Military Engineer Services-MES has published Repairs Maintenance And Updation Of Automation System Scada For Water Supply System Connected Works Under Ge I Navy Jamnagar. Submission Date for this Tender is 30-03-2021. SCADA Tenders in GE I NAVY JAMNAGAR Gujarat. Bidders can get complete Tender details and download the document.




Tender Notice

26051822
Corrigendum : Repairs Maintenance And Updation Of Automation System Scada For Water Supply System Connected Works Under Ge I Navy Jamnagar
Open Tender
Indian
Gujarat
GE I NAVY JAMNAGAR
30-03-2021

Tender Details

Repairs Maintenance And Updation Of Automation System Scada For Water Supply System Connected Works Under Ge I Navy Jamnagar

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 28-Nov-2020 CORRIGENDUM TO TENDER BOQ 05-12-2020
2 05-Dec-2020 CORRIGENDUM TO TENDER Date 12-12-2020
3 08-Dec-2020 CORRIGENDUM TO TENDER Technical Bid 12-12-2020
4 12-Dec-2020 CORRIGENDUM TO TENDER DATE Date 19-12-2020
5 18-Dec-2020 CORRIGENDUM TO TENDER REVISED DATE Date 04-01-2021
6 21-Dec-2020 Date Corrigendum IV Date 09-01-2021
7 06-Jan-2021 Date Corrigendum V Date 20-01-2021
8 19-Jan-2021 Date Corrigendum VI Date 06-02-2021
9 03-Feb-2021 DATE CORRIGENDUM TO TENDER Date 06-03-2021
10 05-Mar-2021 Date Corrigendum VIII Date 23-03-2021
11 23-Mar-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 30-03-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 34000.0 /-
Tender Value
INR 17 Lakhs /-

BOQ Items

Name of Work: REPAIRS/ MAINTENANCE AND UPDATION OF AUTOMATION SYSTEM (SCADA) FOR WATER SUPPLY SYSTEM CONNECTED WORKS UNDER GE (I) NAVY JAMNAGAR
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Repair/ Maintenance/ updating including operation and regular maintenance of the Automatic water suppply system excluding spares. Carrying out complete maintenance/ servicing/ Repairs with establishing Ladder Logic Programming as required of all the sub system viz. PLC based control panels (with all the Morris), breakdown maintenanace all as specified and directed by Engineer-in-Charge on following location:-\nEstablishing Ladder Logic programming Automation Control Panel at location: Main Pump House, Pump House No.2, NEU Pump House, Bedi Well Pump House No.1 & 2, Bedi OHT, OHT No.3, OHT No.4, OHT No.5, OHT No. 7&8 and MIMIC Panel at Main Pump House.\nNotes:-\n(i) Unit rate quoted by tenderer is of checking of system fortnightly and necessary servicing, repair and daily printing log sheets data on hourly basis and to be submitted to EIC the register will be maintained to that effect. \n(ii) In addition to above specific emergency complaints from time to time shall be attended after receiving the same.\n(ii)The work has to be carried by OEM M/S Recktronic Devices & Systems or through their authorized agent documents of authorization provided before execution of work. \n(iv) Quoated rate deems to be included for SIM card charges and Data \n 11 Per Month
2 2 Dismantling existing IPS monitor by disconnecting all connection of any description and Supply, install, testing and commissioning of new 32 inch IPS monitor inclusing necessary connection at SCADA Room at Pump House No.1 for data monitoring and report submission on daily basis complete all as specified. Make: LG/ Samsung/ ASUS/ ACER/ Dell Model Optiplex 1 Each
3 3 Dismantling existing IPS monitor by disconnecting all connection of any description and Supply, install, testing and commissioning of new 22 inch IPS monitor including necessary connection at SCADA Room at Pump House No.1 for data monitoring and report submission on daily basis complete all as specified. Make: LG/ Samsung/ ASUS/ ACER/ Dell Model Optiple 1 Each
4 4 Dismantling existing printer by disconnecting all connection of any description and Supply, install, testing and commissioning of new Lesar Jet Printer complete all as specified. Make: HP Laser Jet 1020 Plus or equivalent in Canon, Samsung 1 Each
5 5 S&F in repairs single phase preventer, AC, 415 V including commissioning & testing complete all as specified. Make: Minilec Model 1:VSP D2/ L&T / C&S\n 3 Each
6 6 S&F in repair relay with base 4 C/O / 24 V DC / 240 V DC. Make: LEONE Cat Part No. AY4S-05D or equivalent in IDEC 5 Each
7 7 S&F in repair GPRS communication modem alongwith suitable patch chord and mounting Mrories compatible with existing system. Make: Motorola Cat Part No. M100 or equivalent Visiontek / LEO / Meastro Heritage\n 3 Each
8 8 S&F in repair LED type Red /Yellow /Green indicating lamp Make: ESBEE Cat Part No. or equivalent in TEKNIC / TELEMEACHNIQUE 20 Each
9 9 S&F in repair PLC (Programmable Logic Controller) comprising of Main Controller, MMI with display, input / output. Make: Unitronics Cat Part No. XB7-EV04 MPN or equivalent in Mitsubishi / Electric India / Siemens 1 Each
10 10 S&F water lever controller PCB-5/10 level. Make: SPLASH / RDS / ICS 1 Each
11 11 S&F push botton with LED indicator, 240 V AC colour Red/Yellow/Green. Make: ESBEE Cat Part No. XB-AW-34M 2N WITH NC or equivalent in TEKNIC / TELEMEACHNIQUE 20 Each
12 12 S&F in repairs Flow switch. Make: Danfoss Cat Part No. RC 61(8481-80) or equivalent in Rapid Control 2 Each
13 13 S&F Selector Switch / Buzzer. Make Scheinder Cat Part No. XBS-AD33 N WITH 2NO 2 Each
14 14 S&F in repais solenoid valve 10mm/15mm/20mm bore 230 V AC. Make: Rotex Cat Part No. 9210B61/BR/54/BN/BSP or equivalent in Avcon / Johnson Controls / Danfoss 5 Each
15 15 S&F coil for solenoid valve 10mm/15mm/20mm bore 230 V AC. Make: Rotex Cat Part No. 9210B61/BR/54/BN/BSP or equivalent in Avcon / Johnson Controls / Danfoss 2 Each
16 16 S&F Magnetic level switch. Make: RDS Cat Part No. MG 03 or equivalent in Mahalaxmi / Crystal 3 Each
17 17 S&F in repairs Pressure switch 0-10 kg/sqcm. Make: Indfoss Cat Part No. P220 7MF1567-3CA00-1GA1 or equivalent in Danfoss 2 Each
18 18 S&F in repairs Ultrasonic Level Transmitter at Pure Water Sump (for measurement of level in pure water sump / OHT) having 0-5 meters range, 0.5% minimum Accuracy, 24 V DC supply Voltage and 4-20 mA output complete. Make: Banner Cat Part No. QT50 ULB or equivalent in ABB / E& H / Krohne Marshall 2 Each
19 19 S&F in repairs 80 mm dia Electric motor suitable for actuator complete. Make: Marsh RT Series or equivalent in Ritetork / Rotork 1 Each
20 20 All as per item No. 47 here in above but 100 mm dia. 2 Each
21 21 All as per item No. 47 here in above but 150 mm dia. 2 Each
22 22 All as per item No. 47 here in above but 200/250 mm dia. 1 Each
23 23 S&F in repairs MS spiral gear for gear box or actuator suitable for 80 mm dia butterfly valve complete. Make: Marsh / Ritetork / Rotork 1 Each
24 24 All as per item No. 51 here in above but 100 mm dia. 1 Each
25 25 All as per item No. 51 here in above but 150 mm dia. 1 Each
26 26 All as per item No. 51 here in above but 200/250 mm dia. 1 Each
27 27 S&F in repairs MS sector gear for gear box or actuator suitable for 80 mm dia butterfly valve complete. Make: Marsh / Ritetork / Rotork 1 Each
28 28 All as per item No. 55 here in above but 100 mm dia. 1 Each
29 29 All as per item No. 55 here in above but 150 mm dia. 1 Each
30 30 All as per item No. 55 here in above but 200/250 mm dia. 1 Each
31 31 S&F in repairs 80 mm bore Cast Iron foot valves, flanged type, ISI Marked (flange drilling) complete all as directed. Make: Normex / IVC / Venus / Leader / Kirloskar / Sant / AUDCO\n 1 Each
32 32 All as per item No. 59 here in above but 100 mm bore. 2 Each
33 33 S&F in repair Motorised actuator suitable for 80 mm dia butterfly valve complete. Make: Marsh Cat Part No. or equivalent in Hassel Hoffner / Ritetork (RT Series) 1 Each
34 34 All as per item No. 61 here in above but 100 mm dia. 1 Each
35 35 All as per item No. 61 here in above but 150 mm dia. 1 Each
36 36 All as per item No. 61 here in above but 200 mm dia. 1 Each
37 37 All as per item No. 61 here in above but 250 mm dia. 1 Each
38 38 S&F in repair capacitor & Resistor (RC Circuit) for Actuator suitable for 50 / 80 / 100 / 150 / 200 / 250 / 300 mm dia butterfly valve complete. Make: CTR Cat Part No. MPRC/502 15 Each
39 39 S&F in repair limit switch for Actuator suitable for 50 / 80 / 100 / 150 / 200 / 250 / 300 mm dia butterfly valve complete. Make: Cherry Cat part No D449-Q1RA 10 Each
40 40 S&F in repair top cover for actuator suitable for 50 / 80 / 100 / 150 / 200 / 250 / 300 mm dia butterfly valve complete. 1 Each
41 41 S&F in repair SMPS having input 230 V AC and output 24 V DC complete. Make: NHP Cat Part No. NF824V5ARM or equivalent in Telemehanique 1 Each
42 42 S&F in repair 5 pair 0.5 sqmm armoured communication cable with copper conductor complete. Make: FSC / Polycab / Delton 20 Running Metre
43 43 S&F in repair 2 core 1.5 sqmm armoured cable with copper conductor complete. Make: Polycab / Primecab / Finolex 30 Running Metre
44 44 S&F in repair 4 core 1.5 sqmm armoured cable with copper conductor complete. Make: Polycab / Primecab / Finolex 40 Running Metre
45 45 S&F in repair 6 core 1.5 sqmm armoured cable with copper conductor complete. Make: Polycab / Primecab / Finolex 50 Running Metre
46 46 S&F in repair cable joint kit complete. Make: Clip - Seal or equivalent 2 Each
47 47 Supply and laying 32 mm bore high density polyethylene pipes (HDPE) of pressure rating 6 kgf/cm2 for protection of cable. 50 Running Metre
48 48 S&F MCB SPN 6 Amp 10 kA, 240 V, 50 Hz, AC supply complete. Make: Havells Cat Part No. A9N2P06C or equivalent in Schneider / Legrand 4 Each
49 49 S&F external antenna for PLC to Modem Gain 9db. Make: Pentagon Cat Part No. PSO1GSM/9RM (SMA) or equivalent in Cherry \n 5 Each