Repair/Replacement Of Lt Panels / Feeder Pillar Box And Connected Work In Map And Otm Under Zone A At Bathinda Under Ge ( U ) Bathinda ., Garrison Engineer Utility Bathinda MIil Stn-Punjab

Military Engineer Services-MES has published Repair/Replacement Of Lt Panels / Feeder Pillar Box And Connected Work In Map And Otm Under Zone A At Bathinda Under Ge ( U ) Bathinda .. Submission Date for this Tender is 06-02-2021. Feeder Pillar Tenders in Garrison Engineer Utility Bathinda MIil Stn Punjab. Bidders can get complete Tender details and download the document.




Tender Notice

26616135
Repair/Replacement Of Lt Panels / Feeder Pillar Box And Connected Work In Map And Otm Under Zone A At Bathinda Under Ge ( U ) Bathinda .
National Competitive Bid
Indian
Punjab
Garrison Engineer Utility Bathinda MIil Stn
06-02-2021

Tender Details

Repair/Replacement Of Lt Panels / Feeder Pillar Box And Connected Work In Map And Otm Under Zone A At Bathinda Under Ge ( U ) Bathinda .

Key Value

Document Fees
INR 500 /-
EMD
INR 56000.0 /-
Tender Value
INR 28 Lakhs /-

BOQ Items

Name of Work: :REPAIR/REPLACEMENT OF LT PANELS / FEEDER PILLAR BOX AND CONNECTED WORK IN MAP AND OTM UNDER ZONE 'A' AT BATHINDA UNDER GE(U) BATHINDA.
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Taking down old unserviceable LT panel of any discription and size including demolished PCC foundation and all accessories such as MCCB/Cubical type switch /Measuring instruments /indicator lamps etc. complete all as directed. 16 Each Job
2 2 Supply, fabricating, installation, testing , commissioning and electrically connecting floor mounted panel polycarbonate CPRI approved OEM made LT Panel shall be made of modular Polycarbonate Thermoplastic Enclosures which should be UV resistance , Degree of protection against mechenical load should be IK08n (05 Joule ) in accordance with IEC 62262. The manufacturer of panel shall submit a copy of CPRI Test report in Polycarbonate of Degree of ingress Protection IP65 in accordance with IEC 60529.The gasket should be internally embedded made of polyurethane. The panel should pass glow wire test 960 degree in accordance with 60695-2 11 Flame retardant and self- extinguising , embeding / grouting / placing in PCC (1:2:4) type B1 using 20 mm graded crushed stone aggregate in foundation , including necessay earth work , including all connections / control wiring incoming / outgoing with suitable size of PVC insulated copper conductor cable of 1100 / 650 vot grade comprising of following accessories including testing Copper Busbar of size 30x2x10 (600A) for Main and riser as per MCCB Capacity 1 A=1Sqmm with phase & Neutral color code sleeves complete all as directed.\nMake- Hensel/Rittal/L&T/Schneider/ABB or equivalent in CPRI & CMD approved. (a) MCCB 4 pole , 415 volt, 250 Amp rating with breaking capacity 36 KA,adjustable thermal setting = 80-100% and magnetic setting 50 Hz , Icu = Ics = 100% - 01 No. ( incomming )\n(b) MCCB 4 pole , 100 Amp rating with breaking capacity 25 KA,adjustable thermal setting = 80-100% and magnetic setting 50 Hz , Icu = Ics = 100% - 02 Nos. (Outgoing) \n (c) MCCB 4 pole 63 Amp rating with breaking capacity 16 KA,adjustable thermal setting = 80-100% and magnetic setting 50 Hz , Icu = Ics = 100% -02 No. (Outgoing) (d) Volt meter Digital type 0-500 volt with in built selector switch - 01 No. (e) Amp meter Digital type 0-200 Amp with inbuilt selector switch & CTs of suitable ratio - 01 No. \n(f) Indicator lamp R,Y,B = 01 Set of three \n Note :- it shall be responsibilty of contractor to obtain the copy of CPRI Test report in Polycarbonate of Degree of ingress Protection IP65 in accordance with IEC 60529 from the manufacturer and submit the same to Engineer-in-charge.If contractor fails submit the report to the department will recover an amount of Rs.10000.00 from the dues of contractor. 2 Each
3 3 Supply, fabricating, installation, testing , commissioning and electrically connecting LT panel Board of size 150cm x 120cm x 80 Cm ,415 volts factory made dust proof vermin for out door type made out of CRCA sheet 3.15 mm thick except inner sheath of 3 mm LT Panel internally and externally shall be painted with expoxy powder coating paint with 7 tank process for treatment of degreasing, pickling & two coats primer, before being given the stove epoxy finish.powder machine pressed both side opening in two halves with rubber beading including aluminium bus bar of 1200 amp capacity 4 strip mounted on porcelain insulator bus bar chamber shall be provided with inspection covers , each MCCB /cubical switch shall have be indipendent opening panel shall be mounted an angle iron frame and legs made from angle of size 40mm x40mm x 5mm frame including lifting arrangement and legs duly spray painted internally and externally with two coats of red oxide primer grouted in PCC (1:3:6) type C2 ( using 40 mm graded crushed stone aggregate ) including all connections / control wiring incoming/outgoing with suitable size of PVC insulated copper conductor cable comprising of following accessories including testing complete all as directed. (a) LT Air circuit breaker microprocessor release 4 pole 415 volts 50 Hz, 36 KA, Manual draw out type 1000 Amp capacity as incoming -01 No.\n(b) MCCB 4 pole 630 Amp rating with breaking capacity 36 KA,adjustable thermal and magnetic setting 50 Hz Ics =100% of Icu Ics =100% of Icu - 01No. (Outgoing) \n (c) MCCB 4 pole 250 Amp rating with breaking capacity 25 KA,adjustable thermal and magnetic setting 50 Hz -04 Nos. (Outgoing) (d) Spare pocket for fixing of 01 No. MCCB with separate compartment - 01 No . (e) Indicator lamp R,Y,B = 01 Set of three \n(f) Digital Amp meter 0-1000 Amp with in built selector switch & CTs of suitable ratio - 01 No. 1 Each
4 4 Supply, fabricating, installation, testing, commissioning and electrically connecting LT panel board of size 120cm x 120cm x 50 cm 415 volts factory made dust proof vermin for out door type made out of CRCA sheet 3.15 mm thick except inner sheath of 2mm LT Panel internally and externally shall be painted with expoxy powder coating paint with 7 tank process for treatment of degreasing, pickling & two coats primer, before being given the stove epoxy finish. machine pressed both side opening in two halves with rubber beading including aluminium bus bar of 400 Amps capacity 4 strip mounted on porcelain insulator bus bar chamber shall be provided with inspection covers, each MCCB/cubmical switch shall have the indipendent opening panel shall be mounted on angle iron frame and legs made from angle of size 40mm x 4mm0 x 5mm frame including lifting arrangement and legs duly spray painted internally and externally with two coats of red oxide primer grouted in PCC (1:3:6) type C-2 (using 40mm graded stone aggregate) including all connections/control wiring incoming/outgoing with suitable size of PVC insulated copper conductor cable comprising of following accessories including testing complete all as directed.\n(i) MCCB 4 pole 415 volts 250 Amp rating with breaking capacity 25 KA, adjustable thermal and magnetic setting 80-100%- lcs = 100% lcu. 01 No. (incoming) \n(ii) MCCB 100 Amp 4 pole 16 KA lcs = 100% lcu = 04 Nos. (outgoing). (iii) Digital volt meter 0-500 volt with in built selector switch - 01 No \n(iv) Indicator lamp R, Y, B = 01 Set of three\n (v) Digital Amp meter 0-500 Amp with in built selector switch & CTs of suitable ratio - 01 No. 1 Each
5 5 Supply, fabricating, installation, testing , commissioning and electrically connecting LT panel Board of size 120cm x120cm x 50 Cm 415 volts factory made dust proof vermin for out door type made out of CRCA sheet 3.15 mm thick except inner sheath of 2mm LT Panel internally and externally shall be painted with expoxy powder coating paint with 7 tank process for treatment of degreasing, pickling & two coats primer, before being given the stove epoxy finish. machine pressed both side opening in two halves with rubber beading including aluminium bus bar of 800 amp capacity 4 strip mounted on porcelain insulator bus bar chamber shall be provided with inspection covers , each MCCB /cubical switch shall have be indipendent opening panel shall be mounted on angle iron frame and legs made from angle of size 40mm x40 mm x 5mm frame including lifting arrangement and legs duly spray painted internally and externally with two coats of red oxide primer grouted in PCC (1:3:6) type C2 (using 40 mm graded crushed stone aggregate ) including all connections /control wiring incoming/outgoing with suitable size of PVC insulated copper conductor cable comprising of following accessories including testing complete all as directed. \n(i) MCCB 4 pole 415 volts 400 Amp rating with breaking capacity 36 KA,adjustable thermal and magnetic setting 80-100% - Ics =100%Icu 01 No. (incoming) . \n(ii) MCCB 250 Amp 4 Pole 25 KA Ics = 100% Icu = 02 Nos. (outgoing) \n(iii) MCCB 100Amp 4 Pole 16 KA Ics = 100% Icu = 02 Nos. (outgoing) \n(iv) Digital volt meter 0-500 volt with in built selector switch = 01 No. \n(v) Indicator lamp R,Y,B = 01 Set of three \n(vi)Digital Amp meter 0-500 Amp with in built selector switch & CTs of suitable ratio - 01 No 1 Each
6 6 Supply, fabricating, installation, testing , commissioning and electrically connecting LT panel Board of size 100cm x 80cm x 50 cm , 415 volts ,factory made , machine pressed , dust and vermin proof , out door type made with CRCA sheet 3.15 mm thick , LT Panel internally and externally shall be painted with expoxy powder coating paint with 7 tank process for treatment of degreasing, pickling & two coats primer, before being given the stove epoxy finish. , both side opening in two halves with rubber beading , including aluminium bus bar of 300 Amp capacity, 4 strip mounted on porcelain insulator , bus bar chamber and shall be provided with inspection covers , Each MCCB / Cubical switch shall have the indipendent opening panel and shall be mounted on angle iron frame and legs made from angle iron of size 40mm x 40mm x 5mm frame including lifting arrangement and legs duly spray painted with two coats of synthetic enamel paint over a coat of red oxide primer , embeding and grouting in PCC (1:2:4) type B1 using 20 mm graded crushed stone aggregate in foundation including necessay earth work , all connections / control wiring incoming / outgoing with suitable size of PVC insulated copper conductor cable of 1100 / 650 vot grade comprising of following accessories and testing complete all as directed. \n(a) MCCB 200 Amps , 4 Pole 36 KA with adjustable thermal setting = 80-100% and magnetic setting 50 Hz , Icu = Ics = 100% - 01 No. ( incomming ) \n(b) MCCB 63 Amps , 4 Pole 25 KA with adjustable thermal setting = 80-100% and magnetic setting 50 Hz , Icu = Ics = 100% - 02 Nos. (Outgoing) (c) Indicator lamp R,Y,B = 01 Set of three \n(f) DIgital electronic Ammeter 0 to 800 Amp with CTs/selector switch - 01 No \n(g) Digital electronic volt meter 3 phase 0 to 500 volts with selector switch -01 No. \n(h) Complete panel wiring with tagging and double layer of rubber bidding. 1 Each
7 7 Supply, fabricating, installation, testing , commissioning and electrically connecting LT panel Board of size 120cm x 120cm x 50 cm , 415 volts ,factory made , machine pressed , dust and vermin proof , out door type made with CRCA sheet 3.15 mm thick , LT Panel internally and externally shall be painted with expoxy powder coating paint with 7 tank process for treatment of degreasing, pickling & two coats primer, before being given the stove epoxy finish. , both side opening in two halves with rubber beading , including aluminium bus bar of 630 Amp capacity , 4 strip mounted on porcelain insulator , bus bar chamber and shall be provided with inspection covers , Each MCCB / Cubical switch shall have the indipendent opening panel and shall be mounted on angle iron frame and legs made from angle iron of size 40mm x 40mm x 5mm frame including lifting arrangement and legs duly spray painted with two coats of synthetic enamel paint over a coat of red oxide primer , embeding and grouting in PCC (1:2:4) type B:1 using 20 mm graded crushed stone aggregate in foundation including necessay earth work complete , including all connections / control wiring incoming / outgoing with suitable size of PVC insulated copper conductor cable of 1100 / 650 vot grade comprising of following accessories including testing complete all as directed. \n(a) MCCB 400 Amp , 4 pole , 415 volts rating with breaking capacity 50 KA, adjustable setting = 80-100% and magnetic setting 50 Hz , Icu = Ics = 100% .- 01No. (incoming) \n(b) MCCB 250 Amp , 4 pole , 36 KA adjustable setting = 80-100% and magnetic setting 50 Hz , Icu = Ics = 100% = 02 Nos. (outgoing).\n(c) MCCB 100 Amp , 4 pole , 25 KA adjustable setting = 80-100% and magnetic setting 50 Hz , Icu = Ics = 100% = 02 Nos (outgoing). \n (d) Spare pocket for fixing of 01 No. MCCB with separate compartment - 01 No. (e) Volt meter Digital type 0-500 volt with in built selector switch - 01 No.\n (f) Amp meter Digital type 0-200 Amp with inbuilt selector switch & CTs of suitable ratio - 01 No. \n(g) Indicator lamp R,Y,B = 01 Set of three.\n 1 Each
8 8 Supply, fabricating, installation, testing , commissioning and electrically connecting LT panel Board of size 120cm x 120cm x 50 cm , 415 volts ,factory made , machine pressed , dust and vermin proof , out door type made with CRCA sheet 3.15 mm thick , LT Panel internally and externally shall be painted with expoxy powder coating paint with 7 tank process for treatment of degreasing, pickling & two coats primer, before being given the stove epoxy finish. , both side opening in two halves with rubber beading , including aluminium bus bar of 630 Amp capacity , 4 strip mounted on porcelain insulator , bus bar chamber and shall be provided with inspection covers , Each MCCB / Cubical switch shall have the independent opening panel and shall be mounted on angle iron frame and legs made from angle iron of size 40mm x 40mm x 5mm frame including lifting arrangement and legs duly spray painted with two coats of synthetic enamel paint over a coat of red oxide primer , embeding and grouting in PCC (1:2:4) type B1 using 20 mm graded crushed stone aggregate in foundation including necessay earth work , including all connections / control wiring incoming / outgoing with suitable size of PVC insulated copper conductor cable of 1100 / 650 vot grade comprising of following accessories including testing complete all as directed. \n(i) MCCB 400 Amp , 4 pole , 415 volts rating with breaking capacity 50 KA, adjustable setting = 80-100% and magnetic setting 50 Hz , Icu = Ics = 100% .- 01 (incoming) \n(ii) MCCB 100A , 4 pole , 25 KA adjustable setting = 80-100% and magnetic setting 50 Hz , Icu = Ics = 100% = 04 Nos (outgoing).\n(iii) Spare pocket for fixing of 01 No. MCCB with separate compartment - 01 No. (iv) Volt meter Digital type 0-500 volt with in built selector switch - 01 No.\n(v) Amp meter Digital type 0-200 Amp with inbuilt selector switch & CTs of suitable ratio - 01 No. \n(vi) Indicator lamp R,Y,B = 01 Set of three\n 1 Each
9 9 Supply , Fixing , commissioning and testing Polycarbonate Floor Mounting Panel CPRI approved OEM made LT Panel shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES which should be UV resistance, Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262. The manufacturer of panel shall submit a copy of CPRI TEST REPORT IN POLYCARBONATE OF DEGREE OF INGRESS PROTECTION IP65 IN ACCORDANCE WITH IEC 60529. The gasket should be internally embedded made of polyurethane. Copper Busbar of size 40mm x10mm x 2mm (800A) for Main and riser as per MCCB Capacity 1 A=1Sqmm with phase & Neutral color code sleeves. The panel should pass glow wire test 960ºC in accordance with 60695-2-11 flame retardant and self-extinguishing complete all as directed.\nMake- Hensel / Rittal / L&T / Schneider / ABB or equivalent in CPRI & CMD approved.\n\n(i) MCCB 4 pole 415 volts 400 Amp rating with breaking capacity 36 KA,adjustable thermal and magnetic setting 80-100% Ics =100%Icu . -01No. incoming\n(ii) MCCB 4 pole 415 volts 100 Amp rating with breaking capacity 16 KA,adjustable thermal and magnetic setting 80-100% Ics =100%Icu . -04 Nos. (outgoing)\n(iii) MCCB 4 pole 415 volts 63 Amp rating with breaking capacity 16 KA,adjustable thermal and magnetic setting 80-100% Ics =100%Ic -02 Nos. (outgoing) \n(iv) Indicator lamp R,Y,B = 01 Set of three\n(vi) Digital Amp meter 0-400 Amp with in built selector switch & CTs of suitable ratio - 01 No. \n\nNote :- it shall be responsibilty of contractor to obtain the copy of CPRI Test report in Polycarbonate of Degree of ingress Protection IP65 in accordance with IEC 60529 from the manufacturer and submit the same to Engineer-in-charge.If contractor fails to submit the report to the department recovery of Rs.10000.00 shall be effected from contractor from his dues and nothing shall be claimed on this account.\n\n\n 2 Each
10 10 Supply , Fixing , commissioning and testing Polycarbonate Floor Mounting Panel CPRI approved OEM made LT Panel shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES which should be UV resistance, Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262. The manufacturer of panel shall submit a copy of CPRI TEST REPORT IN POLYCARBONATE OF DEGREE OF INGRESS PROTECTION IP65 IN ACCORDANCE WITH IEC 60529. The gasket should be internally embedded made of polyurethane. Copper Busbar of size 30x2x10 (600A) for Main and riser as per MCCB Capacity 1 A=1Sqmm with phase & Neutral color code sleeves. The panel should pass glow wire test 960 degree centigrade in accordance with 60695-2-11 [flame retardant and self-extinguishing complete all as directed.\n Make- Hensel/Rittal/L&T/Schneider/ABB or equivalent in CPRI & CMD Make approved\n(i) MCCB 4 pole 415 volts 320 Amp rating with breaking capacity 36 KA,adjustable thermal and magnetic setting 80-100% Ics =100%Icu -01 No. (incoming) \n(ii) MCCB 4 pole 415 volts 100 Amp rating with breaking capacity 16 KA,adjustable thermal and magnetic setting 80-100% Ics =100%Icu . -04 Nos. (outgoing) \n(iii) MCCB 4 pole 415 volts 63 Amp rating with breaking capacity 16 KA,adjustable thermal and magnetic setting 80-100% Ics =100%Icu-02 Nos. (outgoing). \n(iv) Digital volt meter 0-500 volt with in built selector switch = 01 No\n(v) Digital Amp meter 0-400 Amp with in built selector switch & CTs of suitable ratio - 01 No \n(vi) Indicator lamp R,Y,B = 01 Set\n\nNote :- it shall be responsibilty of contractor to obtain the copy of CPRI Test report in Polycarbonate of Degree of ingress Protection IP65 in accordance with IEC 60529 from the manufacturer and submit the same to Engineer-in-charge.If contractor fails to submit the report to the department recovery of Rs.10000.00 shall be effected from contractor from his dues and nothing shall be claimed on this account.\n\n\n\n 2 Each
11 11 Supply and fixing, commissioning and testing LT panel cubical type of size 180cm x 140cm x 80 cm (Panel box size only), 415 Volts, factory made dust proof vermin proof for out door using made out of CRCA sheet 3.15 mm thick except inner sheath of 2mm LT Panel internally and externally shall be painted with expoxy powder coating paint with 7 tank process for treatment of degreasing, pickling & two coats primer, before being given the stove epoxy finish, machine pressed, both side opening in two halves with provision of rubber beadings and locking system, including aluminium bus bar of 1200 Amp capacity, 4 strip mounted on porcelain insulator, bus bar chamber shall be provided with inspection covers, each MCCB/ cubical switch shall have independent opening , panel shall be mounted on angle iron frame and legs (vertical height of legs not less than 30cm except in PCC ) made from angle of size 40x40x5mm , frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, legs grouted in PCC (1:3:6) type B-2 (using 40 mm graded stone aggregate) complete including all connections/control wiring incoming/out going with suitable size of copper conductor cable, including danger notice sticker, comprising of following accessory including testing complete all as specified and directed by Engineer-in-charge:- \n(a) LT ACB 800 Amps 4 Pole fixed manual type with microprocessor based released (O/L and E/F protection and metering display) 36 KA Ics=Icu =Icw (1Sec) as incomming - 01 No. \n(b) MCCB 400 Amps 4 Pole 36 KA Ics =100% Icu with adjustable thermal and magnatic setting as outgoing - 01 No. (c) MCCB 250 Amps 4 Pole 25 KA Ics =100% Icu with adjustable thermal and magnatic setting as outgoing - 04 No. (d) Indicator lamp R, Y, B - 01 Set of three \n(e) DIgital electronic Ammeter 0 to 800 Amp with CTs/selector switch - 01 No . \n(f) Digital electronic volt meter 3 phase 0 to 500 volts with selector switch -01 No. 1 Each
12 12 Supply and fixing, commissioning and testing LT panel cubical type of suitable size to accomodate following switchgear with all accessories and seperate cable run chember as per standard, 415 Volts, factory made dust proof vermin proof for out door using made of SS304 sheet 3.0 mm thick except inner sheath of 2mm with out powder coated, machine pressed, both side opening in two halves with provision of rubber beadings and locking system, including Main aluminium bus bar of 40mm X 2mm X 10mm (800 Amp) capacity and sub riser to MCCB according to MCCB capacity 1Sqmm=1Amp , 4 strip mounted on porcelain insulator, bus bar chamber shall be provided with inspection covers, each MCCB/ cubical switch shall have independent opening , panel shall be mounted on angle iron frame and legs (vertical height of legs not less than 30cm except in PCC ) made from angle of size 40x40x5mm , frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, legs grouted in PCC (1:3:6) type B-2 (using 40 mm graded crushed stone aggregate) including all connections/control wiring incoming/out going with suitable size of copper conductor cable, including danger notice sticker, comprising of following accessory including testing complete all as directed.\n(a) MCCB 400 Amps 4 Pole fixed manual type with microprocessor based released (O/L and E/F protection and metering display) 36 KA Ics=Icu =Icw (1Sec) as incomming - 01 No \n(b) MCCB 250 Amps 4 Pole 26 KA Ics =100% Icu with adjustable thermal and magnatic setting as outgoing - 02 Nos. (c) MCCB 160 Amps 4 Pole 16 KA Ics =100% Icu with adjustable thermal and magnatic setting as outgoing - 03 Nos. \n (d) MCCB 100 Amps 4 Pole 16 KA Ics =100% Icu with adjustable thermal and magnatic setting as outgoing - 03 Nos. \n(e) Indicator lamp R, Y, B - 01 Set of three. \n(f) DIgital electronic Ammeter 0 to 800 Amp with CTs/selector switch - 01 No \n(g) Digital electronic volt meter 3 phase 0 to 500 volts with selector switch -01 No. \n(h) Complete panel wiring with tagging and double layer of rubber besding. 1 Each
13 13 Supply and fixing, commissioning and testing LT panel cubical type of suitable size to accomodate following switchgear with all accessories and seperate cable run chember as per standard, 415 Volts, factory made dust proof vermin proof for out door using made of SS304 sheet 3.0 mm thick except inner sheath of 2mm with out powder coated, machine pressed, both side opening in two halves with provision of rubber beadings and locking system, including Main aluminium bus bar of 40mm X 2mm X 10mm (800 Amp) capacity and sub riser to MCCB according to MCCB capacity 1Sqmm=1Amp , 4 strip mounted on porcelain insulator, bus bar chamber shall be provided with inspection covers, each MCCB/ cubical switch shall have independent opening , panel shall be mounted on angle iron frame and legs (vertical height of legs not less than 30cm except in PCC ) made from angle of size 40x40x5mm , frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, legs grouted in PCC (1:3:6) type B-2 (using 40 mm graded crushed stone aggregate) including all connections/control wiring incoming/out going with suitable size of copper conductor cable, including danger notice sticker, comprising of following accessory including testing complete all as directed.\n(a) MCCB 320 Amps 4 Pole fixed manual type with microprocessor based released (O/L and E/F protection and metering display) 36 KA Ics=Icu =Icw (1Sec) as incomming - 01 No \n(b) MCCB 160 Amps 4 Pole 26 KA Ics =100% Icu with adjustable thermal and magnatic setting as outgoing - 02 Nos. (c) MCCB 100 Amps 4 Pole 16 KA Ics =100% Icu with adjustable thermal and magnatic setting as outgoing - 02 Nos. \n(d) Indicator lamp R, Y, B - 01 Set of three. \n(e) DIgital electronic Ammeter 0 to 800 Amp with CTs/selector switch - 01 No \n(f) Digital electronic volt meter 3 phase 0 to 500 volts with selector switch -01 No. \n(g) Complete panel wiring with tagging and double layer of rubber besding. 2 Each
14 14 Supply and fixing in repair LT junction box cubical type of size 60cm x 40cm x 30 cm, 415 volts for outdoor use made of CRCA sheet 3.15 mm thick powder coated ,machine pressed front opening with single door with provision of rubber beading and locking system including aluminium bus bar 4 strip of size 30 mm wide and 6 mm thick with provision of hole on bus bar for fixing of cable mounted on PVC / epoxy insulators, mounted on angle legs of size 25mm x 25mm x 5mm frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer ,legs grouted in PCC(1:2:4) Type B-1 (using 20 mm graded crushed stone aggregate) including all provision of opening for incomming/outgoing cables and testing complete all as directed. 8 Each
15 15 S&F in repair of indicator lamp in differenet colour code LED / Neon type (as per sample) complete (RYB) including wiring with copper conductor cable of suitable size complete all as directed. 20 Each
16 16 Material and Labour for Preparation of old painted surfaces of feeder piller box / panel of any size any description and in any position including removel of faded & deteriorated paint either by hand scrubbing or by blow lamps , applying necessary filler coat and scrapping as required and applying two coats of synthetic enamelled paint (grey in colour) with using spray machine over a coat of primer complete all as specified and as directed. 140 Sqm
17 17 Material and Labour for repairing the LT panel board body by replacing with new MS sheet of existing gauge size and shape including applying two coats of synthetic enamelled paint (Existing shade colour ) with using spray machine over a coat of primer for door shutter / body of feeder pillar box, including replacement of broken hinges with new hinges complete all as specified and as directed.\n 1 Qtl
18 18 Supply,Fixing in repair and testing LT Air circuit breaker 1000 Amp . 4 pole , 415 volts , 50 Hz, 65 KA, microprocessor release Manual draw out type complete all as per manufacturers instructions and as directed. 2 Each
19 19 Supply,Fixing in repair and testing LT Air circuit breaker 800 Amp . 4 pole , 415 volts , 50 Hz, 65 KA, microprocessor release Manual draw out type complete all as per manufacturers instructions and as directed. 2 Each
20 20 Cutting / trimming of tree branches upto 1.50 metre distance on each side and 3.00 mtr distance on both sides of LT over head lines including collection and removal from road complete all as directed.\nNote :-For measurement and payment purpose each span shall be considered as 40.00 mtr. Span.If the length of span is less than 40.00mtr measurment and payment shall be considered proportionally. 500 Each Span
21 21 Opening /disconnecting the electrical connection of defective/burnt out underground LT cable of any size 2 to 4 core from main switch/DB/junction box / LT panel/ L T O/H line etc. Taking out the required length of cable from existing loop, cutting the defective portion of cable ,providing required thimbles/connectors at cable end and reconnecting the cable in previous location with existing main switch/DB/Junctionbox/LT panel/O/H line etc complete all as directed. \nNote:- (I) the cost of required earth work ie excavation,returning filling,relaying of sand/bricks and cost of drawing the required length from protection pipe ,breaking of required brick work/plaster/concrete and redoing the required cement work to match the existing surface is deemed to be included in quoted rates and nothing extra shall be paid on this account.\n(ii)Additional cable/ protection pipe required at site shall be measured and paid seperatly as supply and fix under respective item here in after. 310 Each Job
22 22 Supply and fixing in repair Polycarbonate CPRI approved OEM made LT FEEDER PILLAR shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES which should be UV resistance, Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262. The manufacturer of panel shall submit a copy of CPRI TEST REPORT IN POLYCARBONATE OF DEGREE OF INGRESS PROTECTION IP65 IN ACCORDANCE WITH IEC 60529. The gasket should be internally embedded made of polyurethane. The panel should pass glow wire test 960ºC in accordance with 60695-2-11 (flame retardant and self-extinguishing). LT junction box cubical type of size 60x40x30 cm,415 volts for outdoor use ,machine pressed front opening with single door with provision of rubber beading and locking system including aluminium bus bar 4 strip of size 30 mm wide and 6 mm thick with provision of hole on bus bar fixing of cable mounted on PVC / epoxy insulators, mounted on angle legs of size 25x25x5mm frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer ,legs grouted in PCC(1:2:4) Type B-1 (using 20 mm graded stone aggregate) including provision of opening for incomming/outgoing cables and testing complete all as directed. \nMake- Hensel/Rittal/L&T/Schneider/ABB.\nNote :- it shall be responsibilty of contractor to obtain the copy of CPRI Test report in Polycarbonate of Degree of ingress Protection IP65 in accordance with IEC 60529 from the manufacturer and submit the same to Engineer-in-charge.If contractor fails submit the report to the department will recover an amount of Rs.10000.00 from the dues of contractor. 5 Each
23 23 Supply and fix in repair LT feeder pillar box factory made cubical type dust proof, out door type both side opening of size 110cm x 100cm x 60cm of SS304 sheet 3 mm thick WITH OUT powder coated machine pressed front opening in two halves with rubber gasket / bedding , locking arrangement with sliding bolt including aluminium bus bar of size 50 x 10 mm and 80 cm long 3 strips mounted on HT insulators each strip should be munted on minimum two insulators and nut bolt panel shall be mounted on angle iron frame and legs made from angle iron of size 50x 50 x 6 mm and legs 40 cm long duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer grouted in PCC (1:2:4) type ‘B’1 ( using 20 mm graded crushed stone aggregate) including incoming / outgoing cable provision complete all as directed. 2 Each