Military Engineer Services-MES has published Repairs / Replacement Of External Electrification Lt Distribution System At Pangode Military Station Trivandrum As Per Tender Documents. Submission Date for this Tender is 03-11-2020. Electrification Work Tenders in Trivandrum Kerala. Bidders can get complete Tender details and download the document.
Name of Work: | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Excavation in trenches n.exc 1.5mtr wide and n.exc 1.5mtr in depth and getting out in hard/ dense soil for cable/pipe/poles, trimming the sides forming bottom surface to required levels complete all as specified. | 216 | Cum | |
2 | 2 | All as per item No 1 above but beyond 1.5m depth and n.exc 3 m | 0.3 | Cum | |
3 | 3 | Returning filling in & including spreading leveling watering and well ramming in layers not exc 25C M all as specified. | 123 | Cum | |
4 | 4 | Removing excavated materials (surplus soil) to a distance not exceeding 50m in distance and depositing where directed at level n exc 1.5m above the starting point all as specified and directed. | 93 | Cum | |
5 | 5 | M & L brick common burnt clay sub class `B; lying flat on cable in trenches size of brick 230 x 115 x 75mm all as specified. | 6.9 | Per 1000 Nos | |
6 | 6 | M & L for sand cushoning 80mm thick before laying of cable and 150mm thick on cable after laying in trenches complete all as specified and directed by Engr-in-charge. | 64 | Cum | |
7 | 7 | M & L PCC (1:4:8) type D2 using 40mm graded stone aggregate) as in foundation of poles/stays complete all as specified. | 3 | Cum | |
8 | 8 | M&L PCC 1:3:6 type C2 using 40 mm graded stone aggregates as in foundationof poles complete all as specified and as directed. | 2.6 | Cum | |
9 | 9 | M & L PCC (1:2:4) type B1 using 20mm graded stone aggregate for copping of poles all as specified | 0.45 | Cum | |
10 | 10 | S&Laying cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 150 sqmm 3.5 core | 297 | RM | |
11 | 11 | S&Laying cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 95 sqmm 3.5 core | 50 | RM | |
12 | 12 | S&Laying cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 70 sqmm 3.5 core | 50 | RM | |
13 | 13 | S&Laying cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 50 sqmm 3.5 core | 50 | RM | |
14 | 14 | S&Laying cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 35 sqmm 3.5 core | 450 | RM | |
15 | 15 | S&Laying cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 25 sqmm 3.5 core | 140 | RM | |
16 | 16 | S&Laying cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 16 sqmm 4 core | 475 | RM | |
17 | 17 | Dismantling of old unserviceable PCC poles 9 mtr long complete. | 5 | Each | |
18 | 18 | S & F in replacement prestressed concrete pole 9 Mtr long 102 x 172 mm at top and 102 x 279mm at bottom class-10 all as specified. | 5 | Each | |
19 | 19 | Dismantling stay assembly complete including insulator,stay strand all as specified and directed. | 6 | per set | |
20 | 20 | M &L Stay assembly complete with accessories 16mm Dia Stay rod as shown in electrical plate No. 1 (loop type insulator, stay clamps, excavation and concrete measured separately) | 6 | per set | |
21 | 21 | S & F loop type insulator vitorious porcelain white or brown or green large size with overall dimension 90 x 140mm clearance hole 25mm. | 6 | Each | |
22 | 22 | S & F galvanised stay strand of size 7/3.15mm complete. | 0.23 | Qtl | |
23 | 23 | Dismantling of ACSR conductor of any size from LT OH line complete | 1.3 | Qtl | |
24 | 24 | S & F ACSR conductor sqirrel/weasel/ferret all as specified & directed. | 1.3 | Qtl | |
25 | 25 | Dismantling earth wire and removed from site all as specified. | 0.2 | Qtl | |
26 | 26 | S & F galvanised steel earth wire 4.00mm dia complete all as specified . | 0.2 | Qtl | |
27 | 27 | Restringing ACSR conductor/squirrel/weasel/ferret of conductors 2/5 wires per span of upto 50 RM complete including tightening of conductors all as directed. | 50 | Per Span | |
28 | 28 | Dismantling insulator any type/size complete. | 50 | Each | |
29 | 29 | S & F pin type porcelian & Vitreous white brown or green insulator including one galvanised mild steel spindle two galvanised iron nut 150mm height 150mm dia for 11000 volts complete. | 8 | Each | |
30 | 30 | S & F disc type insulator porcelain vitreous 145mm high and 255mm dia ball & socket type white, green, or brown single disc assembly for tension with tension clamp for conductor working pressure 11000 volts grade complete. | 2 | Each | |
31 | 31 | S & F shackle type porcelain vitreous white or brown green insulator 100 mm height and max dia 115 mm including galvanised mild steel staps, washers, insulators bolts nuts for working pressure 1100 volts complete. | 20 | Each | |
32 | 32 | S & F pin type procelain, vitreous white or brown, green insulator, including one galvanised mild steel spindle two galvanised iron washers and one galvanised iron nut 100mm height 65mm dia for 1100 volts complete. | 20 | Each | |
33 | 33 | Dismantling GI pipe light grade size 50mm dia from trenches poles complete. | 31 | RM | |
34 | 34 | Dismantling GI pipe light grade size 80mm dia from trenches poles complete. | 27 | RM | |
35 | 35 | S & laying GI pipe light grade with all fittings complete fixed to walls/poles laid in trenches for cable protection 50mm dia. | 24 | RM | |
36 | 36 | All as per item No 35 above but 80mm dia complete. | 18 | RM | |
37 | 37 | M & L in replacement for cross arms , supports clamps and back plate, fabricated from structural steel section including nuts bolts washers welding bending cold or hot drilling holes for bolts in any shapes or sizes as indicated, including one coat of primer above two coat of synthetic enammeled paint. | 0.4 | Qtl | |
38 | 38 | M&L in replacement for earthing galvanised steel earth plate electrode 600X600X6.30mm thick burried directly in ground (earth plate not less than 2.25 mtr deep below normal ground level with top edge of the plate less than 1.5 mtr below normal ground level) connected to GI strip 25x4mm by means of bolts, nuts, check nuts, and washers, of galvanised iron or steel including GI pipe light grade 40 mm bore for protection of earth lead,GI funnel and wire mesh etc complete all as shown in Electrical plate no 3 of SSR 2009(part- I)including necessary excavation earth work, form work.earth pit of size 450X450X300 mm of PCC M-15 (Nominal mix)using stone aggregate earth pit cover of PCC and 20 mm bore light grade GI pipe for watering and charcoal dust,common salt, and connected to test point 7.5 mtr from earth pit including testing complete all as specified and as directed. | 16 | Each | |
39 | 39 | M&L cutting/Trimming of tree branches 3 mtr all arround apart from LT O/H line,two pole/ 4 pole structures,substations,cleaning of LT/OH conductor line and removing trimmed tree branches from site all as specified and directed. | 200 | per Span | |
40 | 40 | M & L for replacement of cable jointing kit straight through for earthed grade cable heat shrinkable suitable for 3 core 11 KV XLPE cable size 120-185 Sq mm complete. Make - Rechyem/Denson | 1 | Each | |
41 | 41 | M & L for replacement of cable jointing kit straight through for earthed grade cable heat shrinkable suitable for 3 core 11 KV XLPE cable size 95 Sq mm complete. Make - Rechyem/Denson | 1 | Each | |
42 | 42 | M & L for replacement of cable end termination kit with all accessories for earthed system grade cable heat shrinkable outdoor type suitable for 3 core 11 KV XLPE cable size 120-185 Sq mm complete. Make - Rechyem/Mseal/Danson | 2 | Each | |
43 | 43 | M & L for replacement of cable end termination kit with all accessories for earthed system grade cable heat shrinkable outdoor type suitable for 3 core 11 KV XLPE cable size 95 Sq mm complete. Make - Rechyem/Mseal/Danson | 1 | Each | |
44 | 44 | M & L for replacement of cable jointing kit straight through heat shrinkable type(tubular sleeve version) suitable for LT 1100 volts 3.5/4 core 10-16 sqmm.Make: Reychem RPG | 3 | Each | |
45 | 45 | All as per item No.44 above but 3.5 core 25-50 sqmm. | 4 | Each | |
46 | 46 | All as per item No.44 above but 70-150 Sq mm. | 3 | Each | |
47 | 47 | All as per item No 44 above but 185-300 Sq mm. | 2 | Each | |
48 | 48 | Taking out unserviceable MCCB from existing panel board & Supply and fix new MCCB TPN 100 Amp 16 KA ,ICS=ICU=100% suitable for existing panel board by cutting welding as per site condition complete. | 5 | Each | |
49 | 49 | All as per item No 48 above but 125 Amp 25 KA | 4 | Each | |
50 | 50 | All as per item No 48 above but 200 Amp 25 KA | 2 | Each | |
51 | 51 | All as per item No 48 above but 250 Amp 25 KA | 3 | Each | |
52 | 52 | All as per item No 48 above but 400 Amp 36 KA | 1 | Each | |
53 | 53 | Taking out unserviceable MCB TPN from existing panel board & Supply and fix new MCB TPN 63 Amp 10 KA suitable for existing panel board by cutting welding as per site condition complete. | 10 | Each | |
54 | 54 | S & F seperator/ O/H line spacer for LT O/H line conductor 2 wire/4 wire (separate 2 way and 4 way) complete all as specified. | 30 | Each | |
55 | 55 | Supply & Fix replacement of switch air break gang operated device with drop out fuse tripple pole, mechanically operated mounted on insulator and steel frames vertical/Horizontal with operating mechanism, from ground level of current rating upto 400 Amps complete all as specified. Make:Jaipuria brothers or equivalent | 2 | Each | |
56 | 56 | Supply and fix in repair single pointed air termination aluminium rod, 12 mm dia, 300 mm long all as per specification and upto the satisfaction of Engineer-in-Charge. | 15 | Each | |
57 | 57 | S&F in repair aluminium strip 25mm x 3 mm complete with saddles and fixing screws for fitting the strip for roof conductors and down conductors above ground all as per specification and upto the satisfaction of Engineer-in-Charge.. | 140 | RM | |
58 | 58 | Supply and fix in repair GI strip 25 x 4 mm buried in ground all as per specification and upto the satisfaction of Engineer-in-Charge. | 15 | RM | |
59 | 59 | M&L repair for test point terminal block made of gun metal or phosporus bronze size 75x75x25mm drilled and screwed including 3 Nos 8 mm dia 25 mm long hexagonal head screw all as per specification and upto the satisfaction of Engineer-in-Charge. | 10 | Each | |
60 | 60 | Supply and fix in repair of Danger notice plate 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with FI MS clamps 25x3mm with, bolts and nuts of approved size, for HT, 20 X 15 cm size all as specified and directed. | 5 | Each | |
61 | 61 | M&L for checking out servicibillity and function of air brake switch applying petrolium jelly in all moving contacts and binding of conductor of suitable size at all structures including tightening all connections to lightining arrestor /drop out fuse /insulators complete all as specified and as directed. | 10 | Job | |
62 | 62 | S & F in repair lightening arrestor nonlinear type complete with all fittings transmission class discharge capacity and suitable for 11000 volts complete all as specified and as direcetd. | 4 | Set of three | |
63 | 63 | Removing grass and bushes growing at sub stn and keep the sub stn yard neat and clean complete all as specified and as directed . Note:-Unit rate quotated deemed to include to keep the installation neat and clean through out the period of contract Location S/S No1,2, 3,4,5,6, 7 ,8,9,10 and KV S/S .and NFS sub station (Approximate area 800 sqm) Note:Contractor shall keep all the sub station neat and clean throughout the contract period and each job will be completed once in three month. | 2 | Job |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail