Military Engineer Services-MES has published Provision Of Certain Repair To Lt Distribution Network Including Lt Panels , Underground Cables And Other Connected Items At 8 Fbsu Af Station Awantipur. Submission Date for this Tender is 04-02-2021. LT Cable Tenders in GE (AF) AWANTIPUR Jammu And Kashmir. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 08-Jan-2021 | amendment1 | Terms and Conditions | 28-01-2021 |
2 | 28-Jan-2021 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 04-02-2021 |
Name of Work: PROVISION OF CERTAIN REPAIR TO LT DISTRIBUTION NETWORK INCLUDING LT PANELS, UNDERGROUND CABLES AND OTHER CONNECTED ITEMS AT 8 FBSU AF STATION AWANTIPUR | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Supply, installation, testing & commisioning in replacement of factory made (CPRI test certified manufacturer) LT feeder pillar box of minimum size 80 cm (Height) x 60 cm (Width) x 30 cm (Depth), outdoor type, double door, cubical compartmentalized type suitable for 415 volts, 3 phase, 4 wire, 50 Hz supply system all as specified and directed having busbar chamber with insulated aluminium busbar 200 Amps rating (100% neutral) installed on porcelain insulators. The panel shall be dust and vermin proof made of 3 mm thick (outer) & 2 mm thick (inner compartment door) CRCA sheet duly power coated finished and 40x40x6 mm angle iron frame work duly powder coated, panel mounted on angle iron 40x40x6 mm frame having 4 Nos legs 45 cm long of 40x40x6 mm angle iron, 15 mm grouted in PCC (1:2:4) type B1 using 20mm graded stone aggregate and 30 cm clear space for ground level. Front & back opening type with aprons for cable entry with locking arrangement including internal wiring with PVC insulated multistranded copper conductor cables of suitable size, thimbling and cable entry boxes with cable glands. The scope of the work also includes supply and fixing the following:-\n | 1 | Each job | |
2 | 1.01 | INCOMING:-\n(a) MCCB 160 Amps, 25 kA rupturing capacity, 4 pole, 415 Volts, 50 Hz, thermal magnetic release type - 01 No. \n(b) Voltmeter digital type 0-500 Volts, flush type with 3 way rotary selector switch -01 No\n(d) Ammeter digital type 0-100 Amps, flush type with 3 way rotary selector switch and 3 Nos CTs of ratio 160/5 Amps - 01 No\n(e) Indicating lamp (LED type) RYB - 01 Set of three.\nOUTGOING:-\n(a) MCCB 100 Amps, 25 kA rupturing capacity, 3 pole, 415 Volts, 50 Hz AC, thermal magnetic release type connected through solid busbar of suitable size in both incoming & outgoing side - 03 Nos. | |||
3 | 2 | S&F in replacement of MCCB 3 Pole, 415 vots AC, 50 Hz with adjustable thermal fixed magnetic setting complete including carrying out modification in existing panel to fixed MCCB all as specified of following rating:- Make: Havells/ABB/Legrand | |||
4 | 2.01 | (a) 100 Amps, 25 kA. | 2 | Each | |
5 | 2.02 | (b) 63 amps, 25 kA. | 2 | Each | |
6 | 3 | S&F in replacement of MCCB 4 Pole, 415 vots AC, 50 Hz with adjustable thermal fixed magnetic setting complete including carrying out modification in existing panel to fixed MCCB all as specified of following rating:- Make: Havells/ABB/Legrand | |||
7 | 3.01 | (a) 630 Amps, 36KA | 2 | Each | |
8 | 3.02 | (b) 400 Amps, 36KA | 2 | Each | |
9 | 3.03 | (c) 320 Amps, 36 kA. | 2 | Each | |
10 | 3.04 | (d) 250 Amps, 36 kA. | 2 | Each | |
11 | 3.05 | (e) 200 Amps, 25 kA | 2 | Each | |
12 | 3.06 | (f) 160 Amps, 25 kA. | 2 | Each | |
13 | 3.07 | (g) 125 Amps, 25 kA. | 2 | Each | |
14 | 4 | Supply only aluminium thimble of size 25 Sqmm Make- Dowells\n | 55 | Each | |
15 | 5 | All as per item no 4 here in before but of size 35 Sqmm | 35 | Each | |
16 | 6 | All as per item no 4 here in before but of size 50 Sqmm | 40 | Each | |
17 | 7 | All as per item no 4 here in before but of size 70 Sqmm | 30 | Each | |
18 | 8 | All as per item no 4 here in before but of size 95 Sqmm | 35 | Each | |
19 | 9 | All as per item no 4 here in before but of size 120 Sqmm | 30 | Each | |
20 | 10 | All as per item no 4 here in before but of size 150 Sqmm | 30 | Each | |
21 | 11 | All as per item no 4 here in before but of size 185 Sqmm | 25 | Each | |
22 | 12 | All as per item no 4 here in before but of size 240 Sqmm | 25 | Each | |
23 | 13 | All as per item no 4 here in before but of size 300 Sqmm | 20 | Each | |
24 | 14 | All as per item no 4 here in before but of size 400 Sqmm | 20 | Each | |
25 | 15 | M&L for welding of old/broken LT panel door with LT panel including hinges and all other connected accessories as required at site complete all specified and directed | 8 | Each | |
26 | 16 | Dismantling unservicable and S&F RYB phase indicating lamp on existing LT panel including wiring where required all as directed.Make:-HAVELLS/POLYCAB/HPL. | 12 | Set of 3 | |
27 | 17 | Dismantling unservicable and S&F Voltmeter on existing LT panel including wiring where required all as directed.Make:-C&S/HAVELLS/INDOASIAN. | 16 | Each | |
28 | 18 | Dismantling unservicable and S&F RYB Ammeter on existing LT panel including wiring where required all as directed.Make:-C&S/HAVELLS/INDOASIAN. | 16 | Each | |
29 | 19 | Dismantling unservicable and S&F voltage/ammeter selector switch on existing LT panel all as directed.Make:-C&S/HAVELLS/INDOASIAN. | 12 | Each | |
30 | 20 | Supply and fixing in replacement of LT busbar chamber box of appx size 90 cm (Height) x 70 cm (Width) x 45 cm (Depth), outdoor type, double door type, front opening type suitable for 415 volts, 3 phase, 4 wire (100% neutral), 50 Hz supply system all as specified and directed. Box made out of 3 mm thick (outer) & 2 mm thick (inner compartment door) CRCA sheet factory made wheather proof, dust proof and vermin proof duly powder coated with 04 Nos hindalco make aluminum busbar 300 Amps, 50 cm each (each busbar having 04 Nos of nuts, bolts, washers) horizentally placed on insulators suitable for & including MCCB 4 Pole 200 A, 25 kA, 415 volts AC hinged and lockable door arrangement complete with interconnections with aluminium solid strips, busbar chamber mounted on angle iron 40x40x6 mm frame having 4 Nos legs 45 cm long of 40x40x6 mm angle iron, 15 cm grouted in PCC (1:2:4) type C-1 using 20MM graded stone aggregate and 30 cm clear space from ground level including fixed on angle iron frame made out of angle 40x40x6mm ,complete all as specified and directed by Engineer-in-Charge. (Note: Panel shall be a front opening with cable entry from the bottom). Make of MCCB:Havells/ABB/Legrand | 2 | Each | |
31 | 21 | Plate earthing complete with galvanized mild steel plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground vertically (in earth pit not less than 2.25 meter deep below ground level) with the top edge of earth plate at a depth not less than 1.5 meter below normal ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides and including GI strip 25x4 mm bolted with GI nuts, bolts & check nuts and riveted to earth (Plate) electrode at one end and connected to main switch board /panel/ test point at the other including watering GI pipe (medium grade) 20 mm bore from bottom of earth pit to top of electrode and 40 mm bore GI pipe light grade for earth strip protection complete including provision of concrete pit in PCC (1:2:4) type B-I , using 20 mm graded crushed stone aggregate with 40 mm thick cover of RCC (1:2:4) type B-I , using 20 mm graded crushed stone aggregate) reinforced with XPM weight not less than 4 Kg /Sqm and 6mm dia bar handle ,excavation and earth work in any type of soil, returning filling in and removal of surplus soil including testing complete all as specified and as directed. | 4 | Each set | |
32 | 22 | Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth for laying of cables or other items and getting out in soft/loose soil complete all as specifed and directed. | 229 | Cubic metre | |
33 | 23 | Returning filling in soil including spreading levelling watering and well ramming in layers not exceeding 25 cm, complete all as specified and directed. | 132 | Cubic metre | |
34 | 24 | Removing excavated material soil not exceeding 50 mtr and depositing where directed in a level not exceeding 1.5 mtr above the starting point of any type of soil, complete all as specified and directed. | 97 | Cubic metre | |
35 | 25 | Sand cushioning to underground cable 8 cm thick layers below the cable and 15 cm thick above the cable in trenches using fine screened river sand, complete all as specified and as directed.\nNote :- Punned thickness shall be measured and paid. | 68 | Cubic metre | |
36 | 26 | Well burnt old size sub class 'B' bricks of nominal size 230X115X075 mm abutting each other and laid perpendicular to the axis of cable for cable protection, complete all as specified and directed. | 6900 | Each | |
37 | 27 | Re-Laying of serviceable bricks obtained from taking out of cable under serial item No. 28 here-in-after, for protection of cable , complete all as specified and as directed. | 456 | Each | |
38 | 28 | Taking out old underground serviceable/unserviceable cable of any size and any type and keeping aside for the purpose of rerouting/relaying in new location or for requisite replacement/further disposal including taking out bricks, complete all as specified and directed. (Note: Earth work shall be measured & paid separately). | 1310 | Running Metre | |
39 | 29 | Labour only for re-laying of serviceable cable (as obltained from taking out of cable) under serial item 28 above , of any type and size includng making all electrical connections, complete all as specified and directed. | 360 | Running Metre | |
40 | 30 | Supply, laying or passing through pipe underground cable PVC sheathed, XLPE insulated armoured LT 1100 volts grade with aluminium conductor of size 185Sqmm, 3.5 core including making electrical connections, complete all as specified and directed. | 190 | Running Metre | |
41 | 31 | Supply, laying or passing through pipe underground cable PVC sheathed, XLPE insulated armoured LT 1100 volts grade with aluminium conductor of size 150Sqmm, 3.5 core including making electrical connections, complete all as specified and directed. | 180 | Running Metre | |
42 | 32 | Supply, laying or passing through pipe underground cable PVC sheathed, XLPE insulated armoured LT 1100 volts grade with aluminium conductor of size 95Sqmm, 3.5 core including making electrical connections, complete all as specified and directed. | 180 | Running Metre | |
43 | 33 | Supply, laying or passing through pipe underground cable PVC sheathed, XLPE insulated armoured LT 1100 volts grade with aluminium conductor of size 70Sqmm, 3.5 core including making electrical connections, complete all as specified and directed. | 200 | Running Metre | |
44 | 34 | Supply, laying or passing through pipe underground cable PVC sheathed, XLPE insulated armoured LT 1100 volts grade with aluminium conductor of size 50Sqmm, 3.5 core including making electrical connections, complete all as specified and directed. | 180 | Running Metre | |
45 | 35 | Supply, laying or passing through pipe underground cable PVC sheathed, XLPE insulated armoured LT 1100 volts grade with aluminium conductor of size 25Sqmm, 3.5 core including making electrical connections, complete all as specified and directed. | 220 | Running Metre | |
46 | 36 | Supply, laying or passing through pipe underground cable PVC sheathed, XLPE insulated armoured LT 1100 volts grade with aluminium conductor of size 10Sqmm, 2 core including making electrical connections, complete all as specified and directed. | 160 | Running Metre | |
47 | 37 | Note :- An amount of Rs. 31,822.00 on account of credit schdule for Sch 'A' Part-II Shall be deducted from the total amount of BOQ to arrive at the contract sum. |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail