Indian Institute Of Astrophysics-IIAP has published Up Gradation Of Building Management Systems At Prof . Mgkm Lab , Crest Campus Of Iia , Hosakote Up Gradation Of Building Management Systems At Prof . Mgkm Lab , Crest Campus Of Iia , Hosakote As Per Attached Rfp. Submission Date for this Tender is 14-12-2020. Building Management System Tenders in CREST Campus, IIA, Hosakote,Bangalore Karnataka. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 04-Dec-2020 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 14-12-2020 |
Name of Work: Upgradation of Building Management Systems installed at Prof.MGKM Lab CREST Hosakote. | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Upgradation of Building Management Systems installed at Prof.MGKM Lab CREST campus of IIA, Hosakote. | |||
2 | 1.01 | Integrator & IP 54 rated wall / Floor mount enclosure Intergator for Integration of VFD's - 9 No's\nSoft Points - 10 Points / VFD, Total - 90 Points\nProtocol - BACnet / MSTP or Modbus, Make: ALC, Model No.LGR-250X1 | Item1 | 1 | Set |
3 | 1.02 | DDC Controller with wall/floor mount enclosure : 16 bit IP Controller with Battery-backed real-time clock;\nShould confirm to BACnet Building Controller (B-BC) Standard Device.\nController must have EIA-485 port for ARCNET 156 Kbps or BACnet MS/TP (9600 baud to 76.8 Kbps)\n EIA-232/485 port* configurable port for BACnet PTP\nController for AHU's - 5 no's, Make: ALC, Model No.BAC net SE Series | Item2 | 1 | set |
4 | 1.03 | DDC panel - 1, IP 54 rated wall / Floor mount type\nenclosure panel, Make and Model: Standard | Item3 | 1 | Set |
5 | 1.04 | DDC Controller with wall/floor mount enclosure : 16 bit IP Controller with Battery-backed real-time clock;\nShould confirm to BACnet Building Controller (B-BC) Standard Device.\nController must have EIA-485 port for ARCNET 156 Kbps or BACnet MS/TP (9600 baud to 76.8 Kbps)\n EIA-232/485 port* configurable port for BACnet PTP\nController for FFU's, Make: ALC, Model: BAC net SE Series | Item4 | 1 | Set |
6 | 1.05 | DDC panel - 2, IP 54 rated wall / floor mount type\nenclosure panel, Make and Model: Standard | Item5 | 1 | Set |
7 | 1.06 | DDC Controller with wall/floor mount enclosure : 16 bit IP Controller with Battery-backed real-time clock;\nShould confirm to BACnet Building Controller (B-BC) Standard Device.\nController must have EIA-485 port for ARCNET 156 Kbps or BACnet MS/TP (9600 baud to 76.8 Kbps)\n EIA-232/485 port* configurable port for BACnet PTP,\nController for AHU's - 2no's, Make: ALC, Model: BAC net SE Series | Item6 | 1 | Set |
8 | 1.07 | DDC Panel-3, IP 54 rated Wall / Floor type enclosure panel, Make and Model Standard | Item7 | 1 | Set |
9 | 1.08 | DDC Controller with wall/floor mount enclosure : 16 bit IP Controller with Battery-backed real-time clock;\nShould confirm to BACnet Building Controller (B-BC) Standard Device.\nController must have EIA-485 port for ARCNET 156 Kbps or BACnet MS/TP (9600 baud to 76.8 Kbps)\n EIA-232/485 port* configurable port for BACnet PTP,\n Controller for Chiller Pumps, Make: ALC, Model: BAC net SE Series | Item8 | 1 | Set |
10 | 1.09 | DDC panel-4, IP 54 rated Wall / Floor type enclosure panel, Make and Model: Standard | Item9 | 1 | Set |
11 | 1.1 | Wiring: Supplying, laying, termination, testing and commissioning of communication cables, 2C X 1.5 Screened Cable, Make and Model: Standard, | Item10 | 300 | Mtrs |
12 | 1.11 | Wiring: Supplying, laying, termination, testing and commissioning of communication cables, 25 mm PVC Conduit, Make and Model: Standard, | Item11 | 600 | Mtrs |
13 | 1.12 | Wiring: Supplying, laying, termination, testing and commissioning of communication cables, CAT 6 Cable, Make and Model: Standard, | Item12 | 300 | Mtrs |
14 | 1.13 | Field Sensors\nCable Type- Temperature sensor ( For AHU CHW Supply and Return )\nQuote for sensor with 100mm probe length of Thermowell and Temperature sensor\nMake :Greystone | Item13 | 10 | No |
15 | 1.14 | Cable Type- Temperature sensor ( For Chiller CHW Supply and Return )\nQuote for sensor with 100mm probe length of Thermowell and Temperature sensor\nMake :Greystone | Item14 | 3 | No |
16 | 1.15 | Cable Type- Temperature sensor ( For Chiller Supply and Return header )\nQuote for sensor with 100mm probe length of Thermowell and Temperature sensor\nMake :Greystone | Item15 | 2 | No |
17 | 1.16 | Temperature and Relative Humidity sensor - Duct Type ( For AHU)\nMake :Greystone | Item16 | 4 | No |
18 | 1.17 | Temperature sensor - Duct Type ( For AHU supply and Return )\nSensor probe length - 1 50 mm\nMake :Greystone | Item17 | 9 | No |
19 | 1.18 | Duct Static pressure sensor (0 to 1000) pascal\nRanges ±1250 / 0-1250 Pa\nMake :Greystone | Item18 | 4 | No |
20 | 1.19 | Temperature and Relative Humidity sensor with Display - Room Type ( For AHU)\nMake :Greystone | Item19 | 4 | No |
21 | 1.2 | Pressure sensor with Display - Room Type (0 to 50)pa\nMake :Greystone | Item20 | 4 | No |
22 | 1.21 | Ambient Temperature and Humidity sensor \nMake :Greystone | Item21 | 1 | No |
23 | 1.22 | Air Differential pressure switch for AHU run status ( 0 to 5) pa\nMake :Greystone | Item22 | 5 | No |
24 | 1.23 | BMS Software & Display Device\nBMS Software for 500 points only, Make: ALC and Model: WC-A + WC Media | Item23 | 1 | No |
25 | 1.24 | SMS Modem, Make and Model: Delmon | Item24 | 1 | No |
26 | 1.25 | Display unit with a 10.9 inch Liquid Retina display, compatible with Wi-fi and with 256 GB of storage ,A14 Bionic chip,Touch ID integrated into the top button, Compatible with both Magic Keyboard and Smart Keyboard, Wi Fi 6 & 4G LTE, 802.11ax Wi-Fi 6; simultaneous dual band (2.4GHz and 5GHz); HT80 with MIMO Bluetooth 5.0 technology, Built-in 28.6-watt-hour rechargeable lithium polymer battery.\nMake: Reputed | Item25 | 1 | No |
27 | 1.26 | Dismantling Work: Dismantiling of existing controllers and panels\n | Item26 | 1 | Lot |
28 | 1.27 | Project Managment, Screen development, graphics development, testing and commissioning charges | Item27 | 1 | Lot |
29 | 1.28 | Installation Cost\n\nAny additional item required for installation may be included in the installation cost. | Item28 | 1 | Lot |