Repair Replacement Of Lt Cables And Bus Bar Chambers Stay Assemblies Earthing And Other Connected Works At 4 Area And Map Ph Ii Under Ge Af Adm Area Agra, GEAFADMAREAAGRA-Uttar Pradesh

Military Engineer Services-MES has published Repair Replacement Of Lt Cables And Bus Bar Chambers Stay Assemblies Earthing And Other Connected Works At 4 Area And Map Ph Ii Under Ge Af Adm Area Agra. Submission Date for this Tender is 28-01-2021. Electrification Work Tenders in GEAFADMAREAAGRA Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

26626324
Repair Replacement Of Lt Cables And Bus Bar Chambers Stay Assemblies Earthing And Other Connected Works At 4 Area And Map Ph Ii Under Ge Af Adm Area Agra
National Competitive Bid
Indian
Uttar Pradesh
GEAFADMAREAAGRA
28-01-2021

Tender Details

Repair Replacement Of Lt Cables And Bus Bar Chambers Stay Assemblies Earthing And Other Connected Works At 4 Area And Map Ph Ii Under Ge Af Adm Area Agra

Key Value

Document Fees
INR 500 /-
EMD
INR 86000.0 /-
Tender Value
INR 43 Lakhs /-

BOQ Items

Name of Work : REPAIR / REPLACEMENT OF LT CABLES AND BUS BAR CHAMBERS, STAY ASSEMBLIES, EARTHING AND OTHER CONNECTED WORKS AT 4 AREA AND MAP PH II UNDER GE (AF) ADM AREA, AGRA
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Excavation in trenches in soft/ loose soil n.exc 1.5m wide and n. exc 1.5m depth for laying of cable, errection of poles, stay and pipe line and getting out complete all as specified and directed. BI01010001010000000000000515BI0100001113 630 Cum
2 2 All are as per item No 1.00 here-in-before but exc 3.0 m depth. BI01010001010000000000000515BI0100001114 0.3 Cum
3 3 Returning & filling including spreading, leveling watering and well ramming in layers n. exc 25 cm thick in soft/ loose soil complete all as specified and directed. BI01010001010000000000000515BI0100001115 340 Cum
4 4 Removal of excavated soil to a distance n. exc 50 m above the starting point complete all as specified and directed. BI01010001010000000000000515BI0100001116 290.3 Cum
5 5 Material and labour for old size brick well burnt, laid flat ,for cable protection complete all as specified and directed. BI01010001010000000000000515BI0100001117 13.4 Per 1000 Nos
6 6 Re-laying of old serviceable bricks retreived from ser item No.1.00 here-in- before for cable protection cover laid flat and dry in trenches over the cable prependicular to the direction of complete all as specified and directed. BI01010001010000000000000515BI0100001118 6.6 Per 1000 Nos
7 7 M&L for local sand coushioning with dry and clean over and under the cable for protection of cable , 80 mm sand laid before laying the cable 150 mm sand after laying the cable and filling the sand in cable duct of inside the sub station building complete all as specified and directed. BI01010001010000000000000515BI0100001119 195 Cum
8 8 M&L for cement concrete 1:4:8 type D-2 ( using 40 mm graded stone aggregate) for foundation of pole complete all as specified and directed. BI01010001010000000000000515BI0100001120 4.8 Cum
9 9 M&L for PCC type B-1 (1:2:4) ( using 20 mm gradded stone aggregate) for coping of poles including formwork complete all as specified and directed. BI01010001010000000000000515BI0100001121 0.15 Cum
10 10 M&L in replacement of GI tubing light grade of 100 mm bore for cable protection on pole/ wall/ floor/ or in trenches and drain etc complete with necessary clamp, nut, bolts and washers and socket and making good the disturbed surface of wall , floor or roof etc all as specified and directed. Make:- Prakash Surya/ TATA/ Jindal. BI01010001010000000000000515BI0100001122 48 RM
11 11 M&L in replacement of GI tubing light grade of 50 mm bore for cable protection on pole/ wall/ floor/ or in trenches and drain etc complete with necessary clamp, nut, bolts and washers and socket and making good the disturbed surface of wall , floor or roof etc all as specified and directed. Make:- Prakash Surya/ TATA/ Jindal. BI01010001010000000000000515BI0100001123 64 RM
12 12 M&L in replacement of GI tubing light grade of 40 mm bore for cable protection on pole/ wall/ floor/ or in trenches and drain etc complete with necessary clamp, nut, bolts and washers and socket and making good the disturbed surface of wall , floor or roof etc all as specified and directed. Make:- Prakash Surya/ TATA/ Jindal. BI01010001010000000000000515BI0100001124 64 RM
13 13 Taking out old unserviceable LT UG cables of size 10 to 70 sqmm 3.5/ 4 core from trenches, poles/ walls and floor for removing of fault or re-laying (Necessary earth work shall be measured and paid under respective item of sch.) complete all as specified and directed. BI01010001010000000000000515BI0100001125 2760 RM
14 14 Taking out old unserviceable LT UG cables of size 95 to 240 sqmm 3.5 core from trenches, poles/ walls and floor for removing of fault or re-laying (Necessary earth work shall be measured and paid under respective item of sch.) complete all as specified and directed. BI01010001010000000000000515BI0100001126 850 RM
15 15 Re-Laying XLPE LT UG cable PVC insulated , bedded armoured heavy duty electric cable 1100 volts grade with aluminium conductor of 10 to 70 sqmm 3.5/ 4 core (Item retreived from item No 13.00 here-in-before) laid in trenches or fixed on wall/ floor/ poles after removing fault complete all as specified and directed. BI01010001010000000000000515BI0100001127 360 RM
16 16 Re-Laying XLPE LT UG cable PVC insulated , bedded armoured heavy duty electric cable 1100 volts grade with aluminium conductor of 95 to 240 Sqmm 3.5/ 4 core (Item retreived from item 14.00 here-in-before) laid in trenches or fixed on wall/ floor/ poles after removing fault complete all as specified and directed. BI01010001010000000000000515BI0100001128 150 RM
17 17 Supply and Laying XLPE LT UG cable PVC insulated , bedded armoured heavy duty electric cable 1100 volts grade with aluminum conductor of size 240 Sqmm 3.5 core in trenches or fixed on wall/ floor/ poles complete all as specified and directed. Make:- Havells/ RPG/ RR Cables. BI01010001010000000000000515BI0100001129 100 RM
18 18 All as per Ser item No 17.00 here-in-before but size of cable 150 Sqmm, 3 & 1/2 Core. BI01010001010000000000000515BI0100001130 150 RM
19 19 All as per Ser item No 17.00 here-in-before but size of cable 120 Sqmm, 3 & 1/2 Core. BI01010001010000000000000515BI0100001131 200 RM
20 20 All as per Ser item No 17.00 here-in-before but size of cable 95 Sqmm, 3 & 1/2 Core. BI01010001010000000000000515BI0100001132 250 RM
21 21 All as per Ser item No 17.00 here-in-before but size of cable 70 Sqmm, 3 & 1/2 Core. BI01010001010000000000000515BI0100001133 250 RM
22 22 All as per Ser item No 17.00 here-in-before but size of cable 50 Sqmm, 3 & 1/2 Core. BI01010001010000000000000515BI0100001134 350 RM
23 23 All as per Ser item No 17.00 here-in-before but size of cable 35 Sqmm, 3 & 1/2 Core. BI01010001010000000000000515BI0100001135 400 RM
24 24 All as per Ser item No 17.00 here-in-before but size of cable 25 Sqmm, 3 & 1/2 Core. BI01010001010000000000000515BI0100001136 400 RM
25 25 All as per Ser item No 17.00 here-in-before but size of cable 16 Sqmm, 4 Core. BI01010001010000000000000515BI0100001137 500 RM
26 26 All as per Ser item No 17.00 here-in-before but size of cable 10 Sqmm, 2 Core. BI01010001010000000000000515BI0100001138 500 RM
27 27 M&L in replacement of existing U/S LT PVC insulated armoured heavy duty cable end terminal joints ( heat shrinkable) any type along pole etc suitable for aluminium conductor cable and testing after jointing of following sizes :- \n\n(a) 120-185 Sqmm, 3.5 core\nMake:- Denson/ Raychem/ Birla 3 M. \nNote:-\n(i) Rate quoted shall be including necessary excavation, returning filling, removal etc for taking out loop/ cutting of burnt cable for required length for making end joint. BI01010001010000000000000515BI0100001139 15 Each
28 27.01 (b) 50-95 Sqmm, 3.5 core BI01010001010000000000000515BI0100001140 20 Each
29 27.02 (c) 16-35 Sqmm, 3.5 core BI01010001010000000000000515BI0100001141 20 Each
30 27.03 (d) 10 Sqmm, 2 core. BI01010001010000000000000515BI0100001142 20 Each
31 28 M&L for jointing kit suitable for LT 1100 Volts cable (earthed) straight through joint, heat shrinkable type complete with jointing material and accessories suitable for 25 to 50 Sqmm 3.5 core XLPE armoured aluminium conductor cable complete all as specified and directed. Make:- Denson/ M seal/ Raychem/ Birla 3 M BI01010001010000000000000515BI0100001143 5 Each
32 29 M&L for jointing kit suitable for LT 1100 Volts cable (earthed) straight through joint , heat shrinkable type complete with jointing material and accessories suitable for 70 to 150 Sqmm 3.5 core XLPE armoured aluminium conductor cable complete all as specified and directed. Make:- Denson/ M seal/ Raychem/ Birla 3 M BI01010001010000000000000515BI0100001144 5 Each
33 30 M&L for drilling suitable dia horizontal bore holes for insertion / laying of 40 to100 mm bore GI tubing of any description below/ under road surface/floors etc with using mechanical or manual devices as required at site including making good disturbed surface to match with the existing streta after laying pipes complete all as specified and directed. BI01010001010000000000000515BI0100001145 72 RM
34 31 M&L in replacement for bus bar panel of capacity 400 Amps copper bus bar 04 Nos with fixed on insulator welded with iron angle of size 50 mm x 50 mm x 6 mm thick grounting in floor , 0.45 mm depth grounting with PCC 1:3:6, type C-1 upto ground level all as specified and directed. Make : Cat Part No IHBC040004 of Make-Havells or equivalent in Legrand/ L&T . BI01010001010000000000000515BI0100001146 3 Each
35 32 M&L in replacement for bus bar panel of capacity 250 Amps copper bus bar 04 Nos with fixed on insulator welded with iron angle of size 40 mm x 40 mm x 6 mm thick grounting in floor , 0.45 mm depth grounting with PCC 1:3:6, C-1 upto ground level all as specified and directed. Make : Cat Part No IHBC025004 of Make-Havells or equivalent in Legrand/ L&T. BI01010001010000000000000515BI0100001147 2 Each
36 33 M&L in replacement for bus bar panel of capacity 200 Amps copper bus bar 04 Nos with fixed on insulator welded with iron angle of size 40 mm x 40 mm x 6 mm thick grounting in floor , 0.45 mm depth grounting with PCC 1:3:6, C-1 upto ground level all as specified and directed. Make : Cat Part No IHBC020004 of Make-Havells or equivalent in Legrand/L&T. BI01010001010000000000000515BI0100001148 2 Each
37 34 M&L in replacement for bus bar panel of capacity 100 Amps copper bus bar 04 Nos with fixed on insulator fixed on pole with bracket made out of FI of size 25 mm x 3 mm -02 Nos including providing new nut, bolt & washers all as specified and directed. Make : Cat Part No IHBC010004 of Make-Havells or equivalent in Legrand/ L&T. BI01010001010000000000000515BI0100001149 5 Each
38 35 Cutting of bushes/ small plants upto root level around and surroundings areas of E/M installations (i.e.Two Pole/ Four structures, outdoor-substation yards,& other Misc E/M installations etc) soft/ loose soil including surface dressing n.exc 15 cm deep and removing debris to a distance n.exc 50m complete all as specified and directed. BI01010001010000000000000515BI0100001150 2500 Sqm
39 36 Supply, erecting and fixing in true vertical position, steel tubular swaged pole (410 SP – 31), 09 meter long, complete with cast iron base plate, pole cap / finial taper plug, bolts, nuts and washers, welded reduced section and longitudinal weld throughout entire length of pole including 2 coats of black bituminous paint externally upto planting depth and remaining exterior portion of pole shall be provided with one coat of red oxide primer and two coats of aluminium paint including taking out old U/S pole complete all as specified and directed. BI01010001010000000000000515BI0100001151 10 Each
40 37 Re-streching (without taking down ) of existing ACSR conductor including cradles and earth wire of any description of any size on LT / HT poles including binding the ACSR with insulator and tightening of conductor / earth wire in position , removing sag and making the jumper connection with new aluminum binding wire etc complete all as specified and directed. \n BI01010001010000000000000515BI0100001152 4500 RM
41 38 Material and labour for replacement of old U/S existing any size ACSR conductor squirrel to dog (6/1/2.11 to 6/1/4.72) any size drawn straight horizontal on over head lines on existing poles including binding with insulators. Weight of conductor shall be measured straight horizontal distance between centre of two adjacent poles and calculating weight of conductor of size and length by adding 3% extra for sag ,jointing jumpers,etc complete all as specified and directed. BI01010001010000000000000515BI0100001153 5 Qtl
42 39 Material & labour for pin type porcelain, vitreous, white, brown or green insulator including one GI nut bolt 100 mm height 65 mm dia for 1100 Volt including taking down old unserviceable insulator complete all as specified and directed. BI01010001010000000000000515BI0100001154 20 Each
43 40 Material & labour shackle type, porcelain, vitreous, white, brown or green insulator including galvanised mild steel straps, washers, insulator bolts, washers and nuts for 1100 Volt 100 mm height & 115 mm dia with GI straps 31 mm x 5 mm & dia of volt 14 mm including taking down old unserviceable insulator complete all as specified and directed. BI01010001010000000000000515BI0100001155 35 Each
44 41 M&L for MS cross arm , bracing supports , clamps and back plate fabricated from structural steel sections holding nut,bolts and washers including necessary welding , bending cold or hot drilling holes for bolts in any shape or size as indicated or directed and inclisive two coats of synethetic enamel paint over a coat of red oxide primer complete all as specified and directed. BI01010001010000000000000515BI0100001156 3 Qtl
45 42 M&L for GI wire of 4 mm dia for earth continuity or cattle cradles on LT/ HT over head line complete all as specified and directed. BI01010001010000000000000515BI0100001157 0.5 Qtl
46 43 M&L in repair for danger notice plate of 1.6 mm thick mild steel sheet viterous enamelled white with letters figures and conventional skul and bones in signal red colour and fixed with MS clamps , bolts, nuts and washers of approved size for LT , 415 volts of size 20 cm x 15 cm complete all as spd and directed. BI01010001010000000000000515BI0100001158 35 Each
47 44 M&L in repair for stay assembly using GI stay rod 20 mm dia complete with stay plate mild steel of size 300 mm x 300 mm x 6 mm thick, stay bow, loop insulator, stay wire, stay clamp, nuts, bolts etc complete all as specified and shown in Electrical Plate No 1 (Necessary earth work and PCC shall be measured and paid seperately) complete all as specified and directed. BI01010001010000000000000515BI0100001159 5 Each Set
48 45 M&L for cement concrete 1:3:6 type C1 ( using 20mm graded stone aggregate ) as in stay including form work etc complete all as specified and directed. BI01010001010000000000000515BI0100001160 1.6 Cum
49 46 Supply and fixing in replacement of MS chequered plate of 5 mm thick or over in thickness in available of Fe - 290 Gde E165 and fixed in substation building including making provision for lifting the plate from duct complete all as specified and directed. BI01010001010000000000000515BI0100001161 300 Kg
50 47 Disconnecting of GI earthing strips/ earth wire leads of any size, any description and in any postion from test point carefully and testing the earth resistance of any type of lightening conductor earthing with the help of earth tester of suitable capacity and recording Ohm value in the register as per proforma approved including cleaning vegetation/ wild growth sorrounding the earth pit and removing dust/ deposited soil from earth pit. \nNOTE :- (i). The contractor will arrange Earth Tester, all T&P & accessories for recording the reading.\n(ii). The contractor shall arrange for watering of the earth pit through watering pipe in the earthing to improve the resistance. The common salt min 10 Kgs for each earthing pit shall be mixed with the water at site and filled/dropped in earthing through warering pipe as per site condtion and as directed. The water for this purpose shall be made available by the deptt. at the nearest available source but contractor shall make his own arrangement for drawing water from this source. \n(iii). The record of resistance value of each earthing alongwith date of testing shall be maintained on register as per format approved.\n BI01010001010000000000000515BI0100001162 75 Each Job
51 48 M&L for PVC seprator for LT over head line suitable for 2 wire and 3 wire sytem and fixed LT OH lines comlete all as specifed and directed. BI01010001010000000000000515BI0100001163 20 Each
52 49 M&L for prepration of old painted surface of steel tubular poles of 9 mtr long including cross arms , cable protection pipe , bus bar box and painting of complete area with one coat of aluminum paint from 1.5 mtr above ground level to top of pole and a height of 1.5 mtr from the ground level synethetic enamel paint in alternate strips / layer (30 cm wide) with white and blue colour including writing the pole number in white letters on black background and cleaning /cutting the grass/ bushes at a radius of 2 mtr surrounding the pole complete all as specified and directed. BI01010001010000000000000515BI0100001164 150 Each
53 50 Supply and fixing in replacement of aluminium bus bar of any size or length and fixed on exisitng panle board including necessary drilling bracing providing colour code sleeves on bus bar complete all as specified and directed. BI01010001010000000000000515BI0100001165 10 Kg
54 51 Supply and fixing of cable route indicator for LT cable and provision of 40 x 5 mm angle iron legs of 0.5 mtr height and errection with PCC foundation with PCC 1:2: 4 with 20 mm graded stone aggregate including taking down old unserviceable route indicator of any description complete all as specified and directed. BI01010001010000000000000515BI0100001166 20 Each
55 52 Supply and fixing in replacement of existing old un-serviceable earth continuity conductor of size 32 mm x 6 mm aluminium strip fixed to wall and batton or recess or chases or burried in ground or drawn in conduit/pipe or fixed in ground or drawn in conduit/ pipe or fixed to poles or any other indicated situation for loop earthing etc complete all as specified and directed. BI01010001010000000000000515BI0100001167 25 RM
56 53 Supply, installation and commissioning in replacement of existing U/S control unit with cubical type enclosed in sheet steel air circuit breaker AC 415 volts, 50 hz, 4 pole, 630 amps current carrying capacity micro processor and comprising the following :- \n(i) Withdraw able version ACB 415 volts 3 pole ,630 Amp capacity .\n(ii) Independent manual spring closing mechanism -one No\n(iii) Shunt opening closing release - one No\n(iv) kiosk box / enclosure shall be included unit rate \n(v) Racking in and out handle\n(vi) CT 630/ 5 one set \n(vii) Safety shutter\n(vi) Make – Legrand Cat Ref DMX3 (028730+028802+028897) or equivalent in Seimens (3WL)/ Schenieder. BI01010001010000000000000515BI0100001168 2 Each
57 54 M&L in replacement of existing U/S MCCB 400 Amps current carrying capacity 36 KA , AC 415 Volts, Ics= 100% Icu, four pole with thermal and magnetic adjustable type setting complete all as specified and directed. \nMake : Legrand (DPX3) Cat Ref 422007 or equivalent in Seimens (3BL)/ Schednieder. BI01010001010000000000000515BI0100001169 3 Each
58 55 M&L in replacement of existing U/S MCCB 320 Amps current carrying capacity 36 KA , AC 415 Volts, Ics= 100% Icu, four pole with thermal and magnetic adjustable type complete all as specified and directed. \nMake : Legrand (DPX3) Cat Ref 422006 or equivalent in Seimens (3BL)/ Schednieder. BI01010001010000000000000515BI0100001170 2 Each
59 56 M&L in replacement of existing U/S MCCB 250 Amps current carrying capacity 36 KA , AC 415 Volts, Ics= 100% Icu, four pole with thermal and magnetic adjustable type complete all as specified and directed. \nMake : Legrand (DPX3) Cat Ref 420249 or equivalent in Seimens (3BL)/ Schednieder. BI01010001010000000000000515BI0100001171 3 Each
60 57 M&L in replacement of existing U/S MCCB 200 Amps current carrying capacity 36 KA , AC 415 Volts, Ics= 100% Icu, four pole with thermal and magnetic adjustable type complete all as specified and directed. \nMake : Legrand (DPX3) Cat Ref 420248 or equivalent in Seimens (3BL)/ Schednieder. BI01010001010000000000000515BI0100001172 3 Each
61 58 M&L in replacement of existing unsv MCCB 160 Amps current carrying capacity 25 KA , AC 415 Volts, Ics= 100% Icu, four pole with thermal and magnetic adjustable type complete all as specified and directed. \nMake : Legrand (DPX3) Cat Ref 420057 or equivalent in Seimens (3BL)/ Schednieder. BI01010001010000000000000515BI0100001173 4 Each
62 59 M&L in replacement of existing unsv MCCB 125 Amps current carrying capacity 25 KA , AC 415 Volts, Ics= 100% Icu, four pole with thermal and magnetic adjustable type complete all as specified and directed. \nMake : Legrand (DPX3) Cat Ref 420056 or equivalent in Seimens (3BL)/ Schednieder. BI01010001010000000000000515BI0100001174 4 Each
63 60 M&L in replacement of existing unsv MCCB 100 Amps current carrying capacity 25 KA , AC 415 Volts, Ics= 100% Icu, four pole with thermal and magnetic adjustable type complete all as specified and directed. \nMake : Legrand (DPX3) Cat Ref 420055 or equivalent in Seimens (3BL)/ Schednieder. BI01010001010000000000000515BI0100001175 5 Each
64 61 Supply and fixing in replacement of existing old un-serviceable fixed type MCCB with MCCB 63 amps, 4 pole, 415 volts, 16 KA, Ics= 100% Icu with thermal and magnetic adjustable type complete all as spd and directed. \nMake : Legrand (DPX3) Cat Ref 420013 or equivalent in Seimens (3BL)/ Schednieder. BI01010001010000000000000515BI0100001176 6 Each
65 62 Trimming up of tree branches upto 3 mtr all around HT/LT overhead lines, removing cut branches from site as directed. \nNote :- (i) The overhead lines will be kept clear from all trees by trimming of tree branches with 3 mtr all around the line. Necessary permission will be obtained from department by contractor one day prior to trimming in particular area and shut down of that area will be arranged by department. BI01010001010000000000000515BI0100001177 100 Per Span
66 63 M&L for replacement of existing U/S sign board with size of 4 feet x 3 feet of PVC fibre sheet board of 6 mm size heavy duty including writing alphabatic letters computerised with refelctive sheets to be made as all directed of size 150 mm fonts and fixed with stainless steel pipe heavy duty of size 40 to 50 mm dia and to be fixed outside the installations duly burried in ground along with required PCC and top of the sign board should be 2.5 mtr and all as directed and specified. BI01010001010000000000000515BI0100001178 15 Each Job
67 64 M&L for replacament of existing old U/S earthing complete with galvanised steel earth plate electrode , 600 x 600 x 6mm thick burried directly in the ground (earth pit not less than 2.25 mtr deep below ground level)with top edge of the plate not less than 1.5mtr below ground level connected to galvanised iron wire 4mm dia as earth lead by means of bolts, nuts and washers of GI up to test point , GI tubing 15 mm bore medium grade protection pipe , GI watering pipe 20mm bore light grade with funnel and wire mesh , charcoal ,salt and precast PCC 1:2:4 (Nominal mix ) reinforced with XPM having weight not less than 4 kg /sqm including suitable handle of 6mm dia MS bar and angle iron 40x40x3mm frame for cover including earth work in any type of soil , removal of surplus soil to a distance n.exc 50m and connecting , testing on completion all as shown on electric plate No 03 of SSR -2009 Part I complete all as specified and directed.\nNote: Excavation and earth work is deemed to be included in the rates quoted. BI01010001010000000000000515BI0100001179 20 Each
68 65 M&L for earthing with steel earth plate electrode of size 60x60cmx6mm thick buried directly in ground to a depth not less than 3.25 mtr deep below normal ground level with top edge of the earth plate not less than 2.5 mtr deep below normal ground level connected to galvanized iron strip of size 32x6mm as earthing lead by means of nuts, bolts and washers of steel after welding of GI strip to earth electrode to the full lenght of earth plate,40mm dia GI tubing light grade protection pipe upto test point, 20mm dia GI watering pipe with funnel and wire mesh, PCC pit 1:3:6 with pit cover of size 30X30cm made of RCC 1:3:6 with suitable handle,angle iron frame made of angle iron of size 40x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate, removal of surplus soil and returning filling in all as required at site including test point made out of steel plate of size 75x75x6mm fixed to wall all as specified in plate No 3 of SSR Part-I and directed. BI01010001010000000000000515BI0100001180 20 Each
69 66 Material and labour for replacement of existing unsv decorative post top lantern 40 watts 230 volts, 50 HZ, mushroom or oval shaped in sothing opal/ prismatic finish made up of polycarbonate, suitable for 40 watt LED, all accessories prewired. \nMake:- Havells Cat Ref RUBYPT35WLED830PSYMTOPC/ Wipro Cat Ref LP07-251-XXX-57-CL or equivalent in Philips. BI01010001010000000000000515BI0100001181 10 Each
70 67 M&L for earthing complete with copper earth plate electrode 600x600x3mm thick buried directly in ground to a depth not less than 4.5 mtr deep below normal ground level with top edge of the earth plate not less than 3.75 mtr deep below normal ground level connected to copper strip 25x3 mm size as earthing lead by means of bolts, nuts, check nuts and washers of brass, GI protection pipe light grade 40mm bore up to test point 20mm dia GI watering pipe with funnel and wire mesh, PCC pit 1:2:4 type BI, RCC cover with suitable GI strip handle, earth pit filled with ground enhancing material i.e. mixture of copper sulphate, magnesia sulphate, graphite power etc mixed in equal quantity all around earth plate up to 15 cm and filled with vegetable soil above GEM up to ground level earth work in soft/ loose soil all as required and directed including testing on completion. BI01010001010000000000000515BI0100001182 10 Each
71 68 Supply installation erection commissioning and testing of LT panel board cubical out door type of suitable size for housing of all equipments & proper heat dissipation, CPRI approved weather/dust proof, factory made out of 3.15 mm thick CRCA sheet powder coated with front and back side openable with suitable cable chamber and front side shutters with locking arrangement panel base of angle iron 50x50x6 mm upto 45 cm height for 433 volts, 3 phase, 4 wire system including TPN copper bus bar of rating not less than 1.5 times the rated capacity of the incomer MCCB. The TPN bus bar shall be insulated with colour coded heat shrinkable sleeves and shall be mounted on F class insulators. All interconnections between the main bus bar as well as outgoing feeders shall be carried out with TPN copper bus bar of rating not less than 1.5 times rated capacity of of individual outgoing feeders. All control wiring shall be with FRLS PVC insulated 6 sqmm multi-stranded copper conductor and shall be properly bunched. The cubical shall have bottom channel of size 75 x 40 mm and complete mounted or fixed on PCC foundation above 0.45 mtr on floor and cable connection with suitable size of copper lugs and suitable size chrome plated glands provided for incoming and out-going cables comprising the following :-\n BI01010001010000000000000515BI0100001183 3 Each
72 68.01 INCOMING :\n(a) 250 Amp 4 pole MCCB 36 KA breaking capacity with fixed thermal magnetic setting Ics= 100% Icu-01 Nos. Make:- of MCCB Legrand Cat Ref 420249 or equivalent in Seimens/ GE Power.\nOUTGOING : \n(a) 100 Amp 4 pole MCCB 25 KA breaking capacity with fixed thermal magnetic setting Ics= 100% Icu - 03 Nos. Make:- of MCCB Legrand Cat Ref 420055 or equivalent in Seimens/ GE Power.\n(b) 63 Amp 4 pole MCCB 16KA breaking capacity with fixed thermal magnetic setting Ics= 100% Icu -02 Nos. Make:- of MCCB Legrand Cat Ref 420013 or equivalent in Seimens/ GE Power.\n(c) AC digital voltmeter 0-500 volts Size 4"X4" with 3 Ph selector switch-01 No\n(d) 0-500 digital Amp meter with suitable Size 4"X4" with 3 Ph selector switch- 01 Set.\n(e) LED indicating lamps RYB set of three -01 Set BI01010001010000000000000515BI0100001184
73 69 Supply installation erection commissioning and testing of LT panel board cubical out door type of suitable size for housing of all equipments & proper heat dissipation, CPRI approved weather/dust proof, factory made out of 3.15 mm thick CRCA sheet powder coated with front and back side openable with suitable cable chamber and front side shutters with locking arrangement panel base of angle iron 50x50x6 mm upto 45 cm height for 433 volts, 3 phase, 4 wire system including TPN copper bus bar of rating not less than 1.5 times the rated capacity of the incomer MCCB. The TPN bus bar shall be insulated with colour coded heat shrinkable sleeves and shall be mounted on F class insulators. All interconnections between the main bus bar as well as outgoing feeders shall be carried out with TPN copper bus bar of rating not less than 1.5 times rated capacity of of individual outgoing feeders. All control wiring shall be with FRLS PVC insulated 6 sqmm multi-stranded copper conductor and shall be properly bunched. The cubical shall have bottom channel of size 75 x 40 mm and complete mounted or fixed on PCC foundation above 0.45 mtr on floor and cable connection with suitable size of copper lugs and suitable size chrome plated glands provided for incoming and out-going cables comprising the following :- BI01010001010000000000000515BI0100001185 3 Each
74 69.01 INCOMING \n(a) 200 Amp 4 pole MCCB 36 KA breaking capacity with fixed thermal magnetic setting Ics= 100% Icu - 01 Nos. Make:- of MCCB Legrand Cat Ref 420248 or equivalent in Seimens/ GE Power.\nOUTGOING\n(a) 63 Amp 4 pole MCCB 25 KA breaking capacity with fixed thermal magnetic setting Ics= 100% Icu - 05 Nos. Make:- of MCCB Legrand Cat Ref 420053 or equivalent in Seimens/ GE Power.\n(b) AC digital voltmeter 0-500 volts Size 4"X4" with 3 Ph selector switch-01 No\n(c) 0-500 digital Amp meter with suitable Size 4"X4" with 3 Ph selector switch- 01 Set.\n(d) LED Indicating lamps RYB set of three -01 Set BI01010001010000000000000515BI0100001186
75 70 Supply installation erection commissioning and testing of LT panel board cubical out door type of suitable size for housing of all equipments & proper heat dissipation, CPRI approved weather/dust proof, factory made out of 3.15 mm thick CRCA sheet powder coated with front and back side openable with suitable cable chamber and front side shutters with locking arrangement panel base of angle iron 50x50x6 mm upto 45 cm height for 433 volts, 3 phase, 4 wire system including TPN copper bus bar of rating not less than 1.5 times the rated capacity of the incomer MCCB. The TPN bus bar shall be insulated with colour coded heat shrinkable sleeves and shall be mounted on F class insulators. All interconnections between the main bus bar as well as outgoing feeders shall be carried out with TPN copper bus bar of rating not less than 1.5 times rated capacity of of individual outgoing feeders. All control wiring shall be with FRLS PVC insulated 6 sqmm multi-stranded copper conductor and shall be properly bunched. The cubical shall have bottom channel of size 75 x 40 mm and complete mounted or fixed on PCC foundation above 0.45 mtr on floor and cable connection with suitable size of copper lugs and suitable size chrome plated glands provided for incoming and out-going cables comprising the following :- BI01010001010000000000000515BI0100001187 2 Each
76 70.01 INCOMING \n(a) 320 Amp 4 pole MCCB 36 KA breaking capacity with fixed thermal magnetic setting Ics= 100% Icu - 01 Nos. Make:- of MCCB Legrand Cat Ref 422006 equivalent in Seimens/ GE Power.\nOUTGOING \n(a) 200 Amp 4 pole MCCB 36 KA breaking capacity with fixed thermal magnetic setting Ics= 100% Icu - 01 Nos. Make:- of MCCB Legrand Cat Ref 420248 or equivalent in Seimens/ GE Power.\n(b) 125 Amp 4 pole MCCB 25 KA breaking capacity with fixed thermal magnetic setting Ics= 100% Icu - 02 Nos. Make:- of MCCB Legrand Cat Ref 420056 or equivalent in Seimens/ GE Power.\n(c) 63 Amp 4 pole MCCB 25 KA breaking capacity with fixed thermal magnetic setting Ics= 100% Icu - 02 Nos. Make:- of MCCB Legrand Cat Ref 420053 or equivalent to Seimens/ GE Power.\n(d) AC digital voltmeter 0-500 volts Size 4"X4" with 3 Ph selector switch-01 No\n(e) 0-500 digital Amp meter with suitable Size 4"X4" with 3 Ph selector switch- 01 Set.\n(f) LED Indicating lamps RYB set of three -01 Set BI01010001010000000000000515BI0100001188
77 71 Dismantling old defective/ peeled of Insulating Mat and M&L for Elastomer Insulating Mats for Electrical Purposes Class A/voltage grade upto 3.3 KV (AC) as per IS : 15652:2006 with ISI mark of thickness 2.5 mm+ 10% of approx width 1 mtr along with suitable adhesive /chemibound resin waterproofing compound and sealing material all as per manufacturers' recommendations. Make: Electromat or equivalent approved make. BI01010001010000000000000515BI0100001189 20 Sqm
78 72 M&L for graded stone aggregate 20 mm size without any vegitation including levelling /sprending surrounding HT/LT 2/3/4 pole structure/Installations/LT/HT panel/around transformer plateforms all as specified directed by Engr-in-Charge. \nNote :- Rates are deemed to be included for setting the existing bricks reqd for rataining the aggregare, if any. BI01010001010000000000000515BI0100001190 25 Cum
79 73 M&L for brick work sub class 'B' straight or curved on plan not exceeding 6. 0 mtr mean radius built in cement mortar 1:6 complete all as specified and directed. BI01010001010000000000000515BI0100001191 3 Cum
80 74 M&L for rendering 10 mm thick on fair faces of brick or concrete surfaces in cement mortar 1:6 finishedthe surface even and fair without using extra cement complete all as specified and directed. BI01010001010000000000000515BI0100001192 40 Sqm
81 75 M&L for 40 mm thick precast RCC type B-1 earth pit covers as specified in SSR Part-I including providing funnel complete all as spd and directed. BI01010001010000000000000515BI0100001193 50 Each Job
82 76 M&L for removing existing old paint with the help of sand/ emery paper etc from LT panel outdoor/ indoor / LT feeder pillar boxes off sizes. Preparing surfaces externally & internally both sides of doors and pannel as directed including cleaning and applying two coats of synthetic enamel grey paint by spraying machine complete all as specified and directed. BI01010001010000000000000515BI0100001194 35 Each Job
83 77 Cutting the tarmac / hard standings and excavating in trenches across the road for laying cable including making good the excavated portion by means of PCC 1:3:6, type C1 matching with the surroundings all as directed. BI01010001010000000000000515BI0100001195 2 Cum
84 78 M&L for dismantling the cable connections of four pole/ three pole Air circuit breaker of capacity upto 1000 Amps ,415 V 50 HZ of Make:- Legrand/ CG/ L & T/ ABB/ Havells/ C & S, strip opening the Air circuit breaker, inspecting the parts for serviceability/ overhauling complete and carrying out the following repairs/ maintenance :- \n(a) Cleaning the insulation parts including bushings with CTC solution\n(b) Checking the alignment and condition of movable and stationary contacts and adjust them all as per manufacturer's instructional manual. (c) Check the bolts, nuts, washers, cotter pins and all terminal connections are in place and tightening and replacementof the worn-out parts. (d) Check arc chutes for damage. (e) Clean and lubricate the operating mechanism with a light machine oil for pins and bearings and with a non-hardening grease for the wearing surfaces . Adjust breaker operating mechanism all as per manufacturer's instructional manual. (f) Checking / inspecting shunt trip coil for serviceability and replacing the same if required. \n(g) Checking control device free for operation. (j) Check after servicing the circuit breaker to verify the contacts move to the fully opened and fully closed positions, that there is an absence of friction and that the electrical operation is functional. Note : The rate quoted deemed to be inclusive of T&P and minor spares like lubricants, nuts/bolts/washers/ pins etc. Major spares like Shunt release & trip coil etc will be measured & paid separately under relevant schedule items. BI01010001010000000000000515BI0100001196 4 Each Job
85 79 Supply only CTs suitable for air circuit breakers of rating 630 Amps to 1000 Amps as all per existing of Make:- Legrand/ CG/ L & T/ ABB/ Havells/ C & S BI01010001010000000000000515BI0100001197 3 Each
86 80 Supply only auxiliary contact block suitable for air circuit breakers of rating 630 Amps to 1000 Amps as all per existing of Make:- Legrand/ CG/ L & T/ ABB/ Havells/ C & S BI01010001010000000000000515BI0100001198 2 Each
87 81 Supply only arcing contacts (fixed/ moving) suitable for air circuit breakers of rating 630 Amps to 1000 Amps as all per existing of Make:- Legrand/ CG/ L & T/ ABB/ Havells/ C & S BI01010001010000000000000515BI0100001199 2 Each Set
88 82 Supply only arc chutes (for 415 V) suitable for air circuit breakers of rating 630 Amps to 1000 Amps as all per existing of Make:- Legrand/ CG/ L & T/ ABB/ Havells/ C & S BI01010001010000000000000515BI0100001200 2 Each
89 83 Supply only shunt release (110 /220 V DC or 240 V/415 V AC) suitable for air circuit breakers of rating 630 Amps to 1000 Amps as all per existing of Make:- Legrand/ CG/ L & T/ ABB/ Havells/ C & S BI01010001010000000000000515BI0100001201 2 Each
90 84 Supply only cluster contact suitable for air circuit breakers of rating 630 Amps to 1000 Amps as all per existing of Make:- Legrand/ CG/ L & T/ ABB/ Havells/ C & S BI01010001010000000000000515BI0100001202 1 Each
91 85 Supply only trip coil suitable for air circuit breakers of rating 630 Amps to 1000 Amps as all per existing of Make:- Legrand/ CG/ L & T/ ABB/ Havells/ C & S BI01010001010000000000000515BI0100001203 3 Each
92 86 Supply and replacing 1100 volts grade heavy duty PVC insulated aluminium conductor, served with inner sheathing of PVC in service connections suspended by insulating hangers not more than 1 mtr apart including 4mm suspension wire one twin core cable of size 16 Sqmm multistranded complete all as specified and directed. \nMake :- Plaza/ Finolex/ Gloster/ Paragon. BI01010001010000000000000515BI0100001204 500 Rm
93 87 M&L for welding work to LT panels/ feeder pillar box as per requirement at site to match with existing complete all as specified and directed. BI01010001010000000000000515BI0100001205 9 Each job
94 88 M&L for brick masonary platform for the installation of transformer of outer size 3000 mm x 2500 mm and 1200 mm high (300 mm below GL and 900 mm above GL) complete with following specifications :- \n(a) 100 mm thick PCC type D-2 in foundation\n(b) one brick thick brick wall alround in CM 1:6\n(c) 15 mm thick cement plaster in CM 1:6\n(d) 40 mm thick PCC type B-1, floor, finished the surface even & smooth with using extra cement\n(e) Two coats of cement based paint over plastered surfaces\n(f) 75 mm thick & 750 mm wide PCC type C-1 plinth protection alround the plateform \n(g) Complete earth work including earth filling in plateform BI01010001010000000000000515BI0100001206 2 Each Job
95 89 S&F framed work as in doors/ gates and fencing post etc of angle or other section with gusset plates, rails braces etc, conforming to Fe-290 Gde Fe-165 complete, drilled for fixing of steel sheeting or other covering doors, etc to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings (exclusive of steel sheeting or other covering, running rails and guides) and hanging, also fastering and fixing complete all as specified and directed. BI01010001010000000000000515BI0100001207 180 Kg
96 90 S&F chain link fencing of 50 mm x 50 mm x 4 mm and fixed to angle iron posts including line wires, and type to any type of standard, rails, straining bolts, etc & provn of winding wire complete all as specified and directed. BI01010001010000000000000515BI0100001208 50 Sqm
97 91 M&L for preparation of new steel surfaces of any description, exc.10 cm in width or girth, not otherwise described and applying two coats of synthetic enamel paint over one coat of red oxide primer complete all as specified and directed. BI01010001010000000000000515BI0100001209 90 Sqm
98 92 S&F in replacement digital type Amp-meter including suitale ratio of CT, rating 0-400 Amps, 96 mm x 96 mm complete all as specified and directed. Make:- HPL/ AE/ Secure/ L &T. BI01010001010000000000000515BI0100001210 15 Each
99 93 M&L for replacement digital type Volt-meter of size 96 x 96 mm, capacity 0- 500 voltscomplete all as specified and directed. Make:- HPL/ AE/ Secure/ L &T. BI01010001010000000000000515BI0100001211 16 Each
100 94 M&L for replacement of existing U/S selector switch of LT panels complete all as specified and directed. BI01010001010000000000000515BI0100001212 15 Each
101 95 M&L for replacement of existing U/S indicators with holder complete all as specified and directed. BI01010001010000000000000515BI0100001213 20 Each
102 96 M&L for rewiring/ making functional of all meters, indicators of LT panel/ FPB using appropriate capacity FRLS wire as directed including all minor accessories like thimbles, sleeves of different colour, nuts/ bolts,complete all as specified and directed. BI01010001010000000000000515BI0100001214 12 Each