Upgradation Of Transformers At Certain Location And Special Repair To Ht Switch Gear And Allied Works At Electric Installation Under Ge North Patiala Upgradation Of Transformers At Certain Location And Special Repair To Ht Switch Gear And Allied Works At , Patiala-Punjab

Military Engineer Services-MES has published Upgradation Of Transformers At Certain Location And Special Repair To Ht Switch Gear And Allied Works At Electric Installation Under Ge North Patiala Upgradation Of Transformers At Certain Location And Special Repair To Ht Switch Gear And Allied Works At . Submission Date for this Tender is 28-11-2020. Switch Gear Tenders in Patiala Punjab. Bidders can get complete Tender details and download the document.




Tender Notice

25836943
Upgradation Of Transformers At Certain Location And Special Repair To Ht Switch Gear And Allied Works At Electric Installation Under Ge North Patiala Upgradation Of Transformers At Certain Location And Special Repair To Ht Switch Gear And Allied Works At
Open Tender
Indian
Punjab
Patiala
28-11-2020

Tender Details

Upgradation Of Transformers At Certain Location And Special Repair To Ht Switch Gear And Allied Works At Electric Installation Under Ge North Patiala Upgradation Of Transformers At Certain Location And Special Repair To Ht Switch Gear And Allied Works At Electric Installation Under Ge North Patiala

Key Value

Document Fees
INR 1000 /-
EMD
INR 198960.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: UPGRADATION OF CERTAIN TRANSFORMERS AND SPECIAL REPAIR TO HT SWITCH GEAR AND ALLIED WORKS AT ELECTRIC INSTALLATION UNDER GE NORTH PATIALA.
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Schedule 'A'Section-I (EXINTERNAL ELECTRIFICATION WORKS)
2 1.01 Total amount of Sch 'A' Sec I (ExInternal Electrification Works) 1 Lumpsum
3 2 Schedule 'A'Section-II (Misc Items of Works) Note : This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under Col. 5 siginifies this fact only.
4 3 Material and labour for disconnecting of 300 kVA transformer from foundation carefully after taking out necessary electrical connection and depositing to MES store yard all as specified and directed at site. 1 Each Job
5 4 Material and labour for disconnecting of 200 kVA transformer from foundation carefully after taking out necessary electrical connection and depositing to MES store yard including demolition including dismantling 02 Nos stay assembly all as specified and directed at site. 2 Each Job
6 5 Material and labour for disconnecting of 63 kVA transformer from foundation carefully after taking out necessary electrical connection and depositing to MES store yard including demolition including dismantling 02 Nos stay assembly all as specified and directed at site. 1 Each Job
7 6 Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 Sqmm 4 core all as specified and directed.\n 400 Running Metre
8 7 Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 11000 Volts grade with stranded aluminium conductor of size 95 Sqmm 3 core all as specified and directed.\n 1185 Running Metre
9 8 Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 240 Sqmm 3.5 core all as specified and directed.\n 75 Running Metre
10 9 Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 400 Sqmm 3.5 core all as specified and directed.\n 100 Running Metre
11 10 Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 500 Sqmm 3.5 core all as specified and directed.\n 40 Running Metre
12 11 Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 Sqmm 3.5 core all as specified and directed.\n 645 Running Metre
13 12 Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 11000 Volts grade with stranded aluminium conductor of size 120 Sqmm 3.0 core all as specified and directed.\n 1595 Running Metre
14 13 Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 300 Sqmm 3.5 core all as specified and directed.\n 38 Running Metre
15 14 Supply installation, testing and commissioning LT Feeder piller board out door type cubicle panel boardsuitable for 3 phase,4 wire 415 volt 50 hz factory febricated approved CPRI powder coated made out of 3.0 mm thick CRCA sheet and MS angle iron sectiom 40X40X6mm frame with front and back openable double door system with locking arragement louver and air vent gaket for netural flow of air with conopy, inner compartment made out of 2 mm the CRCA sheet duly compartmentalized for each MCCB of incoming and outgoing with lockable arragement with alluminium bus bar three phase and neutral of capacity of 800 amp marked red, yelllow, black and blue inslulators, made of high strength insulated material suitable 1100 voltage all controll PVC wires shall be with 2.5 sq mm multistrand copper conductor and shall be properly bunched, tied, frerruled for proper indication , fixed on PCC foundation complete with following accessories:- Note:- PCC shall be measured and paid separately\n INCOMING:- \n(a) ACB Manual drawout type with microprocessor released of capacity 630 Amps 415 Volts,36KA, 4 pole.-01 No. \nOUT GOING:- \n(a) MCCB 250 Amps microprocessor released based 4 pole 415 Volts, 36 KA -04 Nos (b) Digital type Volt meter 0-500 Voltssquare type with selector switch - 01 No.\n(c) Digital type Ammeter 0-400 Amps square type with selector switch - 01 No. (d) Wiring complete with copper wire of suitable size \n(e) Indicator lamp LED type, set of three marked red, yellow & blue - 01 Set.\n(f) Cable glands brass of suitable size for cable. 2 Each Job
16 15 Supply installation, testing and commissioning LT Feeder piller board out door type cubicle panel boardsuitable for 3 phase,4 wire 415 volt 50 hz factory febricated approved CPRI powder coated made out of 3.0 mm thick CRCA sheet and MS angle iron sectiom 40X40X6mm frame with front and back openable double door system with locking arragement louver and air vent gaket for netural flow of air with conopy, inner compartment made out of 2 mm the CRCA sheet duly compartmentalized for each MCCB of incoming and outgoing with lockable arragement with alluminium bus bar three phase and neutral of capacity of 800 amp marked red, yelllow, black and blue inslulators, made of high strength insulated material suitable 1100 voltage all controll PVC wires shall be with 2.5 sq mm multistrand copper conductor and shall be properly bunched, tied, frerruled for proper indication , fixed on PCC foundation complete with following accessories:- Note:- PCC shall be measured and paid separately\n INCOMING:- \n(a) ACB Manual drawout type with microprocessor released of capacity 630 Amps 415 Volts,36KA, 4 pole.-01 No. \nOUT GOING:- \n(a) MCCB 63 Amps microprocessor released based 4 pole 415 Volts, 16 KA -10 Nos (b) Digital type Volt meter 0-500 Voltssquare type with selector switch - 01 No.\n(c) Digital type Ammeter 0-400 Amps square type with selector switch - 01 No. (d) Wiring complete with copper wire of suitable size \n(e) Indicator lamp LED type, set of three marked red, yellow & blue - 01 Set.\n(f) Cable glands brass of suitable size for cable. 1 Each Job
17 16 Boring of holes under road, pavement, hard standing by trench-less technology using ultrasound technique and necessary machine suitable to pass through 40 mm bore GI tubing and cable etc complete all as specified and directed. 28 Running Metre
18 17 Boring of holes under road, pavement, hard standing by trench-less technology using ultrasound technique and necessary machine suitable to pass through 80 mm bore GI tubing and cable etc complete all as specified and directed. 8 Running Metre
19 18 Boring of holes under road, pavement, hard standing by trench-less technology using ultrasound technique and necessary machine suitable to pass through 100 mm bore GI tubing and cable etc complete all as specified and directed. 33 Running Metre
20 19 S& F Rigid non-metallic PVC conduit 40 mm dia exclusive of boxes (junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc all as specified and directed. 300 Running Metre
21 20 S & F factory made sheet distribution board, protection class IP-42 for multiphase out going suitable for mounting MCCBs as incomer of rating 63 Amp, confirming to relevant IS with minimum 200 Amp copper bus bar ,single metal door including connections with copper thimbles as required,415 Volts AC supply all as specified and as directed. 2 Each
22 21 Cutting of wall/hard standing for laying of cables and making good the existing surface with using PCC type B1 (1:2:4) using 20mm graded aggregate excavation and earth work complete all as specified and directed 30 Running Metre
23 22 LT Air Circuit Breaker 4 Pole, 415V, with Manual Draw out type microprocessor release of capacity 630 Amps,50KA all as specified and directed. 1 Each
24 23 Supply installation, Testing and commissioning LT feeder piller board as per designed and approved by GE outdoor type cubical panel board suitable for 3 phase 4 wire 415 Volts 50 Hz factory fabricated, made of 3.0 mm thick CRCA sheet , CPRI approved and MS angle iron sectiom 40X40X6mm frame with front and back openable double door system with locking arragement louver and air vent gasket for manual flow of air with canopy, inner compartment made out of 2mm thick CRCA sheet duly compartmentalised suitable for ACB capacity 630 Amprs incoming and outgoing with lockable arrangement fixed on PCC foundation complete all as specified and directed.\nNote : PCC shall be measured and paid separately 1 Each Job
25 24 Supply installation of outdoor type cubical panel box, made of 3.0 mm thick CRCA sheet , CPRI approved and MS angle iron sectiom 40X40X6mm frame with front and back openable double door system with locking arragement suitable compartlised for mounting of ACB 800 Amprs 4 pole 415 volt using suitable copper conductor for all necessary control wiring with proper colour coding with following components :- \n(a) Digital type Volt meter 0-500 V with selector switch\n(b) Digital type Ammeter 0-400 Amps with selector switch\n(c) Indicator lamp LED type, set of three marked red, yellow & blue. Note:- Before placing order contractor must obtained panel drawing approval from Engr-in-Charge. 1 Each Job
26 25 M&L for expanded metal cut to length bend to shape required with and annealed miled steel not less than 0.9 mm dia including fixed with galvanised steel stapples or welded with supporting steel members. Weight XPM is not less than 3.15 Kg/Sqm complete all as specified.\nNote:MS work required to fixed XPM mesh shall be measured and paid seperately. 104 Squae Metre
27 26 Material and labour for removing old plaster from transformer foundation carefully after taking out necessary electrical shut down and despersal of removed material as indicated by competent authority all as specified and directed at site. 30 Squae Metre
28 27 Supply installation, testing and commissioning LT Feeder piller board out door type cubicle panel boardsuitable for 3 phase,4 wire 415 volt 50 hz factory febricated approved CPRI powder coated made out of 3.0 mm thick CRCA sheet and MS angle iron sectiom 40X40X6mm frame with front and back openable double door system with locking arragement louver and air vent gaket for netural flow of air with conopy, inner compartment made out of 2 mm the CRCA sheet duly compartmentalized for each MCCB of incoming and outgoing with lockable arragement with alluminium bus bar three phase and neutral of capacity of 800 amp marked red, yelllow, black and blue inslulators, made of high strength insulated material suitable 1100 voltage all controll PVC wires shall be with 2.5 sq mm multistrand copper conductor and shall be properly bunched, tied, frerruled for proper indication , fixed on PCC foundation complete with following accessories:- \n INCOMING:- \n(a) MCCB 315 Amps adjustable type 4 pole 415 Volts,36 KA, 4 pole.-01 No. \nOUT GOING:- \n(a) MCCB 100 Amps with Adujustable type 4 pole 415 Volts, 25 KA -2 Nos (b) MCCB 40 Amps with Adujustable type 4 pole 415 Volts, 16 KA - 4 Nos\n(b) Digital type Volt meter 0-500 Voltssquare type with selector switch - 01 No.\n(c) Digital type Ammeter 0-400 Amps square type with selector switch - 01 No. (d) Wiring complete with copper wire of suitable size \n(e) Indicator lamp LED type, set of three marked red, yellow & blue - 01 Set. (f) Cable glands brass of suitable size for cable.\nNote:- Approval of Engr-In-Charge must be obtained for Panel design/drawing and CPRI approval of manufacturer before placing order. 1 Each Job
29 28 Supply installation, testing and commissioning LT Feeder piller board out door type cubicle panel boardsuitable for 3 phase,4 wire 415 volt 50 hz factory febricated approved CPRI powder coated made out of 3.0 mm thick CRCA sheet and MS angle iron sectiom 40X40X6mm frame with front and back openable double door system with locking arragement louver and air vent gaket for netural flow of air with conopy, inner compartment made out of 2 mm the CRCA sheet duly compartmentalized for each MCCB of incoming and outgoing with lockable arragement with alluminium bus bar three phase and neutral of capacity of 800 amp marked red, yelllow, black and blue inslulators, made of high strength insulated material suitable 1100 voltage all controll PVC wires shall be with 2.5 sq mm multistrand copper conductor and shall be properly bunched, tied, frerruled for proper indication , fixed on PCC foundation complete with following accessories:- \n INCOMING:- \n(a) MCCB 400 Amps microprocessor released 415 Volts,36KA, 4 pole.-01 No. \nOUT GOING:- \n(a) MCCB 250 Amps microprocessor released 4 pole 415 Volts, 35 KA -01Nos (b) MCCB 160 Amps microprocessor released 4 pole 415 Volts, 25 KA -01Nos (c) MCCB 100 Amps with Adujustable type 4 pole 415 Volts, 16 KA - 2 Nos (d) Digital type Volt meter 0-500 Voltssquare type with selector switch - 01 No. (e) Digital type Ammeter 0-400 Amps square type with selector switch - 01 No. (f) Wiring complete with copper wire of suitable size \n(g) Indicator lamp LED type, set of three marked red, yellow & blue - 01 Set. (h) Cable glands brass of suitable size for cable.\nNote:- Approval of Engr-In-Charge must be obtained for Panel design/drawing and CPRI approval of manufacturer before placing order. 1 Each Job
30 29 Supply installation, testing and commissioning LT Feeder piller board out door type cubicle panel boardsuitable for 3 phase,4 wire 415 volt 50 hz factory febricated approved CPRI powder coated made out of 3.0 mm thick CRCA sheet and MS angle iron sectiom 40X40X6mm frame with front and back openable double door system with locking arragement louver and air vent gaket for netural flow of air with conopy, inner compartment made out of 2 mm the CRCA sheet duly compartmentalized for each MCCB of incoming and outgoing with lockable arragement with alluminium bus bar three phase and neutral of capacity of 800 amp marked red, yelllow, black and blue inslulators, made of high strength insulated material suitable 1100 voltage all controll PVC wires shall be with 2.5 sq mm multistrand copper conductor and shall be properly bunched, tied, frerruled for proper indication , fixed on PCC foundation complete with following accessories:- \n INCOMING:- \n(a) MCCB 250 Amps microprocessor released 415 Volts,25KA, 4 pole.-01 No. \nOUT GOING:- \n(a) MCCB 160 Amps microprocessor released 4 pole 415 Volts, 25 KA -01Nos (b) MCCB 100 Amps microprocessor released 4 pole 415 Volts, 25 KA -02Nos (c) MCCB 63 Amps with Adujustable type 4 pole 415 Volts, 16 KA - 2 Nos (d) Digital type Volt meter 0-500 Voltssquare type with selector switch - 01 No. (e) Digital type Ammeter 0-400 Amps square type with selector switch - 01 No. (f) Wiring complete with copper wire of suitable size (g) Indicator lamp LED type, set of three marked red, yellow & blue - 01 Set. (h) Cable glands brass of suitable size for cable.\nNote:- Approval of Engr-In-Charge must be obtained for Panel design/drawing and CPRI approval of manufacturer before placing order. 1 Each Job
31 30 Supply installation, testing and commissioning LT Feeder piller board out door type cubicle panel boardsuitable for 3 phase,4 wire 415 volt 50 hz factory febricated approved CPRI powder coated made out of 3.15 mm thick CRCA sheet and MS angle iron sectiom 40X40X6mm frame with front and back openable double door system with locking arragement louver and air vent gaket for netural flow of air with conopy, inner compartment made out of 2 mm the CRCA sheet duly compartmentalized for each ACB/MCCB of incoming and outgoing with lockable arragement with alluminium bus bar three phase and neutral of capacity of 800 amp marked red, yelllow, black and blue inslulators, made of high strength insulated material suitable 1100 voltage all controll PVC wires shall be with 2.5 sq mm multistrand copper conductor and shall be properly bunched, tied, frerruled for proper indication ,Digital type Volt & Amps meters, selector switch, phase indication lamps complete fixed on PCC foundation complete with following accessories / features all as directed by Engineer in Charge - Note:- PCC shall be measured and paid separately\n INCOMING:- \n(a) ACB 630 Amps, 50 KA, 4 Pole, 415 Volts with microprocessor released type.-01 No. \nOUT GOING:- \n(a) MCCB 400 Amps, 36 KA, 4 Pole, 415 Volts with microprocessor released type.-01 No. (b) MCCB 250 Amps, 36 KA, 4 Pole, 415 Volts with microprocessor released type.-06 No. (c) MCCB 160 Amps, 36 KA, 4 Pole, 415 Volts with microprocessor released type.-02 No. (d) MCCB 100 Amps, 25 KA, 4 Pole, 415 Volts with microprocessor released type.-01 No. 1 Each Job
32 31 S&F 11 KV HT Feeder Piller cubicle outdoor type including aluminium bus bar suitable size complete all as specified and directed by Engineer in Charge. 2 Each
33 32 Supply, install, testing and commissioning HT 11 KV , 3 Phase 50 Cycles, totally enclosed , metal clad with drawable type vacuum circuit breaker AIS panel stand alone type used as incomer having rupturing capacity 350 MVA as per ISO 9001and IS 14001 certification and as per IEC 62271-100-200 with short circuit rating 18.4 KA for 3 Sec having one No 630A horizontal isolation, horizontal draw out type vacuum circuit breaker with copper bus bar of suitable rating , floor mounting , trolley mounted complete with following:-\n(a) Manually & motor operated ( 230V, AC, 50 Hz ) spring charged trip free type incorporating mechanical as well electrical ON/OFF indication “OFF” push button test/ service position limit switches with 5 +5NC breaker auxiliary contacts in service position.\n(b) Epoxy cast wound current transformer (CT) dual range 11 KV of ratio 200-100/5A with digital metering and protection core including necessary control wiring:-\n (i) 15 VA burden for protection ( class 5P 10)\n (ii) 15 VA burden for metering (accuracy class 10)\n(c) Voltage transformer with three Nos , 1 phase 3 limbs connected in star, dual class 11KV/3/110V /3 with draw able type with automatic safety shutters 100 VA burden with primary & secondary fuses (confirming to related IS specification)\n(d) Protection arrangement for the breaker shall comprise of the following :-\n (i) Numerical IDMT relay with shunt trip on 24 V DC, consisting 2 element over current relay with\n setting from 50 to 200% (step of 25%) and one element earth fault relay with setting form 20 to \n 80% ( step of 10%)\n 1 Each
34 32.01 (ii) Trip circuit supervision relay \n (iii) Anti pumping relay RE -300\n (iv) Test terminal block fuses, circuit label, phase indication lamp etc as per standard \n(e) The following meters are to be provided \n (i) Digital voltmeter range 0-12KV with built in selector switch and suitable for 110V AC 96x96 \n Sqmm dial surrounded terminal.\n (ii) Digital Ammeter range 0-1200A with built in selector switch dual graduated scale 96x96 \n Sqmm dial surrounded terminal\n (iii) Suitable for 24V , DC supply, healthy indication lamp and switch. \n (iv) Control : T-N-C (trip neutral and close) breaker control switch with indicating arrangement.\n (v) Danger plate (as per manufacturer instructions)\n (vi) set of circuit breaker ON/OFF/ Auto trip/Spring charger /Trip circuit healthy indicating lamp \n (LED).\n (vii) Anti condensation space heater / thermostat.\n(f) All wiring necessary for the above incl interconnection. The size of the conductor shall not be less than 1.5Sqmm copper wire where required. \n(g) Necessary MS cable box for cable termination at input and output.\n(h) Per pack with charging system. \n\n
35 33 Supply, install, testing and commissioning HT 11 KV , 3 Phase 50 Cycles, totally enclosed , metal clad with drawable type vacuum circuit breaker AIS panel stand alone type used as bus coupler having rupturing capacity 350 MVA as per ISO 9001and IS 14001 certification and as per IEC 62271-100-200 with short circuit rating 18.4 KA for 3 Sec having one No 630A horizontal isolation, horizontal draw out type vacuum circuit breaker with copper bus bar of suitable rating , floor mounting , trolley mounted complete with following:-\n(a) Manually & motor operated ( 230V, AC, 50 Hz ) spring charged trip free type incorporating mechanical as well electrical ON/OFF indication “OFF” push button test/ service position limit switches with 5 +5NC breaker auxiliary contacts in service position.\n(b) Epoxy cast wound current transformer (CT) dual range 11 KV of ratio 200-100/5A with digital metering and protection core including necessary control wiring:-\n (i) 15 VA burden for protection ( class 5P 10)\n (ii) 15 VA burden for metering (accuracy class 10)\n(c) Protection arrangement for the breaker shall comprise of the following :-\n (i) Numerical IDMT relay with shunt trip on 24 V DC, consisting 2 element over current relay with\n setting from 50 to 200% (step of 25%) and one element earth fault relay with setting form 20 to \n 80% ( step of 10%)\n (ii) Trip circuit supervision relay \n (iii) Anti pumping relay RE -300\n (iv) Test terminal block fuses, circuit label, phase indication lamp etc as per standard \n\n 1 Each
36 33.01 (d) The following meters are to be provided \n (i) Digital voltmeter range 0-12KV with built in selector switch and suitable for 110V AC 96x96 \n Sqmm dial surrounded terminal.\n (ii) Digital Ammeter range 0-1200A with built in selector switch dual graduated scale 96x96 \n Sqmm dial surrounded terminal\n (iii) Suitable for 24V , DC supply, healthy indication lamp and switch. \n (iv) Control : T-N-C (trip neutral and close) breaker control switch with indicating arrangement.\n (v) Danger plate (as per manufacturer instructions)\n (vi) set of circuit breaker ON/OFF/Auto trip/Spring charger /Trip circuit healthy indicating lamp LED \n (vii) Anti condensation space heater / thermostat.\n(e) All wiring necessary for the above incl interconnection. The size of the conductor shall not be less than 1.5Sqmm copper wire where required. \n(f) Necessary MS cable box for cable termination at input and output.\n(g) Per pack with charging system\n\n
37 34 Supply, install, testing and commissioning HT 11 KV , 3 Phase 50 Cycles, totally enclosed , metal clad with drawable type vacuum circuit breaker AIS panel stand alone type used as outgoing, having rupturing capacity 350 MVA as per ISO 9001and IS 14001 certification and as per IEC 62271-100-200 with short circuit rating 18.4 KA for 3 Sec having one No 630A horizontal isolation, horizontal draw out type vacuum circuit breaker with copper bus bar of suitable rating , floor mounting , trolley mounted complete with following:-\n(a) Manually & motor operated ( 230V, AC, 50 Hz ) spring charged trip free type incorporating mechanical as well electrical ON/OFF indication “OFF” push button test/ service position limit switches with 5 +5NC breaker auxiliary contacts in service position.\n(b) Epoxy cast wound current transformer (CT) dual range 11 KV of ratio 100-50/5A with digital metering and protection core including necessary control wiring:-\n (i) 15 VA burden for protection ( class 5P 10)\n (ii) 15 VA burden for metering (accuracy class 10)\n(c) Protection arrangement for the breaker shall comprise of the following :-\n (i) Numerical IDMT relay with shunt trip on 24 V DC, consisting 2 element over current relay with\n setting from 50 to 200% (step of 25%) and one element earth fault relay with setting form 20 to \n 80% ( step of 10%)\n (ii) Trip circuit supervision relay \n (iii) Anti pumping relay RE -300\n \n 3 Each Job
38 34.01 (iv) Test terminal block fuses, circuit label, phase indication lamp etc as per standard \n(d) The following meters are to be provided \n (i) Digital voltmeter range 0-12KV with built in selector switch and suitable for 110V AC 96x96 \n Sqmm dial surrounded terminal.\n (ii) Digital Ammeter range 0-1200A with built in selector switch dual graduated scale 96x96 \n Sqmm dial surrounded terminal\n (iii) Suitable for 24V , DC supply, healthy indication lamp and switch. \n (iv) Control : T-N-C (trip neutral and close) breaker control switch with indicating arrangement.\n(v) Danger plate (as per manufacturer instructions)\n (vi) set of circuit breaker ON/OFF/Auto trip/Spring charger /Trip circuit healthy indicating lamp LED\n (vii) Anti condensation space heater / thermostat.\n(e) All wiring necessary for the above incl interconnection. The size of the conductor shall not be less than 1.5Sqmm copper wire where required. \n(f) Necessary MS cable box for cable termination at input and output.\n(g) Per pack with charging system. \n