Uttar Pradesh Power Transmission Corporation Limited-UPPTCL has published Etc Mu T 131 2020 21 Work Tender. Submission Date for this Tender is 02-02-2021. Transmission Line Tenders in SHAMLI Uttar Pradesh. Bidders can get complete Tender details and download the document.
Name of Work: Routine maintenance of 06 Nos. 132 KV Lines, Under ETD Shamli against E-tender No. ETC/MU/T-131/2020-21 of Electricity Transmission Circle Muzaffarnagar | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Regular tower to tower ground patrolling and tower top patrolling wherever required of approximate 117.065 Km. long various 132 KV lines Under ETD Shamli, detection of defects like missing/theft tower members, hot point, puncture/flash over of disc insulator and vibration dampers, damaged conductor/earthwire, checking of foundation and tower legs, earthing & position of tree in 27 Meter wide line corridor. Patrolling shall be done on bimonthly basis i.e. 4 times in a year and preparation of patrolling report on UPPTCL Performa. \n(i)132 KV Shamli-Budhana 22.800 \n(ii)132 KV Shamli-Kharad 19.300\n(iii)132 KV Shamli-Lalukheri 22.000\n(iv)132 KV Nara-Lalukheri 32.000\n(v) 132 KV Lalukheri-Titavi Sugar Mill 12.400 \n(vi)132 KV Budhana-Bajaj Sugar Mill 8.565 \n 117.065 Km.\n468.26 Km.\n\n | BI01010001010000000000000515BI0100001113 | 468.26 | Km. |
2 | 2 | Opening/Cutting of nut &bolts of remaining cut pieces of tower members stolen by miscreants to be opened safely/cut safely with the help of gas cutter/hacksaw blade. Fabrication & fixing of tower members including carriage of steel angles from Sub-station store, punching holes for proper placement, tightening of nuts &bolts, punching & chamfering at different tower location of above Transmission line and all other associated work to complete the job satisfactorily as per technical specification. | BI01010001010000000000000515BI0100001114 | 50 | No. |
3 | 3 | Repairing of damaged jumpers with the help of PG clamp at tension towers. | BI01010001010000000000000515BI0100001115 | 10 | Nos |
4 | 4 | Replacement of damaged/puncture polymer/disc Insulator string at different tower location including carriage of material from store to work site of the above line and all other associated work to complete the job satisfactorily as per technical specification. | BI01010001010000000000000515BI0100001124 | ||
5 | 4.1 | For Suspension String. | BI01010001010000000000000515BI0100001125 | 60 | Nos |
6 | 4.2 | For Tension String | BI01010001010000000000000515BI0100001128 | 3 | Nos |
7 | 5 | Looping Chopping and cutting of trees branches in the 27 Meter corridor of above lines and stacking of above cuttings at proper place far from the line. | BI01010001010000000000000515BI0100001128 | 1000 | Nos |
8 | 6 | Removing of bird’s nest from different towers in respect of above lines | BI01010001010000000000000515BI0100001128 | 50 | Nos |
9 | 7 | Tightening/fixing of missing/displaced vibration dampers/arcing horn. | BI01010001010000000000000515BI0100001128 | 10 | Nos |
10 | 8 | Tightening of jumpers at tension towers on per end and replacing nut, bolt & washer if required. | BI01010001010000000000000515BI0100001128 | 300 | Nos |
11 | 9 | Attending conductor break down fault by providing Mid span compression joints including lowering down of conductor and re-hoisting, restringing tensioning etc. of the same up to 1 Km. along with associated works to complete the job as per technical specification. | BI01010001010000000000000515BI0100001128 | 2 | Job |
12 | 10 | Repairing of conductor by providing repairing sleeve when conductor down to earth during attending Breakdown of conductor as mentioned in item No. 9 & 10. | BI01010001010000000000000515BI0100001128 | 10 | Job |
13 | 11 | Attending Breakdown of broken/ failed disc insulator string (Disc insulator string must be dislocated either from hook or from suspension fitting) by replacement of broken disc insulator string with fresh disc insulator string and rehoisting of conductor up to cross arm and fixing it with suspension clamp and all other associated work to complete the job satisfactorily as per technical specification. | BI01010001010000000000000515BI0100001128 | 5 | Job |
14 | 12 | Attending breakdown conductor as mentioned in item No. 9 & 10 in additional phase of same section. | BI01010001010000000000000515BI0100001128 | 10 | Nos |
15 | 13 | Attending Breakdown of broken/ failed disc insulator string (Disc insulator string must be dislocated either from hook or from suspension fitting) by replacement of broken disc insulator string with fresh disc insulator string and rehoisting of conductor up to cross arm and fixing it with suspension clamp and all other associated work to complete the job satisfactorily as per technical specification. | BI01010001010000000000000515BI0100001128 | 15 | Job |
16 | 14 | Emergency patrolling of above lines during tripping to detect the exact fault location & type of fault. | BI01010001010000000000000515BI0100001128 | 400 | Km. |
17 | 15 | Manually checking of tower to detect defective/flashed polymer/disc Insulator strings. | BI01010001010000000000000515BI0100001128 | 500 | Nos |
18 | 16 | Repairing and Strengthening of damaged and rusted legs on different towers of 10 Nos. 132 KV Lines involving following work will be done including all labour, T&P, Material (except Gal. Tower parts and nut & bolts) and all other associated work to complete the job satisfactorily as per technical specification | BI01010001010000000000000515BI0100001128 | 10 | Job |
19 | 16.1 | Excavation earth around the chimney 0.8 mtr to 1.20 mtr deep and 1.0 to 1.2 meter dia. Breaking the chimney 0.4 mtr to 0.8 Mtr below the ground level and 0.2 to 0.3 Mtr above the ground level including removing of earth & cleaning rust from the stub and apply zinc rich allu. paint on rusted portion of stub after applying one coat of red oxide for making suitable lap joint to each stub. | BI01010001010000000000000515BI0100001124 | ||
20 | 16.2 | Making of 1 No. cleat of 0.8 to 1.20 Meter for legs suitable for inner and outer surface of stub from galvanized steel angle of suitable size provided by deptt. by cutting and drilling of holes etc. | BI01010001010000000000000515BI0100001124 | ||
21 | 16.3 | Fixing the inner and outer cleats on damaged and rusted stub by making suitable holes on stub and providing 16 to 20 Nos 16 mm. nut, bolt & washer as per site requirement (Nut, Bolt & Washer will be provided by the Deptt.) by making suitable holes corresponding to cleats & proper tightening. | BI01010001010000000000000515BI0100001124 | ||
22 | 16.4 | Applying of two coat anti rust paint on repaired stub (Approx length of each stub 1.00 to 1.20 Metre) | BI01010001010000000000000515BI0100001124 | ||
23 | 17 | Remaking and increasing chimney height of 132 KV S/C A,B,C, type tower up to length of 0.8 to 1.30 Meter in CC ratio 1:2:4 by using coarse sand & 20 mm grit after providing & fixing of 04 No 16 mm 0.8 to 1.20 meter steel bar including binding by 5 to 6 No. 6 mm steel bar ring and after placing proper shuttering. Including back filling of earth and proper curing for 10 days & after removal of all shuttering. | BI01010001010000000000000515BI0100001128 | 15 | Job |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy