Provision Of Dg Set For New Stp Near Bansi Park And Automatic Power Factor Control ( Apfc ) Panel Installation At Hisar Mil Stn Under Ge Hisar, Hisar-Haryana

Military Engineer Services-MES has published Provision Of Dg Set For New Stp Near Bansi Park And Automatic Power Factor Control ( Apfc ) Panel Installation At Hisar Mil Stn Under Ge Hisar. Submission Date for this Tender is 01-02-2021. Diesel Generators Tenders in Hisar Haryana. Bidders can get complete Tender details and download the document.




Tender Notice

26420745
Corrigendum : Provision Of Dg Set For New Stp Near Bansi Park And Automatic Power Factor Control ( Apfc ) Panel Installation At Hisar Mil Stn Under Ge Hisar
Open Tender
Indian
Haryana
Hisar
01-02-2021

Tender Details

ProvISION Of Dg Set For New Stp Near Bansi Park And Automatic Power Factor Control ( Apfc ) Panel Installation At Hisar Mil Stn Under Ge Hisar

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 15-Jan-2021 Amendment Date 25-01-2021
2 15-Jan-2021 BOQ Amendment BOQ 25-01-2021
3 25-Jan-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 01-02-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 48600.0 /-
Tender Value
Refer document

BOQ Items

Name of Work : Provn of DG Set for new STP near Bansi Park and Automatic power factor control (APFC) panel installation at Hisar Mil Stn under GE Hisar
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Supply, install, testing ans commissioning of silent Diesel engine driven Generating set AC, 415 volts, 3 phase 4 wire 50 Hz, 1500 RPM of capacity 100 KVA with accoustic enclosure, AMF Panel comprising of the following and testing complete all as specified and directed. \nMake : Kirlosker Green Model No KG1-100 WS or Model of Greaves Power / Cummins 1 Each
2 1.01 (a) Diesel Engine : Four cylinder, Liquid cooled, Naturally aspirated and developing 156 BHP @ 1500 RPM, vertical engine, electric start, compression ignition, 4 stroke designed to run continously @ 1500 RPM comfirming to IS 10002m /ISO 3046, BS : 5514 standards with an overload capacity of 10% for one hour in every 12 Hours operation, DG Set to comply with CPCB-II norms and shall comprise the following accesories.\nMake : Kirlosker Green Engine Model No 4K1080TA G2 or its equivalent model viz. equivalent technical specification in other makes as specified here in above.
3 1.02 (i) Radiator, cooling system with fan\n(ii) Micro fuel pump with electronic governor.\n(iii) Dry tube air cleaner\n(iv) Lubricating oil filter (Spin on type)\n(v) 12 Volts electric starting systerm\n(vi) Battery charging alternator\n(vii) Stop solenoid\n(viii) Lub oil pressure gauge\n(ix) Water temprature gauge\n(x) Ammeter battery charging\n(xi) K cool super plus coolant\n(xii) First fill of Lub oil\n(xiii) Safety shut down system for low lube oil\n(xiv) Air valve and drain plug arrangement
4 1.03 (B) Alternator : Alternator suitable for continous operation rated at 1500 RPM, 415 Volts, 3 Phase, 4 Wire system, 50 Hz, 0.8 PF in SPDP enclosure, self excited and self regulated, brushless, foot mounted in single / double bearing construction on end shields conforming to IS-4722, BS EN 60034-1 and will be suitable for tropical condition.
5 1.04 (C) Accoustic enclosure : The accoustic enclosure shall be designed and manufactured conforming to relevant standards suitable for outdoor installation exposed to weather conditions, and to limit noise level of <75 db (A) at a distance of 1 metre from the enclosure as per CRCB II norms. The enclosure shall be fabricated out of FRCA sheet of thickness not less than 2.0mm thick and shall be powder coated.
6 1.05 (D) Control Panel (AMF Panel) : Control panel along with suitable controller and MCCB 4 pole, 25 KA adjustable type to be provided inside canopy.
7 1.06 (E) AMF CONTROL PANEL SUITABLE FOR OUTDOOR INSTALLATION WITH BY PASS ARRANGEMENT : Supply, installation, testing and commissioning of AMF (Automatic Mains Failure) panel suitable for generating set of capacity 100 KVA factor made, fabricated out of CRCA sheet (3.00mm thick) of min size 1.675m x 1.300m x 0.50m, totally enclosed, dust, damp and vermin proof free standing floor mounted type and front operated, degree of protection required will be IP-55 conforming to IS 2147 with and including necessary foundation (minimum height of the base of the panel board should not be less than 0.45 meter) having the following feature / facilities :-
8 1.07 (i) Control system and components such as relays, contactors, timers etc both for automatic operation or mains failure and as well as for manual operation.\n(ii) Necessary instructions and accessories such as Voltmeter, Power factor meter, KW meter, KWH meter, Ammeter, Frequency meter etc in one energy analyser unit with selector switch to obtain the reading of the desired parameter.\n(iii) Necessary indication lamp, fuses, terminal block, push bottons, control switches etc as required.\n(iv) Necessary engine / generating set shut down device due to fault / abnormalities.\n(v) Necessary visual audio alarm indication and annunciation facility as specified.\n(vi) Necessary battery charger.\n(vii) Necessary excitation control and voltage regulating equipment.\n(viii) Necessary breakers as specified in the Schedule of work.\n(ix) All necessaryinternal wiring, connection etc as required.\n(x) 2 Nos MCCB 200 Amps 4 Pole 25 KA for civil as well as DG incoming.\n(xi) 2 Nos MCCB 160 Amps 4 Pole 25 KA for outgoing.\n(xii) Changeover switch 250 Amps 4 Pole on load type for bypass arrangement-1 Nos\n(xiii) Contactor 250 Amps 4 Pole - 2 Nos.\n(xiv) Apart from the above any other arrangement / things required for proper functioning of AMF panel.
9 1.08 Note : \n(i) The cost of first filling of lubricants fuel required for testing and accessories required for proper functioning of DG set shall be deemed to be included in quoted unit rate.\n(ii) Testing of DG set on artificial load shall be carried out for 12 Hours with 10% over load for one hour.\n(iii) Necessary arrangement of precommissioning inspection of inspection officer to be done by the accepting officer.\n(iv) Contractor should submit the technical specifications of the transformer and take necessary approval of accepting officer before placing order of the company.\n(v) DG set should be sound proof as per latest policy.\n(vi) Engine, alternator test certificate and warranty certificate shall be provided by the contractor.\n(vii) Engine operator / maintenance & spare manual shall be given to department.\n(viii) OEM certificate shall be given by the contractor.\n(ix) Tools of DG set shall be supplied by the contractor.
10 2 Supply and installation of 175 KVA, 7 stage (2x50+2x25+2x10+1x5 KVAr) APFC capacitor panel outdoor type with suitable 7 stage APFC relay including fabrication, with 440V MPP (Heavy Duty) capacitor with 400A 50KA TP with inbuilt O/C & S/C with Microprocessor based Release and provised with suitable rating resin cast CTs with Digital Ammeter (0-400 A) with selector switch and Digital Voltmeter (0-500 Volt) with Selector switch, ON/OFF/TRIP LED Indication Lamp and LED phase indication Lamps with control MCBs and suitable rating MCCBs as outgoings with adjustable thermal - magnetic release, as per Standard practice and suitable size enclouser made out of 2mm thick CRCA sheet for frames and door and 1.6mm thick CRCA sheet partition. 3mm thickness for gland plates, dust tight, vermin proof, Bus bar, TPN Aluminium bus bar of rating suitable rating provided with heat shrinkable coloured PVC sleeve insulation mounted on insulators for main bus bar and from main bus bar to outgoing MCCBs and outgoing MCCBs up to cable termination etc complete. (The rating of main bus bar shall be 1.5 times of ampere rating of incomer and outgoing bus bar rating shall be 1.5 times of ampere rating of each outgoing MCCB.) and Continuous earth bus with GI strip of suitable size capable for carrying full short circuit current for 1 sec shall be provided at bottom of the panel totally enclosed with necessary mounting assembley and acessories as per specifications.\n 1 Each Job
11 3 Supply and installation of 150KVAr, 6 stage (2x50+1x25+2x10+1x5KVAr) APFC capacitor panel outdoor type with suitable 6 stage APFC relay including fabrication, with 440V MPP (Heavy Duty) capacitor with 315A 50KA TP with inbuilt O/C & S/C with Microprocessor based Release and provised with suitable rating resin cast CTs with Digital Ammeter (0-400 A) with selector switch and Digital Voltmeter (0-500 Volt) with Selector switch, ON/OFF/TRIP LED Indication Lamp and LED phase indication Lamps with control MCBs and suitable rating MCCBs as outgoings with adjustable thermal - magnetic release, MCBs as per Standard practice and suitable size enclouser made out of 2mm thick CRCA sheet for frames and door and 1.6mm thick CRCA sheet partition. 3mm thickness for gland plates, dust tight, vermin proof, Bus bar : TPN Aluminium bus bar of rating suitable rating provided with heat shrinkable coloured PVC sleeve insulation mounted on insulators for main bus bar and from main bus bar to outgoing MCCBs and outgoing MCCBs up to cable termination etc complete. (The rating of main bus bar shall be 1.5 times of ampere rating of incomer and outgoing bus bar rating shall be 1.5 times of ampere rating of each outgoing MCCB.) and Continuous earth bus with GI strip of suitable size capable for carrying full short circuit current for 1 sec shall be provided at bottom of the panel.totally enclosed with necessary mounting assembley and acessories as per specifications. 1 Each Job
12 4 Supply, laying, jointing, testing and commissioning of LT UG XLPE insulated PVC sheathed, armoured heavy duty electric power cable with multistranded aluminium conductor, 1100 Volts grade, cross sectional area of size 16 sqmm 2 core laid in trenches, wall/floor etc complete all as specified and directed. 20 RM
13 5 Supply, laying, jointing, testing and commissioning of LT UG XLPE insulated PVC sheathed, armoured heavy duty electric power cable with multistranded aluminium conductor, 1100 Volts grade, cross sectional area of size 120 sqmm 3.5 core laid in trenches, wall/floor etc complete all as specified and directed. 300 RM
14 6 Excavation in trenches in soft / loose soil not exceeding 1.5m wide and not exceeding 1.5m in depth for laying of cable etc and for foundation of poles, stays etc, not exc 10 sqm on plan and n exc 1.5m in depth and getting out complete all as specified and directed. 47.5 Cum
15 7 Excavation in trenches in hard / dense soil not exceeding 1.5m wide and not exceeding 1.5m in depth for laying of cable etc and for foundation of poles, stays etc, not exc 10 sqm on plan and n exc 1.5m in depth and getting out complete all as specified and directed. 1 Cum
16 8 Removing excavated soil/material to a distance not.exc. 50m and depositing where directed at a level not exc. 1.5m above starting point complete all as specified and directed. 17 Cum
17 9 Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm thick of soft / loose soil in trenches / pit complete all as specified and directed. 29.65 Cum
18 10 M&L for sand cushioning and covering with clean and dry sand to underground electric cable in trenches 8cm thick before laying and 15cm after laying & stretching the cable. Punning shall be carried out by hand complete all as specified and directed.\nNote : Punned thickness shall be measured and paid separately. 14.04 Cum
19 11 M&L for brick covering to underground electric cable using sub class "B" old size brick laid dry flat per pendicular to the direction of cable complete all as specified and directed. 1.41 Per 1000 Nos
20 12 M&L for earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6mm thick burried directly in ground not less than 2.25 mtrs deep below normal ground level with top edge of the earth plate not less than 1.5 mtrs below normal ground level, surrounded from all sides with mixture of charcoal and common salt, connected to galvanized earth lead strip 25 x 4.00mm means of bolts, nuts, check nuts and washers of galvanized iron or steel protected by galvanised iron light grade 40mm dia protection pipe and 20mm light grade for water filling including 15x20mm reducer socket funnel wire mesh, RCC cover with concrete 1:2:4 using 8 mm# bar@100 mm c/c both ways ,PCC chamber pit with PCC (1:3:6) type C-2 and excavation and earth work,disposal of suplus spoil to a dstance not exceeding 50mtrs all as specified and shown on electrical plate No. 3 of 2009 (Part-I) complete all as specified and directed.\nNote :- The unit rate includes for protection pipe and GI strip 25 x 4.00mm dia from top of earth plate up to 7.5 meter above ground level. 6 Each Set