Repair And Maintenance Of Dg Sets , Panels , Starters With Connected Items And Solar Water Heater Under Ge Nagrota ., NAGROTA-Jammu And Kashmir

Military Engineer Services-MES has published Repair And Maintenance Of Dg Sets , Panels , Starters With Connected Items And Solar Water Heater Under Ge Nagrota .. Submission Date for this Tender is 08-02-2021. Starter Tenders in NAGROTA Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

26624528
Repair And Maintenance Of Dg Sets , Panels , Starters With Connected Items And Solar Water Heater Under Ge Nagrota .
Open Tender
Indian
Jammu And Kashmir
NAGROTA
08-02-2021

Tender Details

Repair And Maintenance Of Dg Sets , Panels , Starters With Connected Items And Solar Water Heater Under Ge Nagrota .

Key Value

Document Fees
INR 500 /-
EMD
INR 90000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: REPAIR AND MAINTENANCE OF DG SETS, PANELS, STARTERS WITH CONNECTED ITEMS AND SOLAR WATER HEATER UNDER GE NAGROTA.
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Dismantaling /Opening of upper portion of Disel Engine 50 KVA to 80 KVA(Make : Greaves/ Kirloskar/ Cumiuns/water cooled,turbo charged ,Vertical type for top over hauling, repair/ servicing of engine including taking out rediator /fuel pump,water Pump,Turbo charger etc:-\n(a) Dismantaling/Opening of complete cyllinder head assebly rockers arms assembly piston head assembly ,sleeves by removing nuts &bolts for repair complete.\n(b) Servicing & washing of complete engine parts with kerosine oil\n( c) Re- assembling of engine after replacementof UNSV/defective parts with new parts as listed in given below per Job shall be deemed to be included in this rates and testing of engineas per company recommendation after reassembling all parts as directed to the satifaction of the Engr-in -Charge\nNote : Repair and Transportation charge for carrying out repair & reinstall on same installation back shall be deemed to be included in this rates.\nS&F in replacement of following parts given below , rates are included in above item\ni) Valve Exhaust -06 Nos\nii)Valve inlet -06 \niii)insert Valve Seat -12 Nos\n iv)Guide Valve -12 Nos\nv)Cup Injector -06 Nos 2 Each Job
2 1.01 vi) Fip Element -06 Nos\nvii) Gasket Set-01 Nos\nviii) Hose Pipe -01 Nos\nix) Fuel Filter -02 Nos\nx) Lubrication Oil Filter -02 Nos\nxi) Super By Pass Fillter -01 Nos\n xii) Hose Clip Set -01 Nos\nxiii) Piston set Complete -06 Nos\nxiv Ring Set Complete -06 Nos\nxv) Cyllinder Linner -06 Nos\nxvi) Connecting Rod Bearing -06 Pair\nxvii) Gasket Set Cyllinder Head -06 Nos\nxvii) Callibration of Fuel Pump -01 Job\n xix )Head Repair Work - 01 Job\nxx ) Callibration of injectors of Nozzels -01 Job\n xxi ) Lubrication Oil Pump -01 Job\n'xxii ) O ' Ring Set Complete -01 Nos\n xxiii) Set of Fuel Flexible Pipe -01 Nos\nxxiv) Stem Seal - 12 Nos
3 2 Dismantaling /Opening of upper portion of Disel Engine 30 KVA to 40 KVA(Make : Greaves/ Kirloskar/ Cumiuns/water cooled,turbo charged ,Vertical type for top over hauling, repair/ servicing of engine including taking out rediator /fuel pump,water Pump,Turbo charger etc:-\n(a) Dismantaling/Opening of complete cyllinder head assebly rockers arms assembly piston head assembly ,sleeves by removing nuts & bolts for repair complete.\n(b) Servicing & washing of complete engine parts with kerosine oil\n( c) Re- assembling of engine after replacementof UNSV/defective parts with new parts as listed in given below per job shall be deemed to be included in this rates and testing of engineas per company recommendation after reassembling all parts as directed to the satifaction of the Engr-in -Charge\nNote : Repair and Transportation charge for carrying out repair & reinstall on same installation back shall be deemed to be included in this rates.\n Supply & fix in replacement of following parts given below rates are included in above item \ni) Valve Exhaust -03 Nos\nii)Valve inlet -03 \niii)insert Valve Seat -6 Nos\n iv)Guide Valve -6 Nos\nv)Cup Injector -03 Nos 3 Each Job
4 2.01 vi) Fip Element -03 Nos\nvii) Gasket Set-01 Nos\nviii) Hose Pipe -01 Nos\nix) Fuel Filter -02 Nos\nx) Lubrication Oil Filter -02 Nos\nxi) Super By Pass Fillter -01 Nos\n xii) Hose Clip Set -01 Nos\nxiii) Piston set Complete -03 Nos\nxiv) Ring Set Complete -03 Nos\nxv) Cyllinder Linner -03 Nos\nxvi) Connecting Rod Bearing -03 Pair\nxvii) Gasket Set Cyllinder Head -03 Nos\nxvii) Callibration of Fuel Pump -01 Job\n xix )Head Repair Work - 01 Job\nxx ) Callibration of injectors of Nozzels -01 Job\n xxi ) Lubrication Oil Pump -01 Job\n'xxii ) O ' Ring Set Complete -01 Nos\n xxiii) Set of Fuel Flexible Pipe -01 Nos\nxxiv) Stem Seal - 6 Nos
5 3 Dismantaling /Opening of upper portion of Disel Engine 12.5 KVA to 25 KVA(Make : Greaves/ Kirloskar/ Cumiuns/water cooled,turbo charged ,Vertical type for top over hauling, repair/ servicing of engine including taking out rediator /fuel pump,water Pump,Turbo charger etc:-\n(a) Dismantaling/Opening of complete cyllinder head assebly rockers arms assembly piston head assembly ,sleeves by removing nuts & bolts for repair complete all as specified and directed.\n(b) Servicing & washing of complete engine parts with kerosine oil\n( c) Re- assembling of engine after replacementof UNSV/defective parts with new parts as listed in given below Per job shall be deemed to be included in this rates and testing of engine as per company recommendation after reassembling all parts as directed to the satifaction of the Engr-in -Charge\nNote : Repair and Transportation charge for carrying out repair & reinstall on same installation back shall be deemed to be included in this rates.\nSupply & fix in replacement of following parts given below rates rates are included in above item .\ni) Valve Exhaust -03 Nos\nii)Valve inlet -03 \niii)insert Valve Seat -6 Nos\n iv)Guide Valve -6 Nos\nv)Cup Injector -03 Nos 3 Each Job
6 3.01 vi) Fip Element -03 Nos\nvii) Gasket Set-01 Nos\nviii) Hose Pipe -01 Nos\nix) Fuel Filter -02 Nos\nx) Lubrication Oil Filter -02 Nos\nxi) Super By Pass Fillter -01 Nos\nxii) Hose Clip Set -01 Nos\nxiii) Piston set Complete -03 Nos\nxiv) Ring Set Complete -03 Nos\nxv) Cyllinder Linner -03 Nos\nxvi) Connecting Rod Bearing -03 Pair\nxvii) Gasket Set Cyllinder Head -03 Nos\nxvii) Callibration of Fuel Pump -01 Job\nxix )Head Repair Work - 01 Job\nxx ) Callibration of injectors of Nozzels -01 Job\nxxi ) Lubrication Oil Pump -01 Job\n'xxii ) O ' Ring Set Complete -01 Nos\n xxiii) Set of Fuel Flexible Pipe -01 Nos\nxxiv) Stem Seal - 6 Nos
7 4 Servicing of DG Sets of capacity 250 KVA of make Kirloskar/ Cummins/CG/Ashok Leyland by the authorised Engineer of respective manufacturer on half yearly basis to make the DG Set continous operational condition including the following checkings all as specified and directed by Engr-in -charge:-\n(i) Removing the existing engine oil, clean the oil sump and refilling with required quantity of new engine oil 20W40 & coolant to top up .(Note :- New oil,coolant will be measured and paid separately) \n(ii) Checking of fan motor hub\n(iii) Checking exhaust and inlet manifold belt and cap screw\n(iv)Cleaning of radiator inside and out side thoroughly with solution (caustic soda) to the entire satisfaction of Eng-in-charge by removing and re-fixing in original position after cleaning.\n(v) Checking and adjusting injector and valves, tappet and replace the gasket including cost of gasket.\n(vi) Cleaning fuel inlet connections and screw\n(vii) Checking of vibration damper and rectified.\n(viii) Servicing of turbocharger by checking, leakage tightening of mounting screws & nuts and replace oil.\n(ix) Checking water temperature safety control \n(x) Checking and correcting up impeller of water pump for excess play. \n(xi) Servicing of governer and Changing of governor oil. \n(xii) Checking and adjusting all fan belt.\n(xiii) Any other check as per manufacturer`s instructions\nNote:- Necessary spare parts required if any will be measured and paid under relevant items and fixed in replacement following items: 1 Each Job
8 4.01 (a) Supply only in repairs Kit, fuel filter and ring. 1 Each
9 4.02 (b) Supply only in repairs Element for Lubrication oil filter 1 Each
10 4.03 (c)Supply only in repairs Kit, Element of super bypass filter 1 Each
11 4.04 (d) Supply only in repairs Seal, O Ring and Air cleaner 1 Each
12 4.05 (e ) Supply only in repairs Kit Conversion 1 Each Set
13 4.06 (e ) Supply only in repairs Kit Conversion. 1 Each
14 4.07 (f )Supply only in repairs Gasket, Rocker lever cover. 1 Each
15 5 All as per item No.4.00 above but for DG Sets of Capacity 180 KVA DG set, 2 Each Job
16 5.01 (a) Supply only Kit, fuel filter and ring 2 Each Set
17 5.02 (b) Supply only Element for Lubrication oil filter. 2 Each
18 5.03 (c) Supply only Kit, Element of super bypass filter. 2 Each Set
19 5.04 (d) Supply only Seal, O Ring and Air cleaner. 2 Each
20 5.05 (e ) Supply only Kit Conversion 2 Each Set
21 5.06 (f )Supply only Gasket, Rocker lever cover 2 Each
22 6 All as per item No.4.00 above but for DG Sets of Capacity 100 KVA DG set 1 Each Job
23 6.01 (a) Supply only Kit, fuel filter and ring 1 Each Set
24 6.02 (b) Supply only Element for Lubrication oil filter. 1 Each
25 6.03 (c)Supply only Kit, Element of super bypass filter. 1 Each Set
26 6.04 (d) Supply only Seal, O Ring and Air cleaner. 1 Each
27 6.05 (e ) Supply only Kit Conversion 1 Each Set
28 6.06 (f )Supply only Gasket, Rocker lever cover 1 Each
29 7 All as per item No.4.00 above but Diesl Engine of 62.5/ 63/50 KVA DG set 5 Each Job
30 7.01 (a) Supply only Kit, fuel filter and ring 5 Each Set
31 7.02 (b) Supply only Element for Lubrication oil filter. 5 Each
32 7.03 (c)Supply only Kit, Element of super bypass filter. 5 Each Set
33 7.04 (d) Supply only Seal, O Ring and Air cleaner. 5 Each
34 7.05 (e ) Supply only Kit Conversion 5 Each Set
35 7.06 (f )Supply only Gasket, Rocker lever cover 5 Each
36 8 All as per item no.4.00 above but DG Sets of Capacity 40/30 KVA DG set 5 Each Job
37 8.01 (a) Supply only Kit, fuel filter and ring 5 Each Set
38 8.02 (b) Supply only Element for Lubrication oil filter. 5 Each
39 8.03 (c)Supply only Kit, Element of super bypass filter. 5 Each Set
40 8.04 (d) Supply only Seal, O Ring and Air cleaner. 5 Each
41 8.05 (e ) Supply only Kit Conversion 5 Each Set
42 8.06 (f ) Supply only Gasket, Rocker lever cover 5 Each
43 9 All as per item no.4.00 above but DG Sets of Capacity 25/20/15 KVA DG set 12 Each Job
44 9.01 (a) Supply only Kit, fuel filter and ring 12 Each Set
45 9.02 (b) Supply only Element for Lubrication oil filter. 12 Each
46 9.03 (c) Supply only Kit, Element of super bypass filter. 12 Each Set
47 9.04 (d) Supply only Seal, O Ring and Air cleaner. 12 Each
48 9.05 (e ) Supply only Kit Conversion 12 Each Set
49 9.06 (f )Supply only Gasket, Rocker lever cover 12 Each
50 10 M&L for Rewinding of armature of Dynamo/alternators of 62.5/63 KVA DG set 24 volts with `F' class copper wire to match existing gauge including dismantling of old coil , cleaning thoroughly winding with super enameled copper wire of existing size and gauge,varnishing, drying etc and fixed with dynamo/alternator properly tesing and commissioning all as specified all and directed by Engr-in-Charge. 4 Each Job
51 11 S & F repair radiator hoses of size 40mm dia or as per existing dia and 60 cm length for any capacity of DG set including jublee clip, clamp nuts etc are properly fixed and connected.as directed to the satifaction of the Engr-in -Charge 6 Each
52 12 M&L for Rewinding of the armature of self starter of 62.5/63 KVA DG set with `F' class 62.5/63 KVA copper wire as per existing gauge dismantling the old coil cleaning throghly winding with super enameled coppper conductor of existing size and gauge , varnishing drying and fixing back with self starter properly tesing and commissioning as directed to the satifaction of the Engr-in -Charge 6 Each Job
53 13 S & F in repalacement of flexible pressure pipe for lubricant size of 60 cm length for oil and fuel connection for complete suitable for 180/100/82.5 KVA/63 KVA Engineas directed to the satifaction of the Engr-in -Charge. 6 Each Set
54 14 Supply and filling Engine oil 15W/40 250 Ltr
55 15 S& Fill distilled water packed in sealed gallan of 5 Ltrs 320 Ltr
56 16 Supply and filling water coolant(diluted)in radiator including removal of old water/coolant, all as directed by Engineer-in-Charge. 200 Ltr
57 17 Dismantling and removing of water pump assembly of 100/125 KVA DG Set complete from the engine,repair/overhauling the same by replacing tornout components like bearing,impeller,bushes, oil seal,water seal,gaskets etc. reassembling,refixing and testing complete as directed to the satifaction of the Engr-in -Charge 3 Each Job
58 18 Repair/overhauling of self starter including replacement of worn out clutch assembly,bush,spring,plunger assembly, solenoid switch,carbon brushes,brush spring etc.as directed to the satifaction of the Engr-in -Charge for the following DG Sets:-
59 18.01 250 KVA DG set 1 Each Job
60 18.02 110/100/160 KVA DG Set 2 Each Job
61 18.03 80 KVA DG set 2 Each Job
62 18.04 63 KVA DG Set 3 Each Job
63 18.05 20/25/40 KVA DG Set 3 Each Job
64 19 M & L for replacement of totally damaged self starter complete assembly suitable for 62.5/63 KVA capacity of DG Set 6 Each
65 20 Repair/overhauling of dynamo including replacement carbon, brushes holder, spring, commutator /slipring assembly bearing, regulator etc. of any make, type and 62.5/63 KVA. 5 Each Job
66 21 Supply in replacement of electrically operated fuel shut down valve assembly complete testing and commissioning as specified and directed by Engr.in-charge including dismantling and removal of old U/S valves of 62.5/63 KVA DG set. 5 EACH
67 22 Repair to battery charging unit 24 VDC 180 AH portable/panel mounting type by replacing defective relays,selector switch, ampere meter, volt meter, internal wiring with suitable size copper conductor cables, rewinding of defective transformer etc.compete. 5 Job
68 23 Servicing/repairs of 62.5/63 KVA AMF panel complete including cleaning resetting/adjustment of relays,calibration of time delay relays, checking and replcement of diods, if required ,resistors contactor etc. complete for any make type and capacity of DG sets. 5 JOB
69 24 Disconnecting and dismantling the alternator unit of DG Set from the base plate of the DG set and transporting to workshop for repair, dismantling the unit, further separating the armature from the startor carefully, cutting and taking out the burnt windings of the alternator carefully, cleaning the slots and , duly applying the insulation and assembling the stampings inserting in position in the startor including applying slot insulation and rewinding of the alternator startor winding with super enameled copper conductor of same gauge and same number of turns as that of existing one including replacement of carbon brushes tapping the windings and bringing out the coil conections for production of 3 phase 415 volt 50 HZ AC supply and preheating the windings and applying insulating varnish and drying the windings in oven and assembling the unit and transporting back to installation and fixing on base plate and coupling with the DG set and testing complete all as specified and directed.
70 24.01 (a)250 KVA capacity 1 JOB
71 24.02 (b) 125/100/180 KVA capacity. 2 JOB
72 24.03 (c) 63 KVA 3 JOB
73 24.04 (d ) 50 KVA 1 JOB
74 24.05 (e) 20/25/40 KVA 4 JOB
75 25 Supply in replacement of diode assembly complete suitable to match the existing one of 250 KVA alternator excitor unit. 1 EACH
76 26 Supply in replacement of diode assembly complete suitable to match the existing one of 180/125/100KVA alternator excitor unit. 4 EACH
77 27 Supply in replacement of diode assembly complete suitable to match the existing one of 63/50/40/30 KVA alternator excitor unit. 10 EACH
78 28 Supply in replacement of diode assembly complete suitable to match the existing one of 12.5/20/25 KVA alternator excitor unit. 10 EACH
79 29 Supply in replacement of PVC insulated battery lead with 16 Sq.mm copper conductor cable of length 2 mtr with copper/brass clamps and lugs for fixing on battery terminals and self starter complete as specified and as directed. 8 EACH
80 30 Supply in replacement of rectifiers for alternators suitable for Gensets upto 40/63/82.5/100/110KVA capacity complete as specified and as directed. 8 EACH
81 31 Supply and fixing carbon brushes suitable for alternators upto 250 KVA gensets. complete as specified and as directed. 6 Each set
82 32 Supply in replacement of RPM meter complete with cable and accessories at the last range 0 to 2500 complete as specified and as directed. 6 EACH
83 33 Supply in replacement of water temperature gauge complete with cable and accessories at the last range 0 to 150 degree centigrate complete as specified and as directed. 6 EACH
84 34 Supply in replacement of oil temp gauge as per existing site requirement complete as specified and as directed. 6 EACH
85 35 Supply in replacement of oil pressue gauge as per existing site requirement complete as specified and as directed. 6 EACH
86 36 Dismantling the defective Fuel Injector Assembly of any capacity from the existing foundation and engine including taking down all electrical connections transporting to approved authorised workshop, after setting up opening the complete, connector plate, gasket & complete overhauling re- assembling the Fuel Injector after transporting back to site re-installing carrying out alignment of complete DG set reconnecting up all electrical connections testing and commissioning complete the following capacity of DG set \nNote:- (a) Rate quoted shall be deemed to be inclusive making good the distrubed surfaces\n(b) The DG set shall be tested for the satisfaction of Engr -in -charge to achive designed parameters.
87 36.01 (a)180 KVA capacity DG Set 1 Each Job
88 36.02 (b) 100/62.5/50 KVA DG 5 Each Job
89 36.03 (c) 40/30/25/20 KVA DG 5 Each Job
90 37 S & F in repair battery terminal brass superior quality suitable for 180 AH 12 Volts Battery 10 Each
91 38 Supply and fixing in replacement of ignition switch and key of 110/100/ 82.5 KVA DG Set 5 Each
92 39 Supply and fixing in replacement of ignition switch and key of 63/40 KVA DG Set 5 Each
93 40 Dismantling/taking down existing AVR unit of 100 KVA to 250 KVA DG Set . Supply and fixing in replacement of AVR unit to match the existing AVR unit, complete all as specified and directed by Eng-in charge. 2 Each
94 41 All as per items No. 40 above but the capacity of 40/50/ 63 KVA 8 Each
95 42 All as per items No. 40 above but the capacity of20/25/12.5 KVA 6 Each
96 43 S&F in replacement of contactor suitable for AMF panel contactor MNX 32 3pole 240V as per existing contactor of site 4 Each
97 44 S&F in replacement of contactor suitable for AMF panel contactor MNX 25 3pole 240V as per existing contactor of site 4 Each
98 45 S&F in replacement of contactor suitable for AMF panel contactor MNX 16 3pole 240V as per existing contactor of site 4 Each
99 46 S&F in replacement maintenance free lead acid battery 12 volts 180 AH complete all as specified and as directed. 8 Each
100 47 S&F in replacement maintenance free lead acid battery 12 volts 150 AH complete all as specified and as directed. 8 Each
101 48 S&F in replacement maintenance free lead acid battery 12 volts 130 AH complete all as specified and as directed. 10 Each
102 49 S&F in replacement maintenance free lead acid battery 12 volts 100 AH complete all as specified and as directed. 10 Each
103 50 S&F in replacement on load change over switch, 63 Amp capacity, 3 phase, 4 pole, 415 volts, 50Hz, side handle operated, with and including MS sheet metal enclosure having advance neutral complete all as specified and as directed. 2 Each
104 51 All as per item No 50 here-in-before but 100 Amp 2 Each
105 52 All as per item No 50 here-in-before but 200 Amp 2 Each
106 53 All as per item No 50 here-in-before but 400 Amp 2 Each
107 54 M&L for servicing/ cleaning of MS diesel tank of DG set 180/160/100 KVA by draining out the diesel from tank, cleaning the tank with soap water/ suitable solution and painting the external surface with one coat of synthetic enamel paint of existing colour including repalcement of drain valve, outlet pipe complete all as specified and as directed. 6 Each Job
108 55 M&L for servicing/ cleaning of MS diesel tank of DG set 62.5/40/50/25 KVA by draining out the diesel from tank, cleaning the tank with soap water/ suitable solution and painting the external surface with one coat of synthetic enamel paint of existing colour including repalcement of drain valve, outlet pipe complete all as specified and as directed. 15 Each Job
109 56 S&F in replacement of MCCB, three pole, 400 Amp 415 volts, 50 Hz breaking capacity not less than 35 kA with adjustable thermal and adjustable magnetic protection release with spreader links, Ics = 100% Icu complete all as specified and as directed. 1 Each
110 57 All as per item No 56 here-in-before but four pole, 250 Amp breaking capacity not less than 25 kA 4 Each
111 58 All as per item No 56 here-in-before but four pole, 160 Amp breaking capacity not less than 25 kA 6 Each
112 59 All as per item No 56 here-in-before but four pole, 125 Amp breaking capacity not less than 25 kA 6 Each
113 60 All as per item No 56 here-in-before but four pole, 100 Amp breaking capacity not less than 25 kA 4 Each
114 61 S&F in replacement, fan belt suitable for 12.5 KVA DG set complete all as specified and as directed. 1 Each Set
115 62 All as per item No 61here-in-before but suitable for 20/25//30 KVA DG set complete all as specified and as directed. 12 Each Set
116 63 All as per item No 61 here-in-before but suitable for 40/50 KVA DG set complete all as specified and as directed. 6 Each Set
117 64 All as per item No 61 here-in-before but suitable for 62.5/63 KVA DG set complete all as specified and as directed. 6 Each Set
118 65 All as per item No 61 here-in-before but suitable for 100 KVA DG set complete all as specified and as directed. 1 Each Set
119 66 All as per item No 61 here-in-before but suitable for 180 KVA DG set complete all as specified and as directed. 2 Each Set
120 67 All as per item No 61 here-in-before but suitable for 250 KVA DG set complete all as specified and as directed. 1 Each Set
121 68 Dismentling/ taking down complete radiator assembly of DG set 180 KVA and transporation to market for repair by :-\n(i) Opening the radiator assembly with brazing/ welding for repair/ services.\n(ii) Cleaning of all water tube with diluted solution of HCL & cleaning with water preasure & removing the sludge and dust from inside the tank by flushing out.\n(iii) Repair of fins by soldring/ brazing. \n(iv) Repair of bottom brass water tank by soldring/ brazing. \n(v) Repair of radiator hose assembly.\n(vi) Fixing the complete radiator assembly to its orignal position and testing complete 2 Each Job
122 69 All as per item No 68 here-in-before but DG set 100 KVA. 2 Each Job
123 70 All as per item No 68 here-in-before but DG set 62.5 /63KVA. 6 Each Job
124 71 All as per item No 68 here-in-before but DG set 20/25/40 KVA. 8 Each Job
125 72 Taking Down and Shifting of Existing DG Sets 62.5/100 KVA and Reinstalled of DG Sets at another location of any Installation of GE Nagrota and reinstall connected panel with wiring Complete completeTransportation charge , any store for connection and labour charge shall be deemed to job all as specified and directed by Engineer-in-charge. 7 Each
126 73 Supply in replacement of copper Thimble of size 95 Sqmm and taking down of thimble from existing panel reconnecting up all electrical connections testing and commissioning complete as directed to the satifaction of the Engr-in -Charge 80 Each
127 74 Supply in replacement of copper Thimble of size 75 Sqmm and taking down of thimble from existing panel reconnecting up all electrical connections testing and commissioning complete as directed to the satifaction of the Engr-in -Charge 80 Each
128 75 Supply in replacement of copper Thimble of size 50 Sqmm and taking down of thimble from existing panel reconnecting up all electrical connections testing and commissioning complete as directed to the satifaction of the Engr-in -Charge 80 Each
129 76 Supply in replacement of copper Thimble of size 35 Sqmm and taking down of thimble from existing panel reconnecting up all electrical connections testing and commissioning complete as directed to the satifaction of the Engr-in -Charge 80 Each
130 77 Supply in replacement of 24 Volt Relay ,taking down and reconnecting up all electrical connections testing and commissioning complete as directed to the satifaction of the Engr-in -Charge 10 Each
131 78 Supply in replacement of 12 Volt Relay ,taking down and reconnecting up all electrical connections testing and commissioning complete as directed to the satifaction of the Engr-in -Charge 10 Each
132 79 Supply in replacement of VMMR , taking down and reconnecting up all electrical connections testing and commissioning complete as directed to the satifaction of the Engr-in -Charge 10 Each
133 80 Supply and fixing in replacement of Didital volt meter 0 to 500 volt as per existing size complete all as specified and directed. 12 Each
134 81 Supply and fixing in replacement of Digital Amp meter 0 to 600 Amp as per existing size complete all as specified and directed. 12 Each
135 82 Supply and fixing in replacement of Digital Frequency meter 0 to 50 Hz as per existing size complete all as specified and directed. 12 Each
136 83 Supply and fixing in replacement of indicator lamp assembly complete LED type suitable for the existing system supply voltage for the existing system supply voltage 230V / 440 V AC including taking down old lamp assembly 20 Each set
137 84 Supply and fixing in replacement of copper cable un armored PVC insulated & sheathed copper conductor cable 1100 Volts grade of size 16 Sqmm 3 core complete all as specified and directed. 250 RM
138 85 Disconnecting & taking up or down the existing old unserviceable solar panel (flat collector plate ) of any description and in any position from the existing location for necessary repairs & maintenance / replacement all as directed. 60 Each Job
139 86 Taking down existing unserviceable solar plate of any description and supply and fixing new solar flat plate collector complete of existing shape & size. complete all as specified & directed by Engineer-in-Charge. 50 Each
140 87 Taking down old existing unserviceable thermal insulation of any description and in any position including aluminum foil cladding from GI pipe lines 15 to 25mm dia complete all as directed. (NOTE : Aluminium foil cladding obtained in serviceable condition shall be re-used in the work ). 100 RM
141 88 Dismantling the solar panel (made of flat collector plates) of any description, material and labour for cleaning the glass by washing with using soft detergent, cleaning & de-scaling the inside surface of copper fins / tubes with suitable size of drill rod, wire brush & with circulating concentrated de-scaling solution(ORISCALE BLASTER) mixed with water in suitable proportion circulating through pump till the complete deposits/scale is removed and approved by the Engineer-in-Charge, brazing the leaking copper tubes, fixing the copper tube & fins properly in their respective positions, reassembling the solar system after servicing / maintenance including replacement of flanges made out of gun metal, nuts, bolts & washers, gaskets etc., fixing & installation of the solar flat collector plate in position and its testing to the entire satisfaction of Engineer-in-Charge. 40 Each Job
142 89 Material & Labour for Insulation of GI pipe 15 to 25mm dia with providing 25mm uniform thickness of glass wool fibers having density of 48 Kg per Cum, including cladding with using old serviceable aluminium foil all as directed. \n 150 RM
143 90 Supply and fixing GI tubings medium grade 15mm bore dia ISI Mark with all fittings such as elbow, bends, sockets, nipples and union etc and fixed complete laid in trench/wall for the following sizes including taking down of existing old GI pipes complete all as specified and directed by Engr-in-charge :- 80 RM
144 91 All item same as Ser item no 90 but 20mm bore dia 80 RM
145 92 All item same as Ser item no 90 but 25mm bore 80 RM
146 93 All item same as Ser item no 90 but 40mm bore dia 80 RM
147 94 All item same as Ser item no 90 but 50mm bore dia 20 RM
148 95 Supply and Fixing 15mm Gun metal Globe or gate valve with iron wheel head screwed both ends for iron pipe of the following bore sizes complete all as per spd and directed by Engineer-in-charge. 40 Each
149 96 All item same as Ser item No. 95 but 20mm bore dia 30 Each
150 97 All item same as Ser item No. 95 but 25mm bore 30 Each
151 98 All item same as Ser item No. 95 but 40mm bore dia 30 Each
152 99 All item same as Ser item No. 95 but 50mm bore dia 10 Each
153 100 Disconnecting & taking out existing unserviceable float valve assembly 20mm bore of any description and in any position and supply, fixing, jointing and testing, 20mm bore, ball brass valve, high pressure with polythene float and fly nut complete, screwed for iron pipe or brass ferrule and fixed complete all as directed. 25 Each
154 101 Disconnecting & taking out existing unserviceable tap, 15mm bore of any description and in any position and supply, fixing, jointing and testing, 15mm bore, concussive push button taps of cast copper alloy, chromium plated, screwed for iron pipe and fixed complete all as directed. 15 Each
155 102 Disconnecting & taking out existing unserviceable non return valve, 25mm bore of any description and in any position and supply, fixing new 25mm bore non return valve, cast iron, ISI marked complete all as specified & directed by Engineer-in-Charge. 10 Each
156 103 Disconnecting & taking out old existing unserviceable temperature meter of any description and in any position and supply, fixing new temperature meter, 0-100 ºC range, dial type suitable for 15mm GI pipe including all necessary fittings complete all as specified and directed. 5 Each
157 104 Opening of existing aluminium cladding from tank ,cleaning and stacking the same for reuse ,taking out glass wool and repairing the stainless steel tank and repairing the leakage by means of TIG welding as approved ,refilling of glass wool ,aluminium cladding by using old aluminium sheet complete all as directed by Engr- in -charge. 20 Each Job
158 105 Disconnecting and taking out old existing unserviceable water heating element of any description and in any position and supply, fixing new water heating element of capacity 2KW/3.0 KW with suitable thermostat including all necessary fittings complete all as specified and directed. 150 Each
159 106 Disconnecting & taking up or down existing unserviceable copper conductor flexible cable of any size & any description and supplying, fixing, connecting & testing new 3 core copper conductor flexible cable of 2.5 sqmm size, PVC insulated and PVC sheathed suitable for 1100 volts grade complete all as specified and directed by Engineer-in-Charge. 200 RM
160 107 Supply & fixing MCBs SPN, 32 Amps capacity 50 Each
161 108 M&L for earthing complete for bldg with galvanized mild steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 meters below ground level) with top edge of earth plate not less than 1.5 meters below ground level connected to galvanized earth wire 4.00 mm dia by means of nuts, bolts, thimbles, chuck nuts, washers of GI or steel, PCC (concrete chamber of size 300 mm x 300 mm x 300 mm inside dimension) shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate with fair finish , internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4, funnel with wire mesh of 22 gauge, 80 mm thick PCC pit cover 320 mm x 320 mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with XPM, JALLI pit shall be filled with charcoal dust and common salt all as shown in electrical plate No 3 of MES SSR Part-I (2009) as specified including provision of 15mm dia medium grade GI pipe for earth wire protection and 20 mm dia for watering complete , all excavation and earth work & connecting the earthing to an earthing test point / main switch board as specified and testing on completion, complete all as specified and directed. 4 Each set
162 109 Supply and fixing in replacement of insulated tank of 500 Ltr capacity with Electric back complete as per sample all as specified and directed by Eng in charge. 20 Each
163 110 Supply and fixing in replacement of insulated tank of 300 Ltr capacity with Electric back complete as per sample all as specified and directed by Eng in charge. 15 Each
164 111 Material & labour for damaged solar collectors of copper fins / tubes with suitable size of drill rod, wire brush & with circulating concentrated , brazing the leaking copper tubes, fixing the copper tube & fins properly in their respective positions, reassembling the solar system after replacement of flanges,collectors made out of gun metal, nuts, bolts & washers, gaskets etc., fixing & installation of the solar flat collector plate in position and its testing to the entire satisfaction of Engineer-in-Charge. 4 Each Job
165 112 Supply in replacement of Service cable/wire 1100 V flat twin core aluminium stranded conductor of size 6 Sqmm complete all as specified and directed. 250 RM
166 113 Supply in replacement of Service cable/wire 1100 V flat twin core aluminium stranded conductor of size 10 Sqmm complete all as specified and directed. 250 RM
167 114 Supply in replacement of Service cable/wire 1100 V flat twin core aluminium stranded conductor of size 16 Sqmm complete all as specified and directed. 250 RM
168 115 Supply in replacement of MCCB 250 Amps 4 pole 415 volt 35 KA with adjustable thermal and adjustable magnetic settings fixed in repair. 1 Each
169 116 Supply in replacement of MCCB 200 Amps 4 pole 415 volt 25 KA with adjustable thermal and adjustable magnetic settings fixed in repair. 1 Each
170 117 Supply in replacement of MCCB 100 Amps 4 pole 415 volt 25 KA with adjustable thermal and adjustable magnetic settings fixed in repair. 2 Each
171 118 S&F in place of thermostat switch range upto 80”C suitable for 500 ltrs Tank cap water heater. Complete all as specified and directed 180 Each
172 119 Deduction to be made from BOQ for schedule of credit (Sch 'A' Part - II) Amount of Rs. 1,41,130.00 during AOC\nNote:- Tenderers shall not quote for this Schedule
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail