 60 cm long complete all as specified and directed. 3 Each
30 30 Dismantling floor, hearth or wall tiling including cement mortar bedding etc (but not backing) and removing rubbish off the premises complete all as specified and directed. 50 Sqm
31 31 M&L for non skid ceramic coloured tiles of design as approved by GE 7 to 8 mm thick (square/rectangular) area of each tile exceeding 0.06 Sqm but not exceeding 0.11 Sqm in floor etc set and jointed in neat cement slurry and pointed in white or coloured cement to match with the shade of tiles including 15 mm thick screed bed in cement mortor 1:6 complete all as specified and directed. 20 Sqm
32 32 M&L for non skid ceramic coloured tiles of design as approved by GE 7 to 8 mm thick (square/rectangular) area of each tile exceeding 0.11 Sqm but not exceeding 0.18 Sqm in floor etc set and jointed in neat cement slurry and pointed in white or coloured cement to match with the shade of tiles including 15 mm thick screed bed in cement mortor 1:6 complete all as specified and directed. 10 Sqm
33 33 M&L for glazed ceramic coloured tiles 350 x 250 x 7 mm / 450 x 350 x 7 mm thick on vertical surface such as dado / skirting / risers to steps etc jointed in neat cement slurry and pointed in white or coloured cement to match surface of tiles over and including rendering 10 mm thick in cement mortor 1:4 complete all as specified and directed.\n Note- (i) The size of tiles (except thickness) may be varied during execution without any price adjustment. 20 Sqm
34 34 Demolition of Cement Concrete (unreinforced) of any description & in any position not otherwise specifically provided for complete all as specified & directed. 63.54 Cum
35 35 M&L for PCC 1:4:8 type D2 using 40mm graded stone aggregate as in foundation filling and mass concrete complete all as specified and directed. 6.96 Cum
36 36 M&L for PCC 1:2:4 type B-1 using 40 mm graded stone aggregate as in surface channels and drains complete all as specified and directed. 2.25 Cum
37 37 M&L Extra for forming fair finished drain or channel 30 cm inner girth in cement concrete, using extra cement, including forms, moulds, mitred / stopped ends etc complete all as specified and directed. 60 RM
38 38 M&L for add or deduct for each 25mm girth or part thereof over or under 30 cm inner girth in cement concrete, using extra cement, including forms, moulds, mitred / stopped ends etc complete all as specified and directed. 30 RM
39 39 Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m depth for foundation etc or for shafts, wells cesspits manholes pier holes etc not exceeding 10 Sqm on plan and not exceeding 1.5 m depth in soft /loose soil etc complete all as specified and directed 248.4 Cum
40 40 Returning, filing in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in any type of soil etc complete all as specified and directed 328.62 Cum
41 41 Removing excavated material n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point complete all as specified and directed. 128.22 Cum
42 42 M&L for 50 mm High density polyethelyene pipes (HDPE) of pressure rating 6kgf/sqcm laid in trenches complete all as specified and directed. 16 RM
43 43 M&L for hard core of gauge n exc 63 mm, deposited, spread and levelled in layers n exc 15 cm thick, watered and rammed to a true surface complete all as specified and directed. 24 Cum
44 44 M&L for 100 mm thick cement concrete 1:4:8 type D-2 using 40 mm graded stone aggregate as sub base of floor complete all as specified and directed. 160 Sqm
45 45 M&L for 50 mm thick cement concrete 1:2:4 type B-1 using 20 mm gradedstone aggregate as in path/hard standing surface finished even and smooth without using extra cement complete all as specified and directed. 80 Sqm
46 46 M&L for forming construction joints 50 mm x 10 mm wide filled with sealing compound Grade A complete all as specified and directed. 2 10RM
47 47 Demolition of cement concrete un reinforced in ground floor and paving n exc 15cm thick (below or above ground level) complete all as specified and directed. 19.25 Cum
48 48 M&L 75 mm thick cement concrete 1:3:6 type C2 using 40 mm graded stone aggregate as in sub base,floor , plinth protection etc and finishing cement concrete even and smooth without using extra cement complete all as specified and directed. 75 Sqm
49 49 M&L for PCC 1:2:4 type B-0 using 12.5 mm graded stone aggregate as in sub base flooring average 25 mm thick surface finished even and rough (as in levelling course) to receive the topping layer complete all as specified and directed. 180 Sqm
50 50 M&L for 10 mm thick heavy duty exterior designer tiles of size 300 mm x 300 mm as in floor set, jointed in neat cement slurry and pointed with grey cement and pigment complete all as specified and directed. 180 Sqm
51 51 M&L for screed bed or bedding layer of mortar 20 mm thick in CM 1:6 for laying floor finishes complete all as specified and directed. 180 Sqm
52 52 M&L chequered tile of size 200 x 200 x 18 to 20mm set and jointed in neat cement slury and pointed in grey cement and pigments to match over 20mm thick screed bed in CM 1:6 complete all as specified & directed. 80 Sqm
53 53 M&L for PCC 1:2:4 type B-1 using 20 mm graded stone aggregate as in lintels upto 1.5 m clear span, coping, benching, bed block, lintel band, plinth courses etc and similar work including weathering,slightly rounded or chamfered angles and throating including necessary form work complete all as specified and directed. 1.5 Cum
54 54 M&L for Sand filling under floors or in foundations including watering and consolidation complete all as specified and directed. 6 Cum
55 55 S&F machine pressed precast concrete interlocking paver block any shape & size conforming to IS 15658-2006 of 60 mm thickness, M-35 Grade with grey cement & pigment complete all as specified & directed. 120 Sqm
56 56 Demolition of RCC of any description and in any position not other wise specially provided for reinforcement cut as required to facilitate demolition complete all as specified and directed. 4 Cum
57 57 M&L for pre cast cement concrete 1:2:4, type B-1, using 20mm graded stone aggregate as in cover slabs (for manholes etc) and similar articles with plain faces, set in CM 1:4 complete all as specified and directed. 4 Cum
58 58 M&L for Mild Steel TMT bar 10mm dia and over cut to length bent to shape required including cranking, bending spirally for hoping for columns hooking ends and binding with & including Mild Steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and directed. 628 Kg
59 59 M&L for TMT Bars 5 mm dia & over upto & including 10 mm dia in stirrups, spaces & binders, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends & binding with & including mild steel wire (annealed) not less than 0.90mm dia or securing with clips complete all as specified & as directed. 175.84 Kg
60 60 Dismantling wrought iron or mild steel work of any description not otherwise provided for complete all as specified and directed. 9 Per Quintal
61 61 M&L for Fe 410-W (Gde E-250 quality A) Framed work as in doors or gates of angle or other section with gusset plates,rails,braces etc complete,drilled for fixing of steel sheeting or other covering. Doors,etc to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings ( exclusive of steel sheeting or other covering, running rails and guides) and hanging; also fastening anf fixing complete all as specified and directed 900 Kg
62 62 M&L preparation of new or previously untreated steel surfaces of any description n exc 10cm in width or girth and priming with red oxide zinc chrome and applying two coat of synthetic enamel paint complete all as specified and directed. 45 per 10 RM
63 63 M&L for two coats synthetic enamelled paint to new steel surfaces after preparation over a coat of red oxide primer area over exc 10cm in width or girth etc complete all as specified and directed. 75 Sqm
64 64 Demolition of brick work or stone/boulder masonry built in cement mortar including all quoins, arches, pillars etc complete all as specified and directed. 4.6 Cum
65 65 M&L Brick work using fly ash bricks straight or curved on plan exc 6m mean radius built in cement mortar 1:6 complete all as specified and directed. 4.6 Cum
66 66 Taking down cement plaster on brick or concrete surface including racking out joints, hacking for key, scrubbing down with water etc complete all as specified and directed. 100 Sqm
67 67 M&L for rendering 15mm thick in CM 1:6 on brick or concrete surface, finishing even and smooth without using extra cement complete all as specified and directed. 146 Sqm
68 68 M&L for preparing new plastered or unplastered surfaces of walls and applying two coats of cement based paint complete all as specified and directed 73 Sqm
69 69 M&L for complete removal of existing treatment on walls and applying two coats of cement based paint complete all as specified and directed 2000 Sqm
70 70 M&L for preparing new plastered or unplastered surfaces of walls and applying three coats of white wash complete all as specified and directed 43 Sqm
71 71 M&L for preparation of newly plastered surfaces of walls and applying two coat of oil bound distemper over a coat of chalk whiting complete all as specified and directed. 30 Sqm
72 72 M&L preparation of old painted surfaces of walls and applying one coat of cement based complete all as directed by Engineer-in-Charge 2500 Sqm
73 73 M&L preparation of old painted surfaces of walls and applying one coat of white wash complete all as specified and as directed by Engr-in-Charge 800 Sqm
74 74 M&L preparation of old painted steel surfaces of any description n exc 10cm in width or girth and priming with red oxide zinc chrome and applying two coat of synthetic enamel paint complete all as specified and as directed by Engineer-in-Charge 200 per 10 RM
75 75 M&L preparation of old painted steel surfaces of any description not other wise described over 10cm width or girth and applying one coat of synthetic enamel paint complete all as specified and as directed by Engineer-in-Charge 200 Sqm
76 76 M&L preparation of old painted surfaces and applying one coat of anti fungal weather coat paint on walls complete all as directed by Engineer-in-Charge 400 Sqm
77 77 M&L for preparation of old painted surfaces of wood and wood based surfaces of any description, over 10 cm in width or girth and apply one coat of synthetic enamel paint complete all as specified and directed. 1000 Sqm
78 78 S&F 110mm dia PVC (SWR) pipes single socketed, in any length with rubber ring joints, laid in trenches or in floors complete all as specified and as directed 10 RM
79 79 S&F 110mm bore PVC (SWR) bends any radius complete all as specified and as directed 3 Each
80 80 Demolition of existing sunken water proofing treatment/cement plaster/cement concrete any descripltion and removing the debris from site n exc 150 m from site complete all as specified and directed. 7.6 Cum
81 81 M & L for rendering 10 mm thick CM 1:3 surface as in roof with 3% integral water proofing compound by the weight of cement complete all as specified and directed 217 Sqm
82 82 Supply only cement concrete type B1 1:2:4 (20 mm graded agg) as in padding concrete/coving for in Jn of sunken floor and vertical wall or to maintain proper slope on roof chamfored on edge complete all as specified and directed. 5.43 Cum
83 83 M&L for repair and caliberation of VCB/RMU any type/cap upto 630A cap indoor/outdoor HT panel with replacment of minor spares/ auxilary contacts of manual closing/charging mechanisam, motorised charging spring and connected mobile parts, check for healthy trip mechanism, closing coil, tripping coil, auxilary contacts, replacment of PVC/Fibre insulator, rectifing the earth fault of the bus bar contacts and protective relays and complete caliberation of VCB/RMU complete testing complete all as specified and as directed. 8 Each Job
84 84 M&L for first-line maint of overhead bus bar grid/ 2 pole str/ 4-pole/ Sub Stn yard structure by checking out the jumpers/discs/ LAs/connectors e t c and locating the fault and replacing with necessary Conductor for jumpers/ clamps & connectors/ LAs /Disc/Pin insulators / clamps etc, making good, cleaning and lubricating the mobile parts etc complete all as specified and as directed : Note : Conductors for jumpers, disc/pin insulators, LAs are measured and paid separately under relavent items 72 Each Job
85 85 Scrapping/cleaning of outer surface of transformer and spray painting with two coats of best quality synthetic enamel paint over of red oxide primer complete including writing of MES NO/SM NO upto 315 KVA capacity transformer of any make/shape/size complete all as specified and directed. 8 Each job
86 86 Scrapping/cleaning of outer surface of transformer and spray painting with two coats of best quality synthetic enamel paint over of red oxide primer complete including writing of MES NO/SM NO above 315KVAand upto 650KVA capacity transformer of any make/shape/size complete all as specified and directed. 4 Each job
87 87 Supply and install HT 11 KV 3 phase 50 cycles out door type air break switch suitable for horiandal/Vertical mounting fixed type complete with 9 insulators operating handle and all clamps,nuts,bolts etc of rating upto 200 Amp complete all as specified and as directed 8 Each
88 88 S & F in repair horn gap fuse 11 kv triple pole, horizontal type for outdoor use including all accessoreis complete all as specified and as directed 8 Each set of 06Nos
89 89 S & F lighting arresters expulsion type complete with all fittings transmission class discharge capacity 65 kilo Amp all accessoreis complete all as specified and as directed 5 Each set of 03Nos
90 90 Supply and fix Male contact /moving contact blade for GOS 9 Each
91 91 Supply and fix Female contact/fix contact jaw for GOS 9 Each
92 92 Supply and fix Tinned copper flexible jumper for GOS 9 Each
93 93 Supply and fix MS jumper carrier for GOS 10 Each
94 94 Supply and fix Back connector plate for GOS 10 Each
95 95 Supply, only fuse wire tinned copper of diff capacity complete all as specified and directed.. 4 Kg
96 96 Supply, and fix in replacment of breather with silica gel complete all as specifed and as directed.. 5 each
97 97 Supply & fix replacement of silica gel complete all as specified and directed.. 3 Kg
98 98 Supply & fix replacement of petrolium jelly complete all as specified and directed.. 4 Kg
99 99 Painting of two pole stucture consistig of 2 Nos PCC pole 11 M height, 1 no GOS, 1 set support insulators with channels, with all connected clamps,supports etc by preparing the surface and applying two coat of syntheti enamal paint over a coat of primer as per colour code to the metal structure and cement paint to the PCC structures complete all as specified and as directed 14 Each job
100 100 Painting of two pole stucture consistig of 2 Nos (Metal Strucure) 11 M height, 1 no GOS, 1 set support insulators with channels, with all connected clamps,supports etc by preparing the surface and applying two coat of syntheti enamal paint over a coat of primer as per colour code to the metal structure and cement paint to the PCC structures all as specified and as directed 6 Each job
101 101 Painting of four pole stucture consisting of 4 Nos pole(metal structure) 11 M height, 3 no GOS, 1 set Fuse with channels,1Bus bars 1 No LA etc with all connected clamps,supports etc by preparing the surface and applying two coat of syntheti enamal paint over a coat of primer as per colour code all as specified and as directed 6 Each job
102 102 Painting of four pole stucture consistig of 4 Nos pole(PCC) 11 M height, 3 no GOS, 1 set Fuse with channels,1Bus bars 1 No LA etc with all connected clamps,supports etc by preparing the surface and applying two coat of syntheti enamal paint over a coat of primer as per colour code all as specified and as directed 6 Each job
103 103 Taking down defective transformer upto 650 KVA capacity from pole/structure/sub-station after disconnecting the connection and removing to sub-station then transporting the same to a reputed work shop for repairs.After repairing the same transporting back the repaired transformer(including loading and unloading) to the directed lacation.After installing the transformer connection of LT and HT has to be done complete all as specified and directed. 3 Each job
104 104 S&F high voltage coil of transformer including double paper insulated conductor of same gauge as per existing and all insulating material,varnishing and he complete all as specified and directed.ating with vaccum impregnation and baking of coil suitable upto 650 KVA transformer complete all as specified and directed. 350 Kg
105 105 S&F low voltage coil of transformer including double paper insulated conductor of same gauge as per existing and all insulating material,varnishing and he complete all as specified and directed.ating with vaccum impregnation and baking of coil suitable upto 650KVA transformer complete all as specified and directed. 350 Kg
106 106 Supply & fix replacement of top cover gasket of transformer suitable for any type/make/capacity upto 650KVA(make up of cork sheet 5mm thick) complete all as specified and directed.. 5 Each job
107 107 Dismantling of HT bushing of transformer including metal parts and rubber parts and replacing with new bushes complete with new metal and rubber parts of any size and shape required for transformer upto 650KVA complete all as specified and directed.. 4 Each
108 108 Dismantling of LT bushing of transformer including metal parts and rubber parts and replacing with new bushes complete with new metal and rubber parts of any size and shape required for transformer upto 650KVA complete all as specified and directed.. 4 Each
109 109 Supply and providing sand cushioning with dry clean sand duly filled in cable ducts/yards etc complete all as specified and directed. 10 Cum
110 110 Supply and spreading 40mm graded stone aggregate complete all as specified and directed. 15 Cum
111 111 Surface dressing n.exc 30 cm deep and average 15 cm deep and getting out in any type of soil complete all as specified and as directed 4000 sqm
112 112 M&L for Danger notice plate made of sheet molding composite (SMC) with red white with letters figures and conventional skull and in bones in signal red colour of HV Size and fixed with GI clamps bolts and nuts for 11 KV /HV Installations complete all as specified and as directed 75 Each
113 113 Supply , spreading and punning river sand for cushoining to cables in trenches , cable ducts , yards e.t.c complete all as specified as per SSR Part - I of 2009 and directed. 45 Cum
114 114 Taking out electric power cable of any size and make heavy duty with alumnium conductor, 11000 volts grade by removing cable protection covers etc complete all as specified and as directed. Excavation measured separately. 300 RM
115 115 Supply, laying & testing in replacement of cable XLPE insulated, screened, PVC bedded, gaivanised steel strip or wire armoured, electric power cable heavy duty with alumnium conductor, 11000 volts grade ISI marked of size 3 core cross section area 95 sqmm complete all as specified and directed. 250 RM
116 116 Supply, laying & testing in replacement of cable XLPE insulated, screened, PVC bedded, gaivanised steel strip or wire armoured, electric power cable heavy duty with alumnium conductor, 11000 volts grade ISI marked of size 3 core cross section area 120 sqmm complete all as specified and directed. 220 RM
117 117 All as per item No.119 above but of size 3 core cross section area 70 sqmm complete all as specified and directed. 190 RM
118 118 Relaying only of any size of electric power cable heavy duty with alumnium conductor, 11000 volts grade complete all as specified and directed. 300 RM
119 119 Supplying & laying of precast concrete cable cover, class HV, type 1 peak type size 300mmx180mmx40mm complete all as specified and directed.. 2800 Nos
120 120 Supply, jointing and testing of cable jointing kit for 11 KV(earthed) grade cable out door termination heat shrink type joint complete with jointly material and accessories suitable for 3 core under ground XPLE armoured aluminium conductor cable of size 70 to 95 sqmm complete all as specified and directed.. 4 Each
121 121 Supply, jointing and testing of cable jointing kit for 11 KV (earthed) grade cable straight through termination heat shrink type joint complete with jointly material and accessories suitable for 3 core under ground XPLE armoured aluminium conductor cable of size 70 to 95 Sqmm complete all as specified and directed.. 4 Each
122 122 Supply, jointing and testing of cable jointing kit for 11 KV (earthed) grade cable straight through termination heat shrink type joint complete with jointly material and accessories suitable for 3 core under ground XPLE armoured aluminium conductor cable of size 120 Sqmm complete all as specified and directed.. 3 Each
123 123 Supply, jointing and testing of cable jointing kit for 11 KV(earthed) grade cable out door termination heat shrink type joint complete with jointly material and accessories suitable for 3 core under ground XPLE armoured aluminium conductor cable of size 120 sqmm complete all as specified and directed.. 3 Each
124 124 Supply & Fixing in replacement precast PCC cable route indicator duly marked and painted for HT /LT cable of size 80 x 25 x 7.5 CM with suitable size of base complete all as specified and as directed. 60 Each
125 125 S&F in replacement of Old unsv cable loop box with PVC box of double hinged door to accommodate 6 amps MCB fixed ondin-rail, 4P connecter complete incl necessary clamps, bolts, nuts comple all as specified and as directed (Syntex/hensel) 40 Each
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail