}

Repair And Maint Of Lt Infra Feeder Piller Box And Allied Works At Af Stn Mandore Under Age Em At Ge Af No 2 Jodhpur . , GE (AF) NO 2 JODHPUR-Rajasthan

Military Engineer Services-MES has published Repair And Maint Of Lt Infra Feeder Piller Box And Allied Works At Af Stn Mandore Under Age Em At Ge Af No 2 Jodhpur . . Submission Date for this Tender is 14-12-2020. Feeder Pillar Tenders in GE (AF) NO 2 JODHPUR Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

26089341
Corrigendum : Repair And Maint Of Lt Infra Feeder Piller Box And Allied Works At Af Stn Mandore Under Age Em At Ge Af No 2 Jodhpur .
Open Tender
Indian
Rajasthan
GE (AF) NO 2 JODHPUR
14-12-2020

Tender Details

Repair And Maint Of Lt Infra Feeder Piller Box And Allied Works At Af Stn Mandore Under Age Em At Ge Af No 2 Jodhpur .

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 07-Dec-2020 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 14-12-2020

Key Value

Document Fees
INR 500 /-
EMD
INR 30000.0 /-
Tender Value
INR 15 Lakhs /-

BOQ Items

Name of Work : REPAIR AND MAINT OF LT INFRA ,FEEDER PILLER BOX AND ALLIED WORKS AT AF STN MANDORE UNDER AGE E/M AT GE (AF) NO 2 JODHPUR.
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Excavation in trenches n.exc 1.5 Mtr wide and n.exc 1.5 Mtr in depth in soft/loose soil and getting out complete all as directed. 94 CUM
2 2 Returning, filling in trenches including spreading, levelling, watering and well ramming in layers n.exc 25cm complete all as directed. 60.12 CUM
3 3 Removal of excavated material to a distance n.exc 50 mtr and depositing where directed at a level n.exc 1.5 m above the starting point complete all as specified and as directed. 34.38 CUM
4 4 M&L sand cushioning / filling for underground cable protection, filling under floors ,consolidated and compacted with clean dry sand complete all as specified and as directed. 28.35 CUM
5 5 M & L stone Slab 40 to 50 mm thick rough dressed jodhpur stone patties/ slab cover in trenches for protection of cable 25 to 30 CM wide and thickness not less than 50 mm in length lay dry abutting each other with gap between adjacent slab not exceeding 10 mm over sand cushioning. 94 SQM
6 6 Taking out defective LTUG cable XLPE/PVC sheathed 1100 volt grade heavy duty armoured with aluminium conductor from trenches, shifting serviceable cable 4 core 16 sqmm for relaying or taking the unserviceable cable as credit complete all as specified and directed for the following:-\nNote: Excavation and earth work shall be measured and paid for separately. 50 RM
7 6.01 All as per itme No 6 above but 3.5 core 25 Sqmm 150 RM
8 6.02 All as per itme No 6 above but 3.5 core 35 Sqmm 100 RM
9 6.03 All as per itme No 6 above but 3.5 core 50 Sqmm 100 RM
10 6.04 All as per itme No 6 above but 3.5 core 70 Sqmm 100 RM
11 7 Supplying, Laying, Jointing and testing of under ground cable XLPE insulated, 1100 volt grade heavy duty armoured with stranded aluminium conductor 4 core 16 sqmm laid in trenches/ duct/ pipe including all electrical connection with required lugs and nuts, bolts complete all as specified and directed by Engr-in-Charge. 50 RM
12 7.01 All as per itme No 7 above but 3.5 core 25 Sqmm 150 RM
13 7.02 All as per itme No 7 above but 3.5 core 35 Sqmm 100 RM
14 7.03 All as per itme No 7 above but 3.5 core 50 Sqmm 100 RM
15 7.04 All as per itme No 7 above but 3.5 core 70 Sqmm 100 RM
16 8 Taking out of existing LT UG cable of any size after joining using LT cable joining kit provided in item No 9 to 12 complete all as specified and directed. 4 Each\nJob
17 9 S&F LT Cable joining kit straight through heat shrinkable type complete with joining materials suitable for LT Armoured cables of size upto10- 25 Sqmm 2/3.5/4 core all as directed. 1 EACH
18 10 S&F LT Cable joining kit straight through heat shrinkable type complete with joining materials suitable for LT Armoured cables of size 35-70 Sqmm 3.5 core all as directed. 1 EACH
19 11 S&F LT Cable joining kit straight through heat shrinkable type complete with joining materials suitable for LT Armoured cables of size 95 Sqmm 3.5 core all as directed. 1 EACH
20 12 S&F LT Cable joining kit straight through heat shrinkable type complete with joining materials suitable for LT Armoured cables of size 185-300 Sqmm 3.5 core all as directed. 1 EACH
21 13 Supply and fix in repairs GI Strip 32 x 6 mm burried in ground/ laid in floor/ fixed to wll on saddles/ on porcelain insulators etc as directed. 20 RM
22 14 Material and labour for earthing complete with galvanized steel earth plate electrode 60cmx60cmx6mm thick, buried directly in ground, vertically to a depth not less than 2.25 mtr deep below ground level with top edge of the earth plate at depth not lss than 1.5 mtr below ground level earth plate surrounded by 15 cm thick and packed layers of charcoal, dust and common salt, earth lead GI strip 32 x 6mm by means of bolts, nuts, check-nuts and washers of galvanised iron and thimbles and of earth wire protected by galvanised iron pipe light grade 40mm bore and water pipe 20mm bore GI medium grade with funnel and wire mesh complete 1:3:6 type C-1 using 20mm graded stone aggregate in lieu of CI cover and frame etc all as specified and shown in electrical plate No 3 of SSR- 2009 (Part-1) 6 Each
23 15 Supply and fixing MCCB in replacement of 63 Amps, 3/4 pole, 415 volts, 50 HZ, rupturing capacity 16KA, connection with proper size of thimbles complete including taking out defective/ unserviceable MCCB all as specified and directed. 1 Each
24 16 All as per item No 15 above but 100 Amps, 16 KA 1 Each
25 17 Supply and fix MCCB in replacement with thermal magnetic release adjustable type DU 160, 125A, 16KA, 415 Volts 3/4 pole all as specified & directed. 1 Each
26 18 Supply and fix MCCB in replacement with thermal magnetic release adjustable type DU 160, 160A, 36KA, 415 Volts 3/4 pole all as specified & directed. 1 Each
27 19 All as per item No 18 above but 200 Amps, 36 KA 1 Each
28 20 Supply and fix MCCB in replacement with thermal magnetic release adjustable type DN2-250D, 250A, 415 Volts 4 pole 36KA all as specified & directed. 2 Each
29 21 Supply and fix MCCB in replacement with thermal magnetic release adjustable type DN3-400D, 400A, 415 Volts 4 pole 36KA all as specified & directed. 2 Each
30 22 S & F Change over main switch, on load, four poles, 200 Amps, 415 Volts, 36 KA ,50 Hz, with enclosure, fixed in the existing LT panel board/ sheet metal enclosure including connecting up incoming/ out going cables with suitable lugs and testing complete all as specified and as directed. Make: L & T 1 Each
31 23 M & L in repair incl taking down old GI tubing Light grade 80mm incl all accessories for protection cable complete all as specified and directed in engr-in-charge 6 RM
32 24 All as per item No 23 above but 50mm 70 RM
33 25 All as per item No 23 above but 40mm 50 RM
34 26 Taking out of existing old unsv LT Panel of any size complete all as specified and directed. 4 Each\nJob
35 27 Supply, install, testing and commissioning of outdoor type factory made ,CRCA Sheet, thickness 3.15 mm, platform mounted LT panel board to accomodate the following items and built upon angle iron frame suitable size compartmentalized design work, duly powder coated with gray paint and suitable size of cable glands chromium plated and copper busbars TPN, 400 Amps,415 V,50 Hz complete as following :- \n(i) MCCB 250 Amps, 4 Pole, 36 kA-01 (Incoming) (ii) MCCB 125 Amps, 4 Poles, 25 kA - 01 No (Outgoing) \n(iii) MCCB 63 Amps, 4 Pole, 25 KA - 03 (Outgoing)\n(iv) Volt meter 0 - 500 V digital type with selector switch - 1 No\n(v) Amp meter 0 - 200 A digital type with selector switch - 1 No \n(vi) Indicating lamp LED RYB set of three with colour codeing - 1 No.\n(vii) ON load change over switch 125 Amps-01 No\n 1 Each
36 28 Supply, installing, testing and commissioning of LT OUTdoor type panel totally enclosed floor mounted fabricated made out of 16 SWG MS sheet and angle iron frame 40x40x6 frame work cubical. The panel should be vermin proof with IP-55, protection suitable 415/440 V , AC 50 Hz , 3 Ph , 4 wire system panel board should be powder coated painted with two coat of approved shade over one coat of red oxide. the panel shall be front and rear opening type and not less than 60 cm above ground level consisting of copper bus bar of 400 Amps capacity for 3 phase and neutral and consisting of the following:-\nIN COMING\n(a) LED Display Voltmeter square type with selector switch-01 (b) LED Display Amp meter 0-100 A with CTs and selector switch -01 (c) R-Y-B neon indicating lamp (set of three)-01 (d) Panel earth connector -02 \n(e) Danger notice plate -01 \n(f) Cable gland suitable size (g) MCCB 4 Pole 160 Amps 35 KA 415 V -01 No OUT GOING (a) MCCB 4 Pole 100 Amps 25 KA 415 V -01 No\n(b) MCCB 4 Pole 63 Amps 25 KA 415 V - 02 No\n(c) MCB TPN Pole 40 Amps 415 V - 02 No\n(d) Fully automatic star delta starter with SPP for cap 12.5 HP Motor - 02 No 1 Each Job
37 29 Supply, installing, testing and commissioning of LT OUTdoor type panel totally enclosed floor mounted fabricated made out of 16 SWG MS sheet and angle iron frame 40x40x6 frame work cubical. The panel should be vermin proof with IP-55, protection suitable 415/440 V , AC 50 Hz , 3 Ph , 4 wire system panel board should be powder coated painted with two coat of approved shade over one coat of red oxide. the panel shall be front and rear opening type and not less than 60 cm above ground level consisting of copper bus bar of 400 Amps capacity for 3 phase and neutral and consisting of the following:-\nIN COMING\n(a) LED Display Voltmeter square type with selector switch-01 (b) LED Display Amp meter 0-100 A with CTs and selector switch -01 (c) R-Y-B neon indicating lamp (set of three)-01 (d) Panel earth connector -02 \n(e) Danger notice plate -01 \n(f) Cable gland suitable size (g) MCCB 4 Pole 250 Amps 35 KA 415 V -01 No OUT GOING (a) MCCB 4 Pole 160 Amps 25 KA 415 V -02 No\n(b) MCCB 4 Pole 100 Amps 25 KA 415 V - 03 No\n(c) MCB TPN Pole 40 Amps 415 V - 02 No\n 1 Each Job
38 30 Supply, installing, testing and commissioning of LT OUTdoor type panel totally enclosed floor mounted fabricated made out of 16 SWG MS sheet and angle iron frame 40x40x6 frame work cubical. The panel should be vermin proof with IP-55, protection suitable 415/440 V , AC 50 Hz , 3 Ph , 4 wire system panel board should be powder coated painted with two coat of approved shade over one coat of red oxide. the panel shall be front and rear opening type and not less than 60 cm above ground level consisting of copper bus bar of 315 Amps capacity for 3 phase and neutral and consisting of the following:-\nIN COMING\n(a) LED Display Voltmeter square type with selector switch-01 (b) LED Display Amp meter 0-100 A with CTs and selector switch -01 (c) R-Y-B neon indicating lamp (set of three)-01 (d) Panel earth connector -02 \n(e) Danger notice plate -01 \n(f) Cable gland suitable size (g) MCCB 4 Pole 200 Amps 35 KA 415 V -01 No OUT GOING (a) MCCB 4 Pole 100 Amps 25 KA 415 V -01 No\n(b) MCCB 4 Pole 63 Amps 25 KA 415 V - 02 No\n(c) MCB TPN Pole 40 Amps 415 V - 02 No\n(d) ONLINE DOL starter for cap 2 HP submersible Motor - 02 No 1 Each Job
39 31 PCC 1:4:8 type D-2 using 40 mm graded crushed stone aggregates as in foundation of poles etc filling and mess concrete complete all as specified. 3 Cum
40 32 PCC 1:2:4 type B-1 using 20 mm graded crushed stone aggregates as in foundation of poles etc filling and mess concrete complete all as specified. 3 Cum
41 33 M&L HERITAGE LED Post Ideal to lit up parks, garden ways and heritage sites 20 Watts complete all as directed by Engr-in -Charge Make :Crompton cat pat no -LPTH-20-CDL or eqult Havells/Bajaj 20 Each
42 34 Supply and fix single core PVC insulated FR cable with multi stranded copper conductor 1.5 sq mm cross sectional area ,1100 volts grade all as specified and as directed. 100 RM
43 35 M&L LED Flood light luminaire 200 Watts Capacity pressure die cast aluminium housing with heat resistant toughned glass and IP66 protection System efficeincy of 110LPW option for 3000K 10 KV SPD include complete all as directed by Engr-in -Charge Make :Crompton cat pat no -LFLN-200-CDL/60-M or eqult Havells/Bajaj 10 Each
44 36 S & F Change over main switch, on load, four poles, 400 Amps, 415 Volts, 36 KA ,50 Hz, with enclosure, fixed in the existing LT panel board/ sheet metal enclosure including connecting up incoming/ out going cables with suitable lugs and testing complete all as specified and as directed. Make: L & T 1 Each
45 37 Material and labour for painting with two coats of synthetic enameled paint on LT PCC pole upto 1.5 mtr above the GL in alternatively black and white strap of 30 cm each after scrapping/ removing the existing paint and the preparation the surface of PCC LT pole complete. 70 Each
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail