Military Engineer Services-MES has published Repair/Maint And Improvement Of Lt/Ht Apfc Panels For The Complete Station In Army Area Jodhpur. Submission Date for this Tender is 16-02-2021. Power Factor Panel Tenders in GE Utility Rajasthan. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 21-Jan-2021 | Corrigendum | BOQ | 09-02-2021 |
2 | 09-Feb-2021 | corrigendum2125 | Other | 09-02-2021 |
3 | 09-Feb-2021 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 16-02-2021 |
Name of Work: REPAIR/MAINT AND IMPROVEMENT OF LT/HT APFC PANELS FOR THE COMPLETE STATION IN ARMY AREA JODHPUR | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Disconnection of LT APFC panel from main distribution panel. Segregation of all serviceable and unserviceable components like capacitors, contactors, auxilary block, CT coil, multifunction meters, relays, indicators, push button etc, carrying out servicing of complete APFC panel, by removing dust and cleaning by CRC solution. carrying out serviceability check of all components and refixing of all servicable components complete including connection with internal wiring. Replacement of all unserviceable components as per existing type/make and rating of equivalent type assembling the APFC panel, including connecting with LT distribution panel board and testing complete to the entire satisfaction of EIC. Note:- (i) All components/spares required to be replaced shall be measured and paid seperately under 'Supply & fixing' of item as detailed hereafter. (ii) The internal wiring of suitable size shall be of copper including terminal, lugs and screw to be replaced as per requirement and cost there of is deemed to be included in item rate. (iii) Inspection note indicating involvement of repair work and replacement of components is to be prepared and submitted by Contractor for each APFC panel. (iv) The servicing/repairing of APFC panel shall be carried out by authorized person of OEM/manufacturer. | 90 | Each Job | |
2 | 2 | Supply and fixing including connection of 3 pole power contactor- Type MO 18, AC 3 and AC 1 rating 18 Amps & 32 Amps respectively. | 40 | Nos | |
3 | 3 | Supply and fixing including connection of 3 pole power contactor- Type MO 20/MO25, AC 3 and AC 1 rating 25 Amps & 45 Amps respectively. | 20 | Nos | |
4 | 4 | Supply and fixing including connection of 3 pole power contactor- Type MO 30/32, AC 3 and AC 1 rating 32 Amps & 50 Amps respectively. | 25 | Nos | |
5 | 5 | Supply and fixing including connection of 3 pole power contactor- Type MO 60, AC 3 and AC 1 rating 60 Amps & 100 Amps respectively. | 12 | Nos | |
6 | 6 | Supply and fixing auxilary contact block front mounting type 4 NO | 22 | Nos | |
7 | 7 | Supply and fixing auxilary contact block front mounting type 2 NO + 2 NC | 25 | Nos | |
8 | 8 | Supply and fixing auxilary contact block front mounting type 1 NO + 1 NC | 18 | Nos | |
9 | 9 | Supply and fixing auxilary contact block front mounting type 4 NC | 22 | Nos | |
10 | 10 | Supply and fixing APFC Controller for contactor switching with CT input, 6 step (5+1) with the combination of 3 step APFC controller + 3 step plug in module, Cat No. combination ETACONM003R + ETACONEXP3R having the feature of capacitor failure indication, suitable for HT & LT side sensing, measurement of individual current and voltage harmonic selectable CT secondary current 1A/5A, modular and expandable steps. | 10 | Nos | |
11 | 11 | Supply and fixing APFC Controller for contactor switching with CT input, 8 step (7+1) with the combination of 5 step APFC controller + 3 step plug in module, Cat No. combination ETACONM005R + ETACONEXP3R having the feature of capacitor failure indication, suitable for HT & LT side sensing, measurement of individual current and voltage harmonic selectable CT secondary current 1A/5A, modular and expandable steps. | 7 | Nos | |
12 | 12 | Supply and fixing APFC Controller for contactor switching with CT input, 10 step (9+1) with the combination of 8 step APFC controller + 2 step plug in module, Cat No. combination ETACONM008R + ETACONEXP2R having the feature of capacitor failure indication, suitable for HT & LT side sensing, measurement of individual current and voltage harmonic selectable CT secondary current 1A/5A, modular and expandable steps. | 5 | Nos | |
13 | 13 | Supply and fixing APFC Controller for contactor switching with CT input, 12 step (11+1) with the combination of 8 step APFC controller + 2 step plug in module + 2 step plug in module, Cat No. combination ETACONM008R + ETACONEXP2R + ETACONEXP2R having the feature of capacitor failure indication, suitable for HT & LT side sensing, measurement of individual current and voltage harmonic selectable CT secondary current 1A/5A, modular and expandable steps. | 4 | Nos | |
14 | 14 | Supply and fixing Current Transformer round type for measuring instrument ratio 800/5 Single phase, | 8 | Nos | |
15 | 15 | Supply and fixing Current Transformer round type for measuring instrument ratio 600/5 Single phase, | 12 | Nos | |
16 | 16 | Supply and fixing Current Transformer round type for measuring instrument ratio 300/5 Single phase, | 8 | Nos | |
17 | 17 | Supply and fixing Current Transformer round type for measuring instrument ratio 200/5 Single phase, | 8 | Nos | |
18 | 18 | Supply and fixing Current Transformer round type for measuring instrument ratio 100/5 Single phase, | 8 | Nos | |
19 | 19 | Supply and fixing Power Factor Correction capacitor heavy duty cylindrical LTCCN type of Rating 1 & 2 KVAR. | 50 | Nos | |
20 | 20 | Supply and fixing Power Factor Correction capacitor heavy duty cylindrical LTCCN type of Rating 3 & 4 KVAR. | 40 | Nos | |
21 | 21 | Supply and fixing Power Factor Correction capacitor heavy duty cylindrical LTCCN type of Rating 5 to 15 KVAR. | 130 | Nos | |
22 | 22 | Supply and fixing Power Factor Correction capacitor heavy duty cylindrical LTCCN type of Rating 20 & 25 KVAR. | 45 | Nos | |
23 | 23 | Supply and fixing Multifunction meter having Accuracy Class 1.0, 0.5, input voltage measurement range 50-520 VAC (P-P), Aux supply 80-300 VAC/DC, CT secondary site selectable 1A/5A, DG sensing input 230 VAC, Flush mounting 96 x 96 mm, CT/PT site programmable, parameters: V, A, F, PF, kW, kVA, Run hours, kWh (EB and DG), old energy, Site selectable kWh/kVAh, Cat no. WL404021OOOO. | 23 | Nos | |
24 | 24 | Supply and fixing Bolted fuse link , type HG, HRC fuse of rating 2A. | 20 | Nos | |
25 | 25 | Supply and fixing Bolted fuse link , type HQ, HRC fuse of rating 32A. | 25 | Nos | |
26 | 26 | Supply and fixing indicator lamp LED type (RYBG) | 140 | Nos | |
27 | 27 | Supply and fixing Push button (Red & Blue), | 75 | Nos | |
28 | 28 | Supply and fixing MCB SP (B) Curve Rtaing 10 Amps cat no. BB10100B, | 20 | Nos | |
29 | 29 | Supply and fixing MCB SP (B) Curve Rtaing 20 Amps cat no. BB10200B | 25 | Nos | |
30 | 30 | Supply and fixing MCB SP (B) Curve Rtaing 32 Amps cat no. BB10320B | 15 | Nos | |
31 | 31 | Supply and fixing MCB SP (B) Curve Rtaing 40 Amps cat no. BB10400B, | 35 | Nos | |
32 | 32 | Supply and fixing Fan and thermostat assembly having range of temparature 30-110°C | 20 | Nos | |
33 | 33 | M & L for repainting of APFC panel of different size using two coat of synthetic enamel spray painting after preparation of surface and carrying out minor repair to APFC panel enclosure by welding of hinges and replacement of locking arrangement and complet all as directed by Engineer-in-charge. | 90 | Each Job | |
34 | 34 | Dismantling of broken U/S existing earthing with galvanised steel strip 32x6mm and 10/8 SWG wire complete including removing of PCC from site. | 10 | Each | |
35 | 35 | Earthing complete with galvanised steel earth plate electrodes 600mmx600mmx6mm thick buried directly in ground earth (earth pit not less 2.25 m deep below ground level) with top edge of the plate not less then 1.5 mtr below normal ground level connected to galvanised iron earthing strip 32mmx6mm thick by means of bolt nuts check nuts and washers of galvanised iron or steel all as specified and shown in electrical plate No. 3 of MES SSR part-I 2009 connected to earth test point as specified and testing on completion including provision of 40 mm dia light grade pipe upto 7.5 mtr length as protection and watering pipe shall be 20 mm bore medium grade including all excavation & earth work in any type of strata incl PCC pit (1:3:6) type C-1 with RCC cover including charcoal, salt, funnel all as directed at site. Note:- Rate included for excavation & earth work in any type of strata as shown in electric plate no-3 in SSR Part-I. | 10 | Each | |
36 | 36 | Carrying out servicing of HT 11 KV capacitor bank of different rating at Main Receiving Station including cleaning and tightning of all terminals and complete all as directed by Engineer-in-charge. | 3000 | Per KVAR | |
37 | 37 | Carrying out servicing/overhauling of HT 11 KV capacitor bank outdoor VCB panel including cleaning and tightning of all terminals and machanical components, replacement of spring charger motor, tripping relay coils, and replacement of internal wiring, calibaration of existing relay complete all as directed by Engineer-in-charge. | 6 | Each Job | |
38 | 38 | Supply and fix switch air break gang operated triple pole mechanically operated mounted on insulator (09 insulators) and steel frame with operating mechanism including spring loaded mechanism set of three working from ground level, including locking arrangement of current rating up to 200 Amps (Vertical type), 11000 Volt, including dismantling of unserviceable GOD. | 3 | Each Set | |
39 | 39 | All as per item no. 38 but (Horizontal type) 11000 Volt, including dismantling of unserviceable GOD. | 3 | Each Set |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy