Rural Development and Panchayat Raj Department has published Supply Installation Testing And Commissioning Of 1 Mva Distribution Transformer Servo Stabilizer And Lt Panel Along With Allied Works In Ess Block Of Maternity Hospital At Skims Soura. Submission Date for this Tender is 03-02-2021. Servo Stabilizer Tenders in SKIMS Soura Jammu And Kashmir. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 31-Dec-2020 | ADDENDUM | Other | 07-01-2021 |
2 | 07-Jan-2021 | date extension | Date | 12-01-2021 |
3 | 08-Jan-2021 | Corrigendum | Other | 12-01-2021 |
4 | 11-Jan-2021 | Corrigendum N Extension | Date | 15-01-2021 |
5 | 18-Jan-2021 | Extension III | Date | 27-01-2021 |
6 | 29-Jan-2021 | ECTENSION IV | Date | 03-02-2021 |
Name of Work: SITC of 1 MVA Distribution Transformer,Servostabiliser and LT Panel Along with Allied Works in ESS BLOCK of Maternity Hos[ital at SKIMS Soura. | |||||
---|---|---|---|---|---|
S. No. | Electrification | Item Code / Make | Quantity | Units | |
1 | 1 | Supply ,Installation.Testing & Commisioning of Distribution Transformer Energy Efficientcy Level 2nd 1000KVA,11/0.433KV 50Hz,Outdoor type,Dyn-11 oil immersed,CopperWound,ONAN Cooled, step down ,Distribution Transformer having C.R.G.O core ,Confirming to IS: 1180 Part-1:2018 with latest amendments dully tested,painted and Oil filled to IS: 335 of 1983 with Latest amendments.The transformer shall be complete with following fittings:- \na) Oil conservator with oil level indicator , minimum level marking and drain plugs. b) Off circuit type tap changer with position indicator and locking arrangement. c) 100mm dial type /Stem type thermometer with metal gaurd. d) Lifting lugs and Bi-directional roller. e) Rating Diagram and terminal marking plate f) Explosion Vent and valves for filtration ,drainage and filling e.t.c with necessaryplugs ,including air release plug. g) Radiator assembly and silica gel breather. (ALBA/ABB/BHEL/Crompton/Andrew-yule/Electric field/JK Transformers make)\n | item1 | 2 | job |
2 | 2 | \nContruction Of RCC bed for 1000 KVA transformer 6' x 8' x 5' | item2 | ||
3 | 3 | a) Earth work excavation manually inculding disposal of earth as directed within SKIMS permises=8'x6'x1'-0" X 2 no. | item3 | 6 | CUM |
4 | 4 | b) P/L of stone soling of specified size including Cost & carraige of material complete, 8'x6'x0'-4"=15.84cft =0.448 cum X 2 no. | item4 | 1 | CUM |
5 | 5 | c) P/L of plain cement concrete 1:4:8 mixture incuding cost & carriage of material complete Qty vide part (b) = 0.448 cm X 2 no. | item5 | 1 | CUM |
6 | 6 | d) P/L of R.C.C work 1:2:4 mix including cost and carriage of material 8'x6'x5' = 240 cft X 2 no. | item6 | 13.58 | CUM |
7 | 7 | e) P/L of steel reinforcement (TMT) 12mm dia including cost of cutting, bending ,binding including cost binding wire Qty vide item (d) = 6.79 cum @ 35 kg/cum X 2 no. | item7 | 500 | KGS |
8 | 8 | f) Shuttering by steel plates/ wooden planks including removal of same after use. | item8 | 13 | Sqmtr |
9 | 9 | Supply, installation, testing and commissioning of servo motor operated line voltage correctors copper wound. Indoor, continuous duty, three phase, to work under unbalanced condition of input voltage and unbalance load which shall comprise 3 nos. fully IC controlled sensing circuit microprocessor based with built in filters & improve the output wave to be pure sinusoidal and control each phase individually. Conforming to IS. 9815: with input voltage range: 250-460V (phase to phase), output voltage 415 (As set output voltage), ± 1%,with under voltage, over voltage & over current protection, naturally oil cooled with first filling of transformer oil with necessary bypass switch arrangement complete with following accessories etc. as required. (Make as Per Makelist Annexed to NIT )\nCapacity - 800 KVA Input - 250 – 460 V AC\nOutput - 415 V + - 1 % First filling of oil\nDrive : Heavy duty A.C Sychronous Motor\nAlarms:\n a) Input low voltage cutoff . b) Input High voltage cutoff.\n c) Output low voltage cutoff. d) Output High voltage cutoff\n Controls: \n a) Auto/Manual. b) Manual Bypass changeover Switch\n c) Manual Raise/Lower for output voltage d) Metering digital.\nUnder / Over Voltage Cutoff Protection Using Contactor 1250A \n Stabiliser Standard:- As per IS: 9815, 1250 Amp.FP ACB ( Electrically Operated ) having breaking capacity atleast 50KA at input for over load and short circuit protection in M.S. enclosure with bus bar.Manual By-Pass / Changeover Switch 1250A - With Enclosure.Complete as per SBD.\n | item9 | 2 | job |
10 | 10 | Providing and making of earth pits using appropriate mixture of salt and charcoal.The job includes providing fixing of copper plate of size 600mmx600x3mm, pit should be dug 3 mtr from the surface including 25mmx5mm copper strip in separate 1½" G.I Pipe from plate to surface and laying of 40 mm G.I water pipe to the plate complete as per latest specification. | item10 | 12 | job |
11 | 11 | Providing and fixing of 25mm x 5mm G.I strip from earth pits to 1000 KVA Distribution Transformer /Servo stabiliser/ LT Panel to be laid through 2 mm thick MS conduit of appropriate dia . | item11 | 500 | mtr |
12 | 12 | Supplying, installation, including suspension, testing and commissioning of following capacity bus trunking with aluminium bus bars having current density of 130 A/ sq. cm at nominal current rating in 1.6mm thick IP 42 sheet steel enclosure in convenient sections for use on, 3 phase, 4 wire, 415 V, 50 Hz, A.C. supply including jointing of sections, flexible joints, expansion joints, bends and earthing with 2 runs of galvanised iron strips, suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required(Make as Per Makelist Annexed to NIT ) | item12 | ||
13 | 13 | 1250 amps | item13 | 30 | MTR |
14 | 14 | Supplying, installing, testing and commissioning of compartmentalised type cubicle board, made of 2 mm thick CRCA sheet steel providing with suitable size angle iron and channels support with suitable size of base channel for floor mounting, dust & vermin proof duly phosphatized & powder coated, inclusive of suitable size 4 strip Aluminium busbar covered with heat shrinkable sleeves of suitable size and length. The panel shall be suitable for incoming Bus ducting and outgoing cables from top and bottom both sides, pdg. inter-earthing and inter-connection with PVC insulated copper conductor cable solid copper conductor of suitable sizes and lugs on both ends of each cable and making electrical & Mechanical inter locking in incomings and bus coupler, and providing all meters with back up fuses & Selector switches etc. i/c pdg. & fixing below noted accessories. INCOMING : SECTION-I 1250 Amp 415 V FP ACB (EDO Draw- out Type) having breaking capacity - 65 KA, with short circuit, earth fault & over-current relay - 1 No. (Incoming from Transformer-1) (0-1250 A) Digital Ammeter with selector switch & 1250/5 C.T.'s - 1 Set (0 - 500) Volt Voltmeter Digital type with selector switch -1 Sets RYB Indication lamps with MCB - 1 Set of three 1000 Amp 415 V FP ACB (EDO Draw- out Type) having breaking capacity - 65 KA, with short circuit, earth fault & over-current relay - 1 No. (Incoming from Synchronization Panel O/G-2) (0-1000 A) Digital Ammeter with selector switch & 1000/5 C.T.'s - 1 Set (0 - 500) Volt Voltmeter Digital type with selector switch -1 Sets RYB Indication lamps with MCB - 1 Set of three (CONTINUED IN BELOW CELL) | item14 | 1 | job |
15 | 15 | BUS COUPLERS - 2 1250 Amp 415 V FP ACB (EDO Draw- out Type) having breaking capacity - 65 KA, with short circuit, earth fault & over-current relay - 1 No. Electrical & Mechanical Interlocking - Electrical Interlocking through Contactors & Mechanical Interlocking through Locks SECTION-2 INCOMING : 1250 Amp 415 V FP ACB (EDO Draw- out Type) having breaking capacity - 65 KA, with short circuit, earth fault & over-current relay- 1 No. (Incoming from Transformer-2) (0-1250 A) Digital Ammeter with selector switch & 1250/5 C.T.'s - 1 Set (0 - 500) Volt Voltmeter Digital type with selector switch -1 Sets RYB Indication lamps with MCB - 1 Set of three 1000 Amp 415 V FP ACB (EDO Draw- out Type) having breaking capacity - 65 KA, with short circuit, earth fault & over-current relay - 1 No. (Incoming from Synchronization Panel o/g-1) (0-1000 A) Digital Ammeter with selector switch & 1000/5 C.T.'s - 1 Set (0 - 500) Volt Voltmeter Digital type with selector switch -1 Sets RYB Indication lamps with MCB - 1 Set of three (CONTINUED IN BELOW CELL) | item15 | ||
16 | 16 | BUS COUPLERS -1 1250 Amp 415 V FP ACB (EDO Draw- out Type) having breaking capacity - 65 KA, with short circuit, earth fault & over-current relay - 1 No. Electrical & Mechanical Interlocking - Electrical Interlocking through Contactors & Mechanical Interlocking through Locks SECTION-3 INCOMING : 1250 Amp 415 V FP ACB (EDO Draw- out Type) having breaking capacity - 65 KA, with short circuit, earth fault & over-current relay - 1 No. (Incoming from Transformer-3) (0-1250 A) Digital Ammeter with selector switch & 1250/5 C.T.'s - 1 Set (0 - 500) Volt Voltmeter Digital type with selector switch -1 Sets RYB Indication lamps with MCB - 1 Set of three CONTINUED ....IN BELOW CELL | item16 | ||
17 | 17 | OUTGOING: SECTION-1 1000 Amp 415 V TP ACB MDO TYPE having breaking capacity - 50 KA, with Ics=Icu=50 KA, - 1 Nos. 630 Amp 415 V TP MCCB having breaking capacity - 50 KA, with Ics=Icu=50 KA, with Rotary Handle operating Mechanism - 2 Nos. 400 Amp 415 V TP MCCB having breaking capacity - 36 KA, with Ics=Icu=50 KA, with Rotary Handle operating Mechanism - 2 Nos. 320 Amp 415 V TP MCCB having breaking capacity - 36 KA, with Ics=Icu=50 KA, with Rotary Handle operating Mechanism - 2 Nos. 100 Amp 415 V TP MCCB having breaking capacity - 25 KA, with Ics=Icu=50 KA, with Rotary Handle operating Mechanism - 2 Nos. 63 Amp 415 V TP MCCB having breaking capacity - 10 KA, with Ics=Icu=10 KA, with Rotary Handle operating Mechanism - 2 Nos. (CONTINUED IN BELOW CELL) | item17 | ||
18 | 18 | OUTGOING: SECTION-2 1000 Amp 415 V TP ACB MDO TYPE having breaking capacity - 50 KA, with Ics=Icu=50 KA, - 1 Nos. 630 Amp 415 V TP MCCB having breaking capacity - 50 KA, with Ics=Icu=50 KA, with Rotary Handle operating Mechanism - 2 Nos. 400 Amp 415 V TP MCCB having breaking capacity - 36 KA, with Ics=Icu=50 KA, with Rotary Handle operating Mechanism - 2 Nos. 320 Amp 415 V TP MCCB having breaking capacity - 36 KA, with Ics=Icu=50 KA, with Rotary Handle operating Mechanism - 2 Nos. 100 Amp 415 V TP MCCB having breaking capacity - 25 KA, with Ics=Icu=25 KA, with Rotary Handle operating Mechanism - 2 Nos. 63 Amp 415 V TP MCCB having breaking capacity - 10 KA, with Ics=Icu=10 KA, with Rotary Handle operating Mechanism - 2 Nos. BUS BAR 4 strip Al. busbar of 1600 A capacity complet with all accessories | item18 | ||
19 | 19 | Supply and laying of 120 mmsq 3core 11 KV (E) XLPE cable circular aluminium conductor, conductor screened, XLPE insulated, insulation screened with extruded semi-conducting compound in combination with copper tape. Aluminium round wire armoured and overall PVC sheathed earthed cable conforming to IS:7098/II/85 with latest amendments.(Havells/Polycab/KEI/Gloster/Paramount make) | item19 | 15 | mtr |
20 | 20 | Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :(Denson /3M/ Frontec/Raychem make) | item20 | 4 | set |
21 | 21 | Supply,testing,connecting & Commissioning of 1000 mm ² single core Aluminium PVC Sheathed Armoured cable (ISI Marked) (Polycab /Havells/Gloster/KEI/Skytone make) from alternator to AMF Panel to main sub-station 1600 Amp Changeover switch | item21 | 1200 | mtr |
22 | 22 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective brick covering and refilling the trench etc as required.\na ) 1000 mm Sq. | item22 | 400 | mtr |
23 | 23 | Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.\na) 1000 mm Sq. | item23 | 400 | mtr |
24 | 24 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.\na) 1000 mm Sq. | item24 | 300 | mtr |
25 | 25 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.\na) 1000 mm Sq. | item25 | 100 | mtr |
26 | 26 | Providing and making of end termination of 1000 mm² single core Aluminium cable including thimbling, crimpingincluding colour coded heat shrinkable slecrc, testing and connecting as per site requirements (dowels /3D make) | item26 | 20 | no |
27 | 27 | Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.. | item27 | ||
28 | 28 | 450 mm width X 50 mm depth X 2.0 mm thickness | item28 | 20 | mtr |
29 | 29 | 600 mm width X 62.5 mm depth X 2.0 mm thickness | item29 | 20 | mtr |
30 | 30 | Providing and fixing of brass compression Cable Glands of 1000 mm sq. single core Aluminium Cable . | item30 | 20 | no |