Supply , Installation , Testing And Commissioning Supply , Installation , Testing And Commissioning Of 3 . 3 Kv Ht Panel , 415 Volt Lt Panels , 3 . 3 / 0 . 433 Kv Transformers , 3 . 3 Kv Grade Ht And 1 . 1 Kv Grade Lt Cabling Work And Other Allied , Haldia-West Bengal

Kolkata Port Trust-KoPT has published Supply , Installation , Testing And Commissioning Supply , Installation , Testing And Commissioning Of 3 . 3 Kv Ht Panel , 415 Volt Lt Panels , 3 . 3 / 0 . 433 Kv Transformers , 3 . 3 Kv Grade Ht And 1 . 1 Kv Grade Lt Cabling Work And Other Allied . Submission Date for this Tender is 11-02-2021. Transformer Supply Tenders in Haldia West Bengal. Bidders can get complete Tender details and download the document.




Tender Notice

25992871
Corrigendum : Supply , Installation , Testing And Commissioning Supply , Installation , Testing And Commissioning Of 3 . 3 Kv Ht Panel , 415 Volt Lt Panels , 3 . 3 / 0 . 433 Kv Transformers , 3 . 3 Kv Grade Ht And 1 . 1 Kv Grade Lt Cabling Work And Other Allied
Open Tender
Indian
West Bengal
Haldia
11-02-2021

Tender Details

Supply , Installation , Testing And Commissioning Supply , Installation , Testing And Commissioning Of 3 . 3 Kv Ht Panel , 415 Volt Lt Panels , 3 . 3 / 0 . 433 Kv Transformers , 3 . 3 Kv Grade Ht And 1 . 1 Kv Grade Lt Cabling Work And Other Allied Works For Augmentation Of Lock Sub-Station At Lock Entrance Of Hdc

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 25-Nov-2020 Addendum -I Date 17-12-2020
2 03-Dec-2020 ADDENDUM - II Date 30-12-2020
3 20-Dec-2020 Addendum- III Date 14-01-2021
4 04-Jan-2021 ADDENDUM - IV Date 28-01-2021
5 08-Jan-2021 ADDENDUM -V BOQ 28-01-2021
6 19-Jan-2021 Addendum - VI Fee 11-02-2021

Key Value

Document Fees
INR 2950 /-
EMD
INR 1521752.0 /-
Tender Value
INR 7.60 Crore /-

BOQ Items

Name of Work: Supply, Installation, Testing and Commissioning of 3.3 kV HT Panel, 415 Volt LT Panels, 3.3 / 0.433 kV Transformers, 3.3 kV grade HT & 1.1 kV grade LT cabling work and other allied works for augmentation of Lock Sub-Station at Lock Entrance of Haldia Dock Complex, SMP, Kolkata.
Sl. No. Item Description Unnamed: 2 Quantity Units
1 1 Part A: Sub-station Equipment:-
2 1.01 HT 3.3KV , 1250A VCB Panel :-\nDesign, fabricate, supply, installation, testing and commissioning of indoor HT 3.3KV VCB Panel 1250A, 3 phase, 50HZ, 26.3KA for 3sec. as per the enclosed SLD & Technical Specification(11 panel).\n
3 1.011 Supply 1 set
4 1.012 Installation, testing and commissioning 1 set
5 1.02 HT 3.3KV, 630 A VCB along with Vaccum contractor Panel :-\nDesign, fabricate, supply, installation, testing and commissioning of indoor HT 3.3KV, 630A, 3 phase, 50HZ, 26.3KA for 3sec. as per the enclosed SLD & Technical Specification (4 panel).\n
6 1.021 Supply 2 set
7 1.022 Installation, testing and commissioning 2 set
8 1.03 HT 3.3KV, 630A VCB along with Vaccum contractor Panel :-\nDesign, fabricate, supply, installation, testing and commissioning of indoor HT 3.3KV, 630A, 3 phase, 50HZ, 26.3KA for 3sec. as per TABLE-I & Technical Specification (5 panel).\n
9 1.031 Supply 2 set
10 1.032 Installation, testing and commissioning 2 set
11 1.04 1MVA Distribution Transformer:-\nDesign, Manufacture, supply, installation, testing and commissioning of following 11/0.433 KV Oil type transformers with off circuit tap changer & marshalling box of make as per the Technical Specification.\n
12 1.041 Supply 2 set
13 1.042 Installation, testing and commissioning 2 set
14 1.05 1600A, LT Panel (PCC-1):-\nDesign, Manufacture, Supply, installation ,testing and commissioning of 1600A, 18 ways, LT distribution panel as per TABLE-II & Technical Specifications.\n
15 1.051 Supply 1 set
16 1.052 Installation, testing and commissioning 1 set
17 1.06 800A, LT Panel (PDB- 2A, 2B & 2C ):-\nDesign, Manufacture, Supply, installation ,testing and commissioning of 800A, 24 ways, LT distribution panel as per the enclosed SLD & Technical Specifications.\n
18 1.061 Supply 3 set
19 1.062 Installation, testing and commissioning 3 set
20 1.07 630A, LT Panel (PDB-1 & 3):-\nDesign, Manufacture, Supply, installation ,testing and commissioning of 630A, 24 ways, LT distribution panel as per TABLE-II & Technical Specifications.\n
21 1.071 Supply 2 set
22 1.072 Installation, testing and commissioning 2 set
23 1.08 400A, LT Panel (PDB-4):-\nDesign, Manufacture, Supply, installation ,testing and commissioning of 400A, 14 ways, LT distribution panel as per TABLE-II & Technical Specifications\n
24 1.081 Supply 1 set
25 1.082 Installation, testing and commissioning 1 set
26 1.09 125A, LT Panel (PDB-5 & 6):-\nDesign, Manufacture, Supply, installation ,testing and commissioning of 125A, 8 ways, LT distribution panel as per TABLE-II & Technical Specifications\n
27 1.091 Supply 2 set
28 1.092 Installation, testing and commissioning 2 set
29 1.1 HT Cable:-\nSupply of 3.3 KV(UE), aluminum, XLPE Insulated, PVC Sheathed, armoured, FR, UG cable.\n
30 1.101 Supply of 3.3 KV(UE), 1c x 1000 Sqmm Cable 300 Mtrs.
31 1.102 Supply of 3.3 KV(UE), 3c x 240 Sqmm Cable 2000 Mtrs.
32 1.103 Supply of 3.3 KV(UE), 3c x 150 Sqmm Cable 1500 Mtrs.
33 1.11 Laying, testing and commissioning including end termination of HT Cables:\nLaying, testing and commissioning including end termination of HT Cables from substation to MH Houses etc. Job includes supply and installation of Hume and GI pipe.\n
34 1.1101 By existing RCC trench/Hume pipe/GI Pipe. 2700 Mtrs.
35 1.1102 By excavating trench. 800 Mtrs.
36 1.1103 By removal of paver blocks, excavating trench and refixing of the same after laying. 50 Mtrs.
37 1.1104 By 150mm dia. Hume pipe through excavating. 50 Mtrs.
38 1.1105 By 150NB GI Pipe through excavating 100 Mtrs.
39 1.1106 By 150NB GI Pipe through Boring 100 Mtrs.
40 1.12 St. through & End termination HT Cables:\nSupply, installation ,testing and commissioning of HT straight through and indoor heat shrinkable type end termination kit. Job includes supply and installation of all materials required for execution of the job.\n
41 1.1201 Supply of st. through jointing kit 25 sets
42 1.1202 Installation, testing and commissioning of st. through jointing 25 sets
43 1.1203 Supply of indoor end termination kit 36 sets
44 1.1204 Installation, testing and commissioning of indoor end termina 36 sets
45 1.13 LT Cable:-\nSupply of 1.1 KV Grade, aluminum, XLPE Insulated, PVC\nSheathed, armoured, FR, UG cable.\n
46 1.1301 Supply of 1.1 KV grade, 3.5c x 240 Sqmm Cable 2000 Mtrs.
47 1.1302 Supply of 1.1 KV grade, 3.5c x 150 Sqmm Cable 750 Mtrs.
48 1.1303 Supply of 1.1 KV grade, 3.5c x 50 Sqmm Cable 250 Mtrs.
49 1.1304 Supply of 1.1 KV grade, 1c x 630 Sqmm Cable 500 Mtrs.
50 1.14 Laying, testing and commissioning including end termination of LT Cables:\nLaying, testing, commissioning including end termination of LT Cables from substation to MH Houses, Outgoing feeders etc. Job includes supply and installation of Hume and GI pipe.\n
51 1.1401 By existing RCC trench/Hume pipe/GI Pipe. 2500 Mtrs.
52 1.1402 By excavating trench. 700 Mtrs.
53 1.1403 By removal of paver blocks, excavating trench and refixing of the same after laying. 50 Mtrs.
54 1.1404 By 150mm dia. Hume pipe through excavating. 50 Mtrs.
55 1.1405 By 150NB GI Pipe through excavating 100 Mtrs.
56 1.1406 By 150NB GI Pipe through Boring 100 Mtrs.
57 1.15 St. through of LT Cables:-\nSupply, installation ,testing and commissioning of LT straight through kit. Job includes supply and installation of all materials required for execution of the job.\n
58 1.1501 Supply of st. through jointing kit 36 sets
59 1.1502 Installation, testing and commissioning of st. through jointing 36 sets
60 1.16 Indoor LT APFC Panel for PCC-1:-\nDesign, Supply, installation, testing and commissioning of 400 KVAR, 440V rated indoor LT APFC Panel as per Technical Specification.\n
61 1.1601 Supply 1 No.
62 1.1602 Installation, testing and commissioning 1 No.
63 1.17 Earthing station:-\nProviding earthing system, using size 600 mm X 600 mm X 3.15 mm Copper flat plate buried in ground in a depth of 2m. from ground level with alternate layer of charcoal & salt, including supply & fixing of 50 mm dia perforated GI pipe funneling for watering purpose and construction of masonry pit with metal cover, as per IS: 3043 as detailed in 'Technical Specification'.\n
64 1.1701 Supply 36 sets
65 1.1702 Installation, testing and commissioning 36 sets
66 1.18 Battery charger with batteries:-\nProviding Maintenance Free Lead Acid battery of 15Nos. Of 2Volts each for 30V, 60AH Battery Bank with Float cum-Boast Charger as per Technical specifications.\n
67 1.1801 Supply 5 sets
68 1.1802 Installation, testing and commissioning 5 sets
69 1.19 GI Earth Flat:-\nSupply and Installation of Hot Dip Galvanized (100 micron) flats of size 50 X 6 mm for earthing connections, as per Technical specification.\n
70 1.1901 Supply 600 Mtrs.
71 1.1902 Laying,Installation, testing and commissioning 600 Mtrs.
72 1.2 Tools tackels and safety equipments:-
73 1.2001 Supply & installation of safety equipments like CO2 fire\nextinguishers, First Aid box, etc. as per CEA norms, for all substations.\n 6 Set
74 1.2002 HT (11kV grade) rubber mats [2Mtrs.x 1Mtrs.] 40 Nos.
75 1.2003 Special tool box (Taparia Make) for maintenance of VCB Panels . 1 Set
76 1.2004 Megger 2.5kV Hand operated (0-5000Ohms) 2 Set
77 1.21 Removal / dismantling, loading / unloading, transporting of existing HT BOCB (21Nos.) & LT Panel (07 sets.), HT isolators 06 (nos) & different sizes HT & LT Power Cable from existing sub- station and depositing the same at the store of HDC. 1 LS
78 1.22 Removal / dismantling, loading & unloading, transporting of existing Transformers 3.3KV/0.415kv, 500KVA (02Nos.) and 3.3KV/0.415KV,200KVA (02Nos.)\nOil type from existing sub-station and depositing the same at the store of HDC.\n 1 LS
79 1.23 SCADA System, as per Technical specification.
80 1.2301 Supply 1 Set
81 1.2302 Installation, Testing & Commissioning 1 Set
82 1.24 FO Cable as per Technical specification.
83 1.2401 Supply 1500 Mtrs.
84 1.2402 Installation, Testing & Commissioning through RCC\ntrench\n 1500 Mtrs.
85 2 Part B:- Civil Works
86 2.1 Construction of RCC cable trench with removable top cover size 650mmx650mm as per enclosed drgs. 350 Mtrs.
87 2.2 GI Chequered Plate:-\nSupply and Installation of Hot Dip Galvanized (100 micron) flats of size 6 mm Plate for covering existing cable trench inside sub-station, all machine houses & impounding pump house as per Technical specification. Job includes cutting fabrication of plate as per site condition.\n
88 2.201 Supply 2500 Kgs.
89 2.202 Installation, testing and commissioning 2500 Kgs.
90 2.3 GI Angle & Channel :-\nSupply and Installation of Hot Dip Galvanized (100 micron) Angle and channels of size 6 mm for repairing existing cable trench supports inside & outside sub-station, all machine houses & impounding pump house etc. as per Technical specification. Job includes cutting fabrication as per site condition.\n
91 2.301 Supply 500 Kgs.
92 2.302 Installation, testing and commissioning 500 Kgs.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail