Delhi University has published Replacement Of Aluminium Wiring By Copper Wiring Including Switch Socket G . I . Modular Box In S . P . Jain Centre At Sdc. Submission Date for this Tender is 27-01-2021. Electrification Work Tenders in South Campus Delhi. Bidders can get complete Tender details and download the document.
Name of Work: Replacement of aluminium wiring by copper wiring including switch socket G.I. modular box in S.P. Jain Centre at SDC | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel conduit including dismantling as required. Group C | BI01010001010000000000000515BI0100001113 | 135 | point |
2 | 2 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 1 x 1.5 sq. mm | BI01010001010000000000000515BI0100001114 | 1000 | metre |
3 | 3 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 2 x 2.5 sq. mm | BI01010001010000000000000515BI0100001115 | 350 | metre |
4 | 4 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 2 x 4 sq. mm | BI01010001010000000000000515BI0100001116 | 400 | metre |
5 | 5 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 2 x 6 sq. mm | BI01010001010000000000000515BI0100001117 | 150 | metre |
6 | 6 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 25 mm | BI01010001010000000000000515BI0100001118 | 300 | metre |
7 | 7 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 5/6 amps switch | BI01010001010000000000000515BI0100001119 | 165 | each |
8 | 8 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 15/16 amp switch | BI01010001010000000000000515BI0100001120 | 25 | each |
9 | 9 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 3 pin 5/6 amp socket outlet | BI01010001010000000000000515BI0100001121 | 30 | each |
10 | 10 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 6 pin 15/16 amp socket outlet | BI01010001010000000000000515BI0100001122 | 25 | each |
11 | 11 | Supplying and fixing stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. | BI01010001010000000000000515BI0100001123 | 30 | each |
12 | 12 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. 3 Module (100mmX75mm) | BI01010001010000000000000515BI0100001124 | 50 | each |
13 | 13 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. 6 Module (200mmX75mm) | BI01010001010000000000000515BI0100001125 | 15 | each |
14 | 14 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. 8 Module (125mmX125mm) | BI01010001010000000000000515BI0100001126 | 15 | each |
15 | 15 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. 12 Module (200mmX150mm) | BI01010001010000000000000515BI0100001127 | 10 | each |
16 | 16 | P/f tinny trip A.C. GI box with mnodular type complete with modular plate including 1 no 32 amps 'c' curve SPMCB and 1 no 25 amp 6 pin socket i/c connections as required. | BI01010001010000000000000515BI0100001128 | 20 | each |
17 | 17 | Dismantling existing switch, socket, sheet Aluminium wirings, TPDB, regulator, fittings, fans etc. required. | BI01010001010000000000000515BI0100001129 | 1 | Job |
18 | 18 | S/L/F 3 1/2 x 25 sqmm pvc insulated pvc sheathed, XLPE power cable of 1.1. KV grade as per latest I.S. code including laying/ fixing on terrace, wall inducing connections etc. as required. (Havells/Sky tone) | BI01010001010000000000000515BI0100001130 | 200 | metre |
19 | 19 | S/f 2x18 watts LED tube fittings i/c LED tube 2 nos direcrt on wall, ceiling on existing down rod i/c connections tc. as required. (4'- 0" long) | BI01010001010000000000000515BI0100001131 | 35 | Nos. |
20 | 20 | S/f 1x18 watts, 4’-0” long LED tube fittings including LED tube direct on wall ceiling on existing down rod i/c Connections. | BI01010001010000000000000515BI0100001132 | 20 | Nos. |
21 | 21 | P/f 1400 mm sweep high speed double ball bearing, three star rating ceiling fan without regulator i/c connections etc. as required. (Havells make) | BI01010001010000000000000515BI0100001133 | 25 | Nos. |
22 | 22 | Supplying and fixing following way prewired TP&N MCB distribution board of steel sheet for 415 volts on surface/ recess complete with loose wire box, terminal connectors for all incoming and outgoing circuits, duly prewired with suitable size FRLS PVC insulated copper conductor up to terminal blocks, tinned copper bus bar, neutral link, earth bar, din bar, detachable gland plate, interconnections, powder painted including earthing etc. as required.(But without MCB/ RCCB/ Isolator) 8 way (4 + 24), Double door | BI01010001010000000000000515BI0100001134 | 2 | Nos. |
23 | 23 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole | BI01010001010000000000000515BI0100001135 | 48 | each |
24 | 24 | Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 100 amps | BI01010001010000000000000515BI0100001136 | 2 | each |