Repair And Maintenance Of External Supply Lt Ug Cables Earthing Lt Poles Apfc Panels Of Zone A At Jasai Mil Stn Under Ge A Barmer, GE ARMY BARMER-Rajasthan

Military Engineer Services-MES has published Repair And Maintenance Of External Supply Lt Ug Cables Earthing Lt Poles Apfc Panels Of Zone A At Jasai Mil Stn Under Ge A Barmer. Submission Date for this Tender is 04-02-2021. Electrification Work Tenders in GE ARMY BARMER Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

26624764
Repair And Maintenance Of External Supply Lt Ug Cables Earthing Lt Poles Apfc Panels Of Zone A At Jasai Mil Stn Under Ge A Barmer
Open Tender
Indian
Rajasthan
GE ARMY BARMER
04-02-2021

Tender Details

Repair And Maintenance Of External Supply Lt Ug Cables Earthing Lt Poles Apfc Panels Of Zone A At Jasai Mil Stn Under Ge A Barmer

Key Value

Document Fees
INR 500 /-
EMD
INR 28000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work : REPAIR/MAINTENANCE OF EXTERNAL SUPPLY LT UG CABLES, EARTHING, LT POLES, APFC PANELS OF ZONE 'A' AT JASAI MIL STN UNDER GE (A) BARMER
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Dismantiling/uprooting of LT unserviceable pre-stressed concrete poles /steel poles of any size and shape including taking out dismantled portion of pole embended in ground after necessary demolition of foundation concrete and making good disturded ground properly and removing the debris out sdide MD land complete all as specified and as directed.\nNote :- The necessary excavation & earth work is required to be included in the unit rate quoted. 10 EACH
2 2 Dismantling of unservicable steel structure, cross arms, bracings, supports, clamps from two /four pole stucture at various location and keeping serviceable materials in safe custody for reuse and/or unserviceable materials credited to contractor or returned to MES store yard complete all as specified and as directed. 5.5 QTL
3 3 Dismantlng of stay assembly of any size complete with stay rod including demolition of PCC and including necessary excavation and earth work complete all as specified and as directed. 20 PER SET
4 4 Disconnecting electric connection and taking down old aluminium conductor steel reinforced (ACSR) of different size from over head line incld line spacer and other connected accessories and keeping serviceable materials in safe custody for re-use and unserviceable material remove from site to store/credited under sch of credit complete all as specified and as directed by Engg-in-charge. 14 Qtl
5 5 Disconnecting electric connection and taking down old guarding cradle /earth wire or copper conductor or disturbed fan from over head line and keeping serviceable materials in safe custody for reuse and removing unserviceable materials from site to store/credited under Sch of Credit complete all as specified and as directed . 3.6 QTL
6 6 Dismantling LT insulators any type & any size, pin/ shackle/ disc & loop type from existing OH lines and keeping serviceable materials in safe custody for reuse and removing unserviceable materials from site to store/credited under Sch of Credit complete all as specified and as directed . 535 EACH
7 7 Excavation in trenches not exceeding 1.5mtr wide and not exceeding 1.5 mtr in depth for foundation, laying of cable / pipe line etc and getting out in soft / loose soil complete all as specified and directed . 8 CUM
8 8 Excavation in trenches not exceeding 1.5mtr wide and depth exceeding 1.5 mtr but not exceeding 3.0mtr in depth for foundation etc and getting out in soft / loose soil complete all as specified and directed . 2.6 CUM
9 9 Returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick in soils complete all as specified and directed. 4 CUM
10 10 Removing excavated materials to a distance not exceeding 50m depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed . 6.6 CUM
11 11 M&L cement concrete 1:3:6 type C-2 by using 40mm graded crushed stone aggregate as in foundation of poles, stays including necessary form work complete all as specified and as directed. 8.75 CUM
12 12 M&L cement concrete 1:2:4 type B-1 by using 10mm graded crushed stone aggregate as in coping / pedestals of poles etc., including necessary form work complete all as specified and as directed. 1 CUM
13 13 Supply and lay in repair synthetic insulatory rubber mat of size 2 mtr x 1 mtr X19 mm thick ISI marked complete all as specified and as directed.\nMake:- Jaipuria Brothers 7 EACH
14 14 Supply and errect steel tubular swaged poles type 410 SP-31 (9.0 metres long) complete with cast iron base plate and finial taper plug, bolts, nuts & screws complete all as specified and directed. \nNote: - (i) Painting with two coats of black bituminous paint throughout internally and externally upto plating depth and the remaining external complete pole portion shall be painted with silver colour in two coats over a red oxide primer and A1 graded radium strip of 100mm width in three colour red, yellow, and green shall be fix around the pole with 100mm gap in each strip at a distance of 1.1 mtr high from the ground level deemed to be included in quoted rates.\n(ii) Excavation, earthwork & PCC shall be measured and paid separately under relevant items.\n 10 EACH
15 15 M&L for Cross arms, bracings, supports, clamps,ladder and back plates fabricated from steel sections including nuts, bolts, washer, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of two coats of aluminum paint over one coat of red oxide primer including preparation of steel surfaces complete all as specified and as directed . 3.5 QTL
16 16 Fixing only serviceable cross arms, bracings, supports, clamps,ladder and back plates including nuts, bolts, washer, welding, bending cold or hot, drilling holes for bolts if required, in any shape or size as indicated or directed and including preparation of old steel surface and apply one coat of aluminum paint complete all as specified and as directed . \nNote :- Serviceable cross arms will be re used, which are obtained from here-in-above sl item No.02. 2 QTL
17 17 S& F pin type, porcelain, vitreous, white, green & brown insulator including one galvanised iron steel spindle, two galvanised iron washer and one galvanised iron nut, size 65mm dia x 100mm height for 1100 Volts grade complete all as specified and as directed . 220 EACH
18 18 Fixing only serviceable pin type, porcelain, vitreous, white, green & brown insulator including one galvanised iron steel spindle, two galvanised iron washer and one galvanised iron nut, of any size & type for 1100 Volts grade complete all as specified and as directed . \nNote :- Serviceable insulators obtained from slitem No.06 of above will be re used. 150 EACH
19 19 S&F shackle type insulators, porcelain, vitreous, brown or green insulator including galvanised mild steel straps, washers, insulators, bolts, washers and nuts, working pressure 1100 volts and size of 75mm in height and 90mm dia with section of straps 31 x 3mm and dia of bolts 12mm complete all as specified and as directed . 60 EACH
20 20 S&F shackle type insulators, porcelain, vitreous, white, brown or green insulator including galvanised mild steel straps, washers, insulators, bolts, washers and nuts, working pressure 1100 volts and size of 100mm in height and 115mm dia with section of straps 31 x 5mm and dia of bolts 16mm complete all as specified and as directed . 40 EACH
21 21 Fixing only serviceable shackle type, porcelain, vitreous, white, green & brown insulator of any size and shape for 1100 volts grade complete all as specified and as directed . \nNote :- Serviceable insulators obtained from slitem No.06 of above will be re used. 50 EACH
22 22 M&L for stay assembly for LT complete with 300 x 500 x 6mm thick plate and 16mm dia stay rod, 7/3.15 mm GI stay strand and stay insulators all as shown in electrical Plate No. 1 of MES SSR Part-I including dismantling of old stay assembly complete all as specified and as directed .\nNote : - Loop insulator,Excavation & Earth work and, PCC shall be measured and paid for separately. 20 EACH \nSET
23 23 S&F loop type porcelain insulator, vitreous white, brown or green, over all dimension 65x90mm and clearance of hole 16mm complete all as specified and as directed. 15 EACH
24 24 Supply, fix, stringing and commisioning & testing of aluminium conductor steel reinforced (ACSR) conductor on existing LT poles including straining, binding with insulators with aluminium binding wire and providing PVC sleeves for jumpers complete all as specified and as directed .\nNote :- Measurement and payment shall be made by measuring horizontal distance between centres of two adjacent poles and compounding the weight of conductors of that size and length and 3% extra added for sag, jointing, jumpers etc complete all as specified and directed. 10 QTL
25 25 Fixing only by re-stringing and commisioning & testing of aluminium conductor steel reinforced (ACSR) conductor on existing LT poles including straining, binding with insulators with aluminium binding wire and providing PVC sleeves for jumpers complete all as specified and as directed .\nNote :- Serviceable ACSR conductors obtained from Sl item No.04 of above will be re used and measurement and payment shall be made by measuring horizontal distance between centres of two adjacent poles and compounding the weight of conductors of that size and length and 3% extra added for sag, jointing, jumpers etc complete all as specified and directed . 4 QTL
26 26 M&L in replacement PVC fibre separator for LT overhead line conductor 3/4 conductor for maintaining horizontal spacing complete with nut and bolts minimum two Nos in a span complete all as specified and as directed . 249 EACH
27 27 S&F in replacement PVC spiral type separator for LT overhead line conductor 3/4 conductor for maintaining horizontal spacing complete with nut and bolts complete all as specified and as directed . 300 EACH
28 28 M&L Galvanised steel wire 3.15mm or 4mm dia as earth wire complete all as specified and as directed . 1.8 QTL
29 29 M&L Galvanised steel wire 3.15mm or 4mm dia fabricated as in guarding cradles, hexagonal /rectangular complete all as specified and as directed . 1.2 QTL
30 30 Fixing only serviceable galvanised steel wire 3.15mm or 4mm dia as earth wire/guarding cradles complete all as specified and as directed \nNote:- Serviceable galvanised steel wire obtained from slitem No.05 of above will be re used. 0.6 QTL
31 31 Trimming / cutting of tree branches, bushes obstructing the HT/ LT OH lines, poles & stay making clearance at a distance of 3mtr from outer conductor of OH lines including cleaning of birdnest, creepers on poles/stays etc removal of rubbish to out side MD land complete all as specified and directed . 1500 RM
32 32 Cutting shurbs, vegetation, grass , bush, weed, trees and saplings not exceeding 30cm in girth, measured at a height of one metre above ground level in inside sub station building, climbing up towartds the poles pump house, OHT's, stay etc., cleaning bottom surface area of pole of stay not less than 1mx1m & inside the fencing of outdoor installations including removal of rubbish to out side MD land complete all as specified and directed . 200 SQM
33 33 Earthing complete with galvanized steel earth plate electrode 60cm X 60cm X 6mm thick buried directly in ground (earth pit not less than 2.25 metre deep below ground level) with top edge of plate not less than 1.5 metre below normal ground level connected to galvanized M.S. earth strip 25mm x4mm by means of bolts, nuts, check nuts and washers of galvanized iron mild steel all as shown in Electrical Plate No.5 of MES SSR Part-I connected to main switch board or main control board all as specified and testing on completion including provision of earth strip protected by galvanized iron 40mm bore light grade pipe and watering pipe shall be 20mm bore light grade including all excavation and earth work in any type of soil, PCC pit with pre-cast RCC cover, charcoal / salt, funnel etc complete all as specified and as directed.\n\nNote : - (i) The concrete pit shall be PCC 1:3:6 type C-1, 40mm thick pre-cast cover slab of RCC (1:2:4) type B-1 using 20mm graded crushed stone aggregate, reinforced with 8mm TMT bars @ 10 cm c/c on both sides with suitable cast iron handle shall be provided in lieu of cast iron cover shown in Electrical Plate No. 3 of MES SSR Part-I, (ii) Item includes the cost of GI pipe up to 7.50m for protection of earth wire/strip, (iii) Item includes the cost of earth lead wire/strip up to7.50m & (iv) PCC pit shall be provided at least 500mm away from the pit and not on the earth pit itself and the extra cost of additional length of watering pipe, bends, elbow etc shall be deemed included in the unit rate quoted. 25 EACH\nSET
34 34 Taking down existing old / unserviceable fitting/fixtures from LT Panel board after carefully disconnecting the electric connection and replace the same in position with new one to match with the existing or replacing the MCCBs/ other items as required in the other panel for the followings items.
35 34.01 Supply only in replacement of 96mm x 96mm square digital voltmeter having 0-500 volts range with in-built selector switch including making necessary connection in existing panel complete all as specified and as directed . 5 EACH
36 34.02 Supply only in replacement of indicator lamp LED type red,blue and yellow colour including making necessary connection in existing panel complete all as specified and as directed. 20 EACH \nSET
37 34.03 Supply only in replacement of digital ampere meter having 0-500 amps range with in-built selector switch and suitable size CT's size 96x96mm including making necessary connection in existing panel complete all as specified and as directed. 6 EACH \n
38 34.04 Supply only in replacement of MCCB,AC,415volts, 315Amp, 25KA, 4 pole, thermal magnetic release, adjustable 70%-100% magnetic setting 5-10 times including making necessary connection in existing panel complete all as specified and as directed . 3 EACH
39 34.05 Supply only in replacement of MCCB,AC,415volts,250 Amp, 25KA, 4 pole, thermal magnetic release, adjustable 70%-100% magnetic setting 5-10 times including making necessary connection in existing panel complete all as specified and as directed. 2 EACH
40 34.06 Supply only in replacement of MCCB,AC,415volts,200 Amp, 25KA, 4 pole, thermal magnetic release adjustable 70%-100% magnetic setting 5-10 times including making necessary connection in existing panel complete all as specified and directed by Engineer -in-Charge. 2 EACH
41 34.07 Supply only in replacement of MCCB,AC,415volts,160 Amp,25KA,4 pole, thermal magnetic release including making necessary connection in existing panel complete all as specified and directed by Engineer -in-Charge. 4 EACH
42 34.08 Supply only in replacement of MCCB,AC,415volts,125 Amp,16KA,4 pole, thermal magnetic release including making necessary connection in existing panel complete all as specified and directed by Engineer -in-Charge. 2 EACH
43 34.09 Supply only in replacement of MCCB,AC,415volts,100 Amp,16KA,4 pole, thermal magnetic release including making necessary connection in existing panel complete all as specified and as directed. 3 EACH
44 34.1 Supply only in replacement of MCCB,AC,415volts,63 Amp,16KA,4 pole, thermal magnetic release including making necessary connection in existing panel complete all as specified and as directed . 4 EACH
45 35 Supply, installation, testing and commisioning of LT bus bar enclosure (WT) cubicle type with RYB indication lamp, floor mounted type bus bars, TPN copper of size 25x3 mm -01 nos, mounted on 02 nos of angle iron of size 40x40x6 mm legs 0.75 mtr long each embedded in PCC outdoor type madeout 1.60 mm thick with CRCA sheet weather proof with locking arrangement duly painted with two coats of powder coated paint of approved shade after seven tank treatment process both internally and externally complete all as per directed and specified by Engg-in-charge. 4 EACH\nJob
46 36 M&L aluminium lugs eye lid or barrel type complete with cripping/ soldering etc., including removing the worn out lugs suitable for aluminium conductor cables / copper conductor cables of sizes from 16sqmm to 35sqmm complete all as specified and as directed. 35 EACH
47 37 M&L aluminium lugs eye lid or barrel type complete with cripping/ soldering etc., including removing the worn out lugs suitable for aluminium conductor cables / copper conductor cables of sizes from 50sqmm to 120sqmm complete all as specified and as directed. 50 EACH
48 38 M&L aluminium lugs eye lid or barrel type complete with cripping/ soldering etc., including removing the worn out lugs suitable for aluminium conductor cables / copper conductor cables of sizes from 150sqmm to 240sqmm complete all as specified and as directed. 40 EACH
49 39 M&L for boring/drilling by machines/manual horizontally under the road in any type of soil/rock without cutting/disturbing the existing road and inserting GI pipe of any size for drawing the cable complete all as specified and as directed \nNote :- GI pipe shall be measured and paid separately 15 RM
50 40 Demolition of old broken earth pit chamber and Repairing the earthing chamber pit of size 450X450X300mm ( external) & 250X250X250mm ( Internal) with PCC 1:3:6 type C-1by using 20 mm graded crushed stone aggregate and 40 mm thick RCC precast cover slab of 1:2:4 type B-1by using 20mm graded stone aggregat,e reinforced with 8mm TMT bars @ 100 mm C/C on both sides with cast iron handle complete all as pecified and as directed . 20 EACH JOB
51 41 S&F 4 sqmm 2 core, 1100 volt grade heavy duty cable PVC insulated aluminium solid conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connection suspended by insulating hangers not less than 01 mtr apart including 4 mm suspention wire. 250 RM
52 42 S&F 6 sqmm 2 core, 1100 volt grade heavy duti cable PVC insulated aluminium solid conduiter, served with inner sheathing of PVC tape and overall PVC sheathed in service connection suspended by insulating hangers not less than 01 mtr apart including 4 mm suspention wire. 300 RM
53 43 S&F 10 sqmm 2 core, 1100 volt grade heavy duti cable PVC insulated aluminium solid conduiter, served with inner sheathing of PVC tape and overall PVC sheathed in service connection suspended by insulating hangers not less than 01 mtr apart including 4 mm suspention wire. 500 RM
54 44 Maintenance of existing APFC panel with cleaning of dust inside by blower and cleaning of moving parts / contacts from CT cleaner, tightening of loose parts/ electrical wires, cleaning of contactors, relays and capacitors, junction point,servicing, oiling to cooling fan including testing of APFC relay with necessary setting with CTs / load adjustments to match with the APFC load management system complete with replacement of worn out unserviceable components / burnt wires/ timbles/ lugs of capacity 10 KVAR to 60 KVAR complete all as specified and as directed. \nNOTE :- (i) There are 17 Nos of APFC panel installed at different locations in Mil stn jassai and all the panels are to be maintained for the complete contract period . \n(ii) The power factor (PF) for all the 08 Nos APFC panel should be in between 0.95 to 0.99 , in case the PF is less than the power factor maintain above due to any reason, then the contractor shall liable to pay compenssation equivalent to JVVNL tarrif .\n(iii) The spare parts shall be of same make and capacity of existing one and shall be measured and paid separately.\n(iv) Replacement of bolt / nut / screws etc. shall deemed to be included in ther rate quoted. 7 Per Month
55 45 Supply only in replacement of MCB TP 415V olts 10KA , C curve 10-32 Amps in existing panel the make should be of the same of existing MCB to mach with existing holes/surface complete all as specified and as directed. 4 Each
56 46 Supply only in replacement of MCB TP 415 Volts 10KA , C curve 40-60 Amps in existing panel the make should be of the same of existing MCB to mach with existing holes/surface complete all as specified and as directed. 3 Each
57 47 Supply only in replacement of Contactor( Capacitor duty type) TP 415 V of capacity 10 to 32 Amps 2 Each
58 48 Supply only in replacement of Contactor( Capacitor duty type) TP 415 V of capacity 32 to 70 Amps 3 Each
59 49 Supply only in replacement of Capacitor 440 volts 50 HZ APP type electric conforming to IS: 13340/13441 & IEC-831-1 complete of capacity 1 KVAR 4 Each
60 50 Supply only in replacement of Capacitor 440 volts 50 HZ APP type electric conforming to IS: 13340/13441 & IEC-831-1 complete of capacity 5 KVAR 4 Each
61 51 Supply only in replacement of Capacitor 440 volts 50 HZ APP type electric conforming to IS: 13340/13441 & IEC-831-1 complete of capacity 10 KVAR 4 Each
62 52 Supply only in replacement of Capacitor 440 volts 50 HZ APP type electric conforming to IS: 13340/13441 & IEC-831-1 complete of capacity 20 KVAR 2 Each
63 53 Supply only in replacement of electric motor single phase 240V for cooling air fan compect size 150mm sweep for APFC panel \nMake :- ALMONARD or equivalent as approved by GE 3 Each
64 54 Supply only in replacement of volt meter 96 mm x 96 mm digital type 0 to 500 volts capacity 2 Each
65 55 Supply only in replacement of Ampremeter 96 mm x 96 mm digital type 0 to 200 amps capacity 3 Each
66 56 Supply only in replacement of CTs suitable for ampere meter 100/5 Amps Rating 2 Each
67 57 Supply only in replacement of CTs suitable for 200/5 Amps Rating 3 Each
68 58 Supply only in replacement of CTs suitable for 60/5 Amps Rating 5 Each
69 59 Supply only in replacement of APFC relay square flush type with protective device intelligent automatic processor based on electronic controller 6 stages for APFC panel 4 Each
70 60 Supply only in replacement of APFC relay square flush type with protective device intelligent automatic processor based on electronic controller 8 to 14 stages for APFC panel 3 Each
71 61 S&F in replacement of selector switch for Volt meter & Amp meter for existing suitable size complete all as specified and as directed. 3 Each
72 62 Spray painting to existing LT panel board/Kisok of any size after scrapping the existing paint and two coats of synethetic enamelled paint over a coat of red oxide primer complete all as specified and as directed. 9 Each Job