Military Engineer Services-MES has published Repair/Replacement Of External Electrification , Solar Street Lights , High Mast Light , Security Lights And Certain Internal Electrification Works At Army Area Trichy Under Age ( I ) Trichy. Submission Date for this Tender is 05-11-2020. Electrification Work Tenders in TRICHY Tamil Nadu. Bidders can get complete Tender details and download the document.
Name of Work: REPAIR/REPLACEMENT OF EXTERNAL ELECTRIFICATION, SOLAR STREET LIGHTS, HIGH MAST LIGHT,SECURITY LIGHTS & CERTAIN INTERNAL ELECTRIFICATION WORKS AT ARMY AREA TRICHY UNDER AGE (I) TRICHY | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Taking down carefully existing point wiring (any type viz. aluminum or copper) with wooden batten/surface PVC conduit (with its fittings)/PVC casing-capping or any other type for light, fan, power point (including switch, socket, ceiling rose, etc.) with fitting and fixtures and making good disturbed surface of wall/ceiling to match with existing surface after necessary rewiring complete all as specified and directed. | 124 | EACH POINT | |
2 | 2 | Taking down main switches, DB, steel enclosure with MCB’s any way and rating including wooden board or from steel board and making good disturbed surfaces complete all as specified and as directed. | 7 | EACH | |
3 | 3 | Taking down unserviceable sub main wiring including service connections, including earth wire on wooden batten/ surface conduit/ casing & caping complete with its all accessories including making good disturbed surface to match the existing surface complete all as specified and directed. | 120 | RM | |
4 | 4 | M&L for point wiring using approved colour coding as per IS (Red , Black and Green for single phase circuits),with multistranded copper conductor 1.5 sq mm nominal cross-sectional area, single core, PVC insulated and unsheathed FRLS cable 1100 Volts grade, ISI-694 marked with valid CML No. in and inciuding medium grade, PVC casing caping and accessories on wall/roof/floor etc, ISI marked with mild steel/ pressed steel sunken box (with earth dolly) duly painted with two coats of anti corrosive paint/aiuminium paint over a coat of red oxide primer internally and two coats of black bituminous paint over a coat of red oxide primer externally, covered with 3 mm thick plastic laminated sheet cover for fixing of switches, socket and fan regulators etc, inciuding PVC insulated multistranded copper conductor 1.5 sq mm nominal cross sectional area single core FRLS cable as earth continuity conductor to common earth and connecting to earth duly completed all as specified and directed by Engr-in-charge for the following. | |||
5 | 4.1 | For one light / fan / bell point complete all as specified and directed. | 8 | POINT | |
6 | 4.2 | For 3 pin 5 Amp socket outlet on same board complete all as specified and directed. | 2 | POINT | |
7 | 4.3 | For 3 pin 5 Amp socket outlet on independent board complete all as specified and directed. | 2 | POINT | |
8 | 5 | All as per BOQ item No.4.00 here-in-before, but wiring with 4.0 Sqmm copper cable for 5/15 amp switch socket combination or 3 pin socket out let 15 amp on independent board and provision of 2.5 Sqmm, FRLS insulated multi-stranded single core earth wire for earth continuity, connected to common earth dolly complete all as specified and directed. | 2 | POINT | |
9 | 6 | M&L for point wiring using approved colour coding as per IS (Red , Black and Green for single phase circuits),with multistranded copper conductor 1.5 sq mm nominal cross-sectional area , single core, PVC insulated and unsheathed FRLS cable 1100 Volts grade, ISI-694 marked with valid CML No.in and inciuding medium grade, non metallic PVC conduit and accessories on wall/roof/floor etc, ISI marked suitable for surface conduit wiring with mild steel/pressed steel sunken box (with earth dolly) duly painted with two coats of anti corrosive paint/aiuminium paint over a coat of red oxide primer internally. and two coats of black bituminous paint over a coat of red oxide primer externally,covered with 3 mm thick plastic laminated sheet cover for fixing of switches, socket and fan regulators etc, inciuding PVC insulated multistranded copper conductor 1.5 sq mm nominal cross sectional area single core FRLS cable as earth continuity conductor to common earth and connecting to earth duly completed all as specified and directed for the following:- | |||
10 | 6.1 | For One light/fan/Exhaust fan point controlled by one switch 5 Amp one way complete all as specified and directed. | 65 | POINT | |
11 | 6.2 | For socket outlet 3 pin 5 amps on same board complete all as specified and directed. | 10 | POINT | |
12 | 6.3 | For socket outlet 3pin 5 amps on independent board complete all as specified and directed. | 20 | POINT | |
13 | 7 | All as per item No 6.00 here-in-before but for one socket outlet of 15 Amps fixed on independent board with 4.0 Sqmm multistranded copper conductor wire FRLS PVC insulated and 2.5 Sq mm copper conductor wire FRLS PVC insulated using as earth wire complete all as specified and directed. | 15 | POINT | |
14 | 8 | S&F switch piano type, single pole, one way, 5/6 Amps, 240V, 50Hz, AC, ISI marked, complete all as specified and as directed. | 107 | EACH | |
15 | 9 | S&F switch piano type, single pole, one way, 15 Amps, 240V, 50Hz, AC, ISI marked, complete all as specified and as directed. | 17 | EACH | |
16 | 10 | S&F socket outlet multi purpose 2 in 1, 3 Pin, 5 Amps, 230V, 50Hz AC, ISI marked complete all as specified and as directed. | 34 | EACH | |
17 | 11 | S&F sockets outlet multi purpose, 3 pin, 5 and 15 Amps, flush type, 230V, 50Hz, AC, ISI marked complete all as specified and as directed. | 17 | EACH | |
18 | 12 | S&F Ceiling rose poly carbonate, isolated body, with two to three terminals complete all as specified and as directed. | 80 | EACH | |
19 | 13 | S&F MCB DB sheet metal enclosures, SPN, 230 Volts, 200 amps rated busbar, Double door type complete all as specified and as directed for the follwing:-. \n | |||
20 | 13.1 | For 12 way type | 1 | EACH | |
21 | 13.2 | For 8 way type | 3 | EACH | |
22 | 13.3 | For 4 way type | 2 | EACH | |
23 | 14 | S&F MCB DB sheet metal enclosures, TPN, 4 way, 415 Volts, 200 amps rated busbar, Double door type complete all as specified and as directed. | 1 | EACH | |
24 | 15 | S&F MCB SP, 240 volts,of capacity 5 to 40 amps including connection with suitable size aluminium / copper lugs complete all as specified and directed. | 30 | EACH | |
25 | 16 | S&F MCB SPN, 240 volts,of capacity 6 to 40 amps including connection with suitable size aluminium / copper lugs complete all as specified and directed. | 8 | EACH | |
26 | 17 | S&F Isolator, TPN, 415 volts of capacity 63 amps including connection with suitable size aluminium / copper lugs complete all as specified and directed. | 1 | EACH | |
27 | 18 | S&F LED tube light fittings, 4 feet with fixture 20 watts, 230v, 50Hz, complete fitting including connecting with PVC two core copper conductor cable from ceiling rose to fittings complete all as specified and directed. | 45 | EACH | |
28 | 19 | S&F LED tube light fittings 2 feet with fixture 10 watts, 230v, 50Hz including connecting up with PVC two core copper conductor cable from ceiling rose to fittings complete all as specified and directed. \n | 10 | EACH | |
29 | 20 | S&F in repairs lamp holder, PVC/polycarbonate type with back plate suitable for batten fittings with & including LED lamp white 9 watt, complete all as specified and directed. | 30 | EACH | |
30 | 21 | S&Fin repairs fan regulator stepped ,electronic, flush type (socket type) 240 V, AC, 50 Hz, flush type, ISI marked complete all as specified and as directed. | 25 | EACH | |
31 | 22 | M&L for earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 meter deep below normal ground level, top edge of the plate not less then 1.5M below nominal ground level connected to galvanised earth lead wire 4mm dia by means of bolts and cheek nut and washer of galvanised iron incl GI protection pipe and watering pipe all as shown in electrical plate No 3 of SSR Pt I including connection with main switch board all as specified including taking out old unserviceable earthing from existing location including all excavation and earth work in any type of soil complete all as specified and directed.\nNote : On testing, if the desired earth resistance is not obtained, the earthing shall be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engr-in-Charge.\n | 4 | EACH | |
32 | 23 | Taking down ceiling fan of any type/size and make, disconnecting electrical wire from ceiling rose, removing substances from bearing, bush by using kerosene oil, carrying out fresh lubrication using grease and to make the ceiling fan noise free, for smooth functioning including replacement of worn-out/ unserviceable spares as required, replacement of PVC insulated unsheathed stranded twisted copper conductor cable of size 1.5 Sqmm upto 1.0 Mtr long assembling the repaired ceiling Fan, testing and hanging at position, connection with point wiring & Testing complete all as specified and directed. Note : Replacement of worn out defective/unserviceable spare parts, flexible wire etc/ rewinding of ceiling fan and painting shall be measured and paid separately under relevant item of the schedule. | 130 | EACH JOB | |
33 | 24 | All same as in item No. 23 here in before but for exhaust fan 300 mm sweep complete all as specified and directed. | 10 | EACH | |
34 | 25 | All same as in item No.23 here in before but for exhaust fan 450 / 400mm sweep complete all as specified and directed. | 5 | EACH | |
35 | 26 | All same as in item No. 23 here in before but for wall mounting fan upto 400 mm sweep complete all as specified and directed. | 1 | EACH | |
36 | 27 | Rewinding of the motor of ceiling Fan of any make and Size (1200 mm sweep) with super enameled copper wire of existing gauge to obtain the specified and satisfactory RPM as per manufacturers specification, including replacement of all insulation materials, varnishing heating, drying, assembling of stator & rotor etc including testing complete all as specifed and directed. | 110 | EACH JOB | |
37 | 28 | All as per item No. 27 above but for exhaust fan of any make / type and size 300 mm sweep complete all as specifed and directed. | 10 | EACH JOB | |
38 | 29 | All as per item No.27 above but for exhaust fan of any make / type and size of 450/400 mm sweep complete all as specifed and directed. | 5 | EACH JOB | |
39 | 30 | All as per item No. 27 above but for wall mounted fan of any make/type and of size upto 400 mm sweep complete all as specifed and directed. | 2 | EACH JOB | |
40 | 31 | S&F ball bearing of any size and type suitable for any type/make/size of ceiling fan, to be incorporated against item No.23 above as required complete all as specifed and directed. | 90 | EACH | |
41 | 32 | S&F condenser, oil base type, 440 Volts, Ac, 50 Hz and rated capacity 2.5 MFD to be incorporated against item No.23 above as required complete all as specifed and directed. | 120 | EACH | |
42 | 33 | S&F condenser, oil base type, 440 Volts, Ac, 50 Hz and rated capacity 3.15 MFD to be incorporated against item No.24 above as required complete all as specifed and directed. | 15 | EACH | |
43 | 34 | S&F condenser, oil base type, 440 Volts, Ac, 50 Hz and rated capacity 4 MFD to be incorporated against item No.25 & 26 above as required complete all as specifed and directed. | 1 | EACH | |
44 | 35 | Supply and connecting PVC insulated sheathed twin core round stranded copper conductor flexible cable of size 1.5 Sqmm as required complete all as specifed and directed. | 40 | RM | |
45 | 36 | Supply and connecting PVC insulated sheathed twin core round stranded copper conductor flexible cable of size 2.5 Sqmm as required complete all as specifed and directed. | 30 | RM | |
46 | 37 | Supply only gun metal bush of suitable size for exhaust fan of any type/size as per existing type complete all as specifed and directed. | 10 | EACH | |
47 | 38 | All as per item No. 37 above but suitable for wall mounted fan of any type/size as per existing type complete all as specifed and directed. | 1 | EACH | |
48 | 39 | S&F MS anodized bolts with anodized nuts, spring washers split pin and clamp etc size 50 mm long 10 mm dia half threaded type with split pin hole for hanging of ceiling fan complete all as specified and directed. | 10 | EACH | |
49 | 40 | All as per item No. 39 above but of size 50 mm long and 8 mm dia for ceiling fan down rod & body connection complete all as specified and directed. | 10 | EACH | |
50 | 41 | S&F down rod of suitable size including grommet/ reel type rubber pad complete all as specified and directed. | 10 | EACH | |
51 | 42 | Taking down unserviceable louver shutter and supply & fixing of louver shutter for 300 mm sweep exhaust fan and to be fixed on wall by drilling and grouting of nut bolts complete all as specified and directed. | 5 | EACH | |
52 | 43 | Taking down unserviceable fan blade and supply & fixing of fan blade for 300 mm sweep exhaust fan complete all as specified and directed. | 4 | EACH | |
53 | 44 | S&F in replacement PVC canopy suitable for ceiling fan of any type / make for both end of down rod including complete all as specified and directed. | 10 | EACH SET | |
54 | 45 | Taking out geyser of any make and capacity for necessary repair/ replacement including refixing at its original position after repair with replacement of passivated bolt, nut, washer etc complete all as specified and directed.\n( Note : passivated bolt, nut, bolt and washer etc. measured and paid separately. ) | 6 | EACH | |
55 | 46 | Taking out unserviceable inlet (cold water) connection pipe from Geyser and supply and fixing 45 cm long steel wire reinforced PVC connections with CP brass nuts complete all as specified and directed. | 4 | EACH | |
56 | 47 | All as per item No. 46 above but for outlet (hot water) connection | 4 | EACH | |
57 | 48 | Taking out unserviceable thermostat from Geyser and supply, fixing, connecting and testing thermostat with cutout for setting temperature 0- 90C complete all as specified and directed. | 3 | EACH | |
58 | 49 | Taking out unserviceable indicator lamp from Geyser and supply, fixing and connecting indicator lamp with transparent cover as per existing size & shape complete all as specified and directed. | 2 | EACH | |
59 | 50 | Taking out unserviceable safety valve from Geyser, supply and fixing gun metal safely valve all as per existing complete all as specified and directed. | 1 | EACH | |
60 | 51 | Taking out unserviceable heating element from geyser, supply, fixing, connecting and testing heating element thread/push type as per existing size & shape of capacity 1.5 KW complete all as specified and directed. . | 3 | EACH | |
61 | 52 | All as per item No. 51 above but 2.0 KW complete all as specified and directed. . | 1 | EACH | |
62 | 53 | S&F in repairs ceiling fan blades of 1200 mm sweep made of aluminium with white painted surface for existing size complete all as specified and directed. | 20 | EACH SET | |
63 | 54 | S&F in repairs PVC connector including capacitor holder suitable for ceiling fan 1200mm sweep complete all as specified and directed. | 20 | EACH SET | |
64 | 55 | M&L for sub main wiring with two single core PVC insulated FRLS cable 1100V unsheathed with stranded copper conductor of 6.0 sqmm and drawing into and including 25mm dia rigid non metallic PVC conduit, inclusive of all fittings such as tees, bends, junction boxes, elbows, saddles, pipe hooks, couples, lock outs, etc. and one single core PVC insulated stranded copper conductor of 4.0 sqmm as earth wire complete all as specified and directed.\nNote :\n(i) Two runs of 6.0 sqmm cable, one run of 4.0 sqmm cable of earth continuity conductor & PVC conduit pipe shall be measured as one unit length.\n | 120 | RM | |
65 | 56 | S&F single phase electronic energy meter, phase direct connection type KWH meter, temper proof, plastic body with optical port with box with LCD display as per IS 13779, ISI marked, 10-60 Amps capacity optical communication port complete all as specified and directed. | 5 | EACH | |
66 | 57 | S&F three phase electronic energy meter, phase direct connection type KWH meter, temper proof, plastic body with optical port with box with LCD display as per IS 13779, ISI marked, 10-60 Amps capacity optical communication port complete all as specified and directed. | 1 | EACH | |
67 | 58 | S&F in repairs Energy saving and environmental friendly long life LED street light 25 watt made up of pressure die cast aluminium housing with acrylic cover as diffuser with IP66 protection and Impact resistance of IK07. including brackets made by GI pipe 40 mm bore to required shape with all accessories (ISI marked) complete all as specified & directed. | 6 | Each | |
68 | 59 | Supply and fixing of call bell, 230 V AC, single pole all as specified and directed | 2 | Each | |
69 | 60 | Supply and fixing bell push, flush type, 5 Amp all as specified and directed | 2 | Each | |
70 | 61 | Dismantling desert cooler of any capacity servicing and replacement of tullu pump and repair and rewinding of blower motor any make and Size with super enameled copper wire of existing gauge to obtain the specified and satisfactory RPM as per manufacturers specification, including replacement of all insulation materials, varnishing heating, drying, assembling of stator & rotor etc including testing complete all as specified and directed. | 8 | Each | |
71 | 62 | Excavating in trenches, not exceeding 1.5m wide and not exceeding 1.5m in depth for pole foundation, cable trench, etc and getting out in soft/loose soil complete all as specified and directed. | 170 | CUM | |
72 | 63 | Removing excavated soil not exceeding 50m and depositing where directed. at a level not exceeding 1.5m above the starting point complete all as specified and directed. | 60 | CUM | |
73 | 64 | Returning, filling in excavated approved soil, including spreading, leveling, watering and well ramming in layers not exceeding 25cm each complete all as specified and directed. | 110 | CUM | |
74 | 65 | M&L for sand filling with clean dry fine sand unwashed including gently punning around cables in trenches for cable protection complete all as specified and directed. \n[Note:- Compacted/punned thickness shall be measured & paid] | 50 | CUM | |
75 | 66 | Supply and laying burnt bricks sub class B of old size laid dry in trenches as cable protection all as specified and directed. | 5500 | EACH | |
76 | 67 | Taking down old unserviceable LT cable, supply and Laying XLPE insulated, armoured heavy duty electric cables of following sizes with aluminum conductor, 1100 volt grade in trenches/through pipes/ducts or on poles/walls jointing to O/H conductor, LT panels, main switch with suitable size aluminum lugs and testing complete, all as specified directed by Engineer In charge:-\nNote: Excavation and earth work, sand, pipe and bricks will be measured and paid separately | |||
77 | 67.1 | For cable size 50 sqmm, 3.5 core complete all as specified and directed. | 100 | RM | |
78 | 67.2 | For cable size 25 sqmm, 3.5 core complete all as specified and directed. | 100 | RM | |
79 | 67.3 | For cable size 16 sqmm, 4 core complete all as specified and directed. | 100 | RM | |
80 | 67.4 | For cable size 10 sqmm, 2 core complete all as specified and directed. | 200 | RM | |
81 | 67.5 | For cable size 6 sqmm, 2 core complete all as specified and directed. | 300 | RM | |
82 | 68 | M&L for cutting the existing bituminous road/concrete floors, removing and making good using PCC 1:4:8 to match with the esisting surface all as specified. \nNote:- Cutting of road/concrete work shall be except earth work shall be measured under this item. | 3 | CUM | |
83 | 69 | S&F GI tubing light grade of following size for protection of cable in trenches/on pole complete all as specified and directed. \n | |||
84 | 69.1 | 40 mm bore tubing | 20 | RM | |
85 | 69.2 | 25 mm bore tubing | 30 | RM | |
86 | 70 | S&F bracket made out of 1.5 m long 40 mm bore light grade galvanised iron tubing for fixing light fitting including dismantling taking out old unserviceable complete all as specified and directed. | 5 | EACH | |
87 | 71 | M&L Earthing complete with galvanised iron earth plate electrode 60cmx60cmx3.15mm thick burried directly in ground (Earth pit not less than 2.25 mtr deep below ground level) with top edge of plate not less than 1.5 mtr below normal ground level, connected to and including GI strip 32x6 mm as earth lead by means of bolts, nuts, check nuts and washers of copper/brass including excavation and earth work in any type of soil, PCC pit in cement concrete 1:2:4 type B-1 including necessary form work, precast RCC cover, angle iron frame 40x40x5mm, GI 20mm watering pipe medium grade with funnel, 40 mm GI pipe light grade as protection pipe upto DB, requisite quantity of common salt, charcoal dust including testing of earthing complete all as specified and shown on Electrical Plate No 5 of SSR (Part-I).\nNote : On testing, if the desired earth resistance is not obtained, the earthing shall be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engr-in-Charge.\n | 6 | EACH | |
88 | 72 | S&F LED street light luminaires 48 watts with high power led and unique peanut lens to ensure uniform distrubtion suitable for 40/50mm OD pipe ingress IP 65 protection (ISI marked) and connecting to electric system complete all as specified & directed.\n | 10 | EACH | |
89 | 73 | Dismantling the Solar street lights 15 watts capacity to carryout required repairs and replace the following items, re-assembling after replacing spare parts as mentioned here in after, drain out distilled water and refilling with fresh distilled water complete all as specified & directed. | |||
90 | 73.1 | Supply in replacement of LED light fitting 15 watts operated by DC power supply complete all as specified and as directed. | 12 | EACH | |
91 | 73.2 | Supply in replacement of tubular battery 12 V, 80 AH ccomplete all as specified & directed. | 12 | EACH | |
92 | 73.3 | Supply in replacement of Charge controller 5 Amps complete all as specified & directed. | 12 | EACH | |
93 | 74 | Dehydration of transformer oil (mounted on pole/platform) with the help of filtering and drying plants by mechenical machine of suitable capacity to achive dielectric strength of 50 kv and pouring into transformercomplete all as specified & directed.\nNOTE: a) Filtration plant arrenged by the contractor. (b) Transformer oil for topping up will be paid separately under relevant item. | 245 | LITRES | |
94 | 75 | Supply and topping up transformer oil of dielectric strength 50 KV capacity complete all as specified & directed. | 30 | LITRES | |
95 | 76 | S&F MCB TPN, 415 volts, 10 KA breaking capacity, 'C' curve, of capacity 63 Amps including connection with suitable size aluminium / copper lugs complete all as specified and directed. | 4 | EACH | |
96 | 77 | S&F shackle type, porcelain, vitreous, white, brown or green insulators 90mm diameter and 75mm height, for working pressure 1100 volts including galvanised mild steel spindle, 12mm diameter insulator bolts, washers & nuts 150mm height, suitable for 11000 volt grade HT OH line including taking down of unserviceable insulators complete all as specified and directed. | 2 | EACH | |
97 | 78 | S&F lightening arrestors expulsion type complete with all fitting, transmission class, discharge capacity 65 KA suitable for HT 11 KV with necessary connection and testing including taking down old unserviceable arresters complete all as specified and directed. | 1 | Per set of three | |
98 | 79 | S&F post top lantern in soothing opal finish made up of Polycarbonate, suitable upto 15 W retrofit including LED lamp ( B-22 base) including old unserviceable light fitting complete all as specified and directed.\n | 4 | EACH | |
99 | 80 | S&F LED light fiting 180 watt Energy saving, environmental friendly, long life, secondary optics made in pressure die cast housing & heat sink in aluminium extrusion with IP 66 protection with all fixing arangement, nuts, bolts and washer connecting to electric system , suitable for high mast application, highlighting architectural facade and general purpose lighting complete all as specified. \n | 4 | EACH | |
100 | 81 | S&F MCCB capacity 63 Amps, 16 KA, 04 pole with fixed thermal and magnetic setting complete all as specified and directed.\n | 2 | EACH | |
101 | 82 | S&F MCCB capacity 100 Amps, 25 KA, 04 pole with fixed thermal and magnetic setting complete all as specified and directed.\n | 2 | EACH | |
102 | 83 | Supply in replacement of Kit kat rewirable fuse carrier with base includung extention strip of capacity 320 amps 415 volts 50 Hz complete all as specified and directed. | 1 | EACH | |
103 | 84 | Supply in replacement of Kit kat rewirable fuse carrier with base includung extention strip of capacity 200 amps 415 volts 50 Hz complete all as specified and directed. | 1 | EACH | |
104 | 85 | Supply in replacement of Kit kat rewirable fuse carrier with base includung extention strip of capacity100 amps 415 volts 50 Hz complete all as specified and directed. | 1 | EACH | |
105 | 86 | Supply in replacement of battery 3.8 volt suitable for security light timer complete all as specified and directed. | 5 | EACH | |
106 | 87 | supply in replacement of 3 phase contactor suitable for security light controller as per sample existing model complete all as specified | 2 | EACH | |
107 | 88 | S&F in replacement street light thermoplastic junction box made of thermoplastic IP 65 suitable for 10 sqmm to 25 sqmm cable metric kockouts for cable entry and front hinged shutter having busbar 100 Amps single phase 2 wire system to connect cable of size 10 sq mm including one number MCB SP 6 amps complete all as specified and directed. | 8 | EACH | |
108 | 89 | S&F air termination single pointed aluminium rod 12 mm dia and 300 mm long complete all as specified and directed. | 6 | EACH | |
109 | 90 | S&F test point terminal block made of gun metal or phosphorus bronze size 75x75x25 mm drilled and screwed including 3 Nos 8 mm dia 25 mm long hexgonal head screw complete all as specified and directed. | 4 | EACH | |
110 | 91 | S&F aluminium strips 25x3.15 mm with saddles and fixing screws etc for roof conductors and down conductors above ground complete all as specified and directed. | 60 | RM | |
111 | 92 | S&F GI strips 32mm x 6mm as in earth continuty conductor or main earthing lead fixed on wall or reces or burried in ground or drawn in coduit pipes complete all as specified and directed. | 20 | RM | |
112 | 93 | S&F prestressed cement concrete pole 9.0 mtr long, dimension 102 mm x 172 mm at top and 102 mm x 279 mm at bottom, class 10, fixed in true vertical position including testing complete all as specified and directed. | 3 | EACH | |
113 | 94 | M&L for PCC 1:3:6 type C-2 using 40mm graded stone aggregate in foundations, filling and mass concrete, making pillars for or foundation of poles & stay etc including necessary form work complete all as specified and directed. | 2 | CUM | |
114 | 95 | M&L for PCC 1:3:6 type C1 using 20mm graded for pedestal block including necessary formwork finished fair using extra cement complete all as specified and directed. | 0.5 | CUM | |
115 | 96 | M&L for wiring for security lights from cable junction box to light fittings using two runs of single core 1.5 sqmm and one run of 1.5 sqmm (earth continuty) PVC insulated FRLS cable 1100V unsheathed with stranded copper conductor to be drawn in and including non metallic PVC conduit in surface / recessed complete all as specified and directed. (Note:Two runs of PVC insulated cable with one run of earth wire and one run of conduit including accessories shall be measured as one length) | 80 | RM |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy