Routine maintenance of 10 Nos. 132 KV Lines, Under ETD Shamli against E-tender No. ETC/MU/T-130/2020-21 of Electricity Transmission Circle Muzaffarnagar

Key Value

Document Fees
INR 1770 /-
EMD
INR 17800.0 /-
Tender Value
INR 17.74 Lakhs /-

BOQ Items

Name of Work: Routine maintenance of 10 Nos. 132 KV Lines, Under ETD Shamli against E-tender No. ETC/MU/T-130/2020-21 of Electricity Transmission Circle Muzaffarnagar
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Regular tower to tower ground patrolling and tower top patrolling wherever required of approximate 131.899 Km. long various 132 KV lines Under ETD Shamli, detection of defects like missing/theft tower members, hot point, puncture/flashover of disc insulator and vibration dampers, damaged conductor/earthwire, checking of foundation and tower legs, earthing & position of tree in 27 Meter wide line corridor. Patrolling shall be done on bimonthly basis i.e. 4 times in a year and preparation of patrolling report on UPPTCL Performa. \n(i)132 KV Shamli-Jhinjhana 15.370\n(ii)132 KV Shamli-Jasala 13.400\n(iii)132 KV Shamli-Jalalpur 13.510\n(iv)132 KV Thanabhawan-Jalalpur 20.700\n(v)132 KV Jasala-Kaniyan 12.400\n(vi)132 KV Thanabhawan-Bajaj Sugar Mill 10.915\n(vii)132 KV Shamli Shyamla-Superior Food \n Grain Ltd 0.600\n(viii)132 KV Jhinjhana-Shamli Shyamla 10.045\n(ix)132 KV Nanauta-Thanabhawan 09.005\n(X) 132 KV Shamli-Shyamla – Nanauta 25.944\n 131.889 Km.\n BI01010001010000000000000515BI0100001113 527.556 Km.
2 2 Opening/Cutting of nut &bolts of remaining cut pieces of tower members stolen by miscreants to be opened safely/cut safely with the help of gas cutter/hacksaw blade. Fabrication & fixing of tower members including carriage of steel angles from Sub-station store, punching holes for proper placement, tightening of nuts &bolts, punching & chamfering at different tower location of above Transmission line and all other associated work to complete the job satisfactorily as per technical specification. BI01010001010000000000000515BI0100001114 50 No.
3 3 Repairing of damaged jumpers with the help of PG clamp at tension towers. BI01010001010000000000000515BI0100001115 10 Nos
4 4 Replacement of damaged/punctured polymer/disc Insulator string at different tower location including carriage of material from store to work site of the above line and all other associated work to complete the job satisfactorily as per technical specification. BI01010001010000000000000515BI0100001124
5 4.1 For Suspension String. BI01010001010000000000000515BI0100001125 85 Nos
6 4.2 For Tension String BI01010001010000000000000515BI0100001128 5 Nos
7 5 Looping Chopping and cutting of trees branches in the 27 Meter corridor of above lines and stacking of above cuttings at proper place far from the line. BI01010001010000000000000515BI0100001128 1500 Nos
8 6 Removing of bird’s nest from different towers in respect of above lines BI01010001010000000000000515BI0100001128 30 Nos
9 7 Tightening/fixing of missing/displaced vibration dampers/arcing horn. BI01010001010000000000000515BI0100001128 5 Nos
10 8 Tightening of jumpers at tension towers on per end and replacing nut, bolt & washer if required. BI01010001010000000000000515BI0100001128 370 Nos
11 9 Attending conductor break down fault by providing Mid span compression joints including lowering down of conductor and re-hoisting, restringing tensioning etc. of the same up to 1 Km. along with associated works to complete the job as per technical specification. BI01010001010000000000000515BI0100001128 2 Job
12 10 Repairing of damaged & bypass ACSR Panther Conductor by intacting of Mid span compression joints including lowering down of conductor and re-hoisting, restringing tensioning etc. of the same up to 1 Km. along with associated works to complete the job as per technical specification. BI01010001010000000000000515BI0100001128 5 Job
13 11 Repairing of conductor by providing repairing sleeve when conductor down to earth during attending Breakdown of conductor as mentioned in item No. 9 &10 BI01010001010000000000000515BI0100001128 10 Nos
14 12 Attending breakdown conductor as mentioned in item No. 9 & 10 in additional phase of same section. BI01010001010000000000000515BI0100001128 2 Job
15 13 Attending Breakdown of broken/ failed disc insulator string (Disc insulator string must be dislocated either from hook or from suspension fitting) by replacement of broken disc insulator string with fresh disc insulator string and rehoisting of conductor up to cross arm and fixing it with suspension clamp and all other associated work to complete the job satisfactorily as per technical specification. BI01010001010000000000000515BI0100001128 10 Job
16 14 Repairing of damaged ACSR Panther conductor by using repair sleeves. BI01010001010000000000000515BI0100001128 10 Job
17 15 Attending breakdown of earthwire/tightening of loose earthwire per span along with associated works to complete the job satisfactorily as per technical specification. BI01010001010000000000000515BI0100001128 5 Job
18 16 Attending breakdown of earthwire/tightening of loose earthwire more than 01 span and up to 01 Km. along with associated works to complete the job satisfactorily as per technical specification. BI01010001010000000000000515BI0100001128 3 Nos
19 17 Attending breakdown of earthwire/tightening of loose earthwire more than 01 Km. along with associated works to complete the job satisfactorily as per technical specification. BI01010001010000000000000515BI0100001128 2 Nos
20 18 Emergency patrolling of above lines during tripping to detect the exact fault location & type of fault. BI01010001010000000000000515BI0100001128 600 Km.
21 19 Manually checking of tower to detect defective/flashed polymer/disc Insulator strings. BI01010001010000000000000515BI0100001128 600 Nos