Military Engineer Services-MES has published Repair Renewal Of Submain Db And Internal Electrification To Otm Accn At Sevoke Mil Stn Under Ge Sevoke Road. Submission Date for this Tender is 09-11-2020. Electrification Work Tenders in GE SEVOKE ROAD West Bengal. Bidders can get complete Tender details and download the document.
Name of Work: REPAIR/RENEWAL OF SUB MAIN, DB AND INTERNAL ELECTRIFICATION TO OTM ACCN AT SEVOKE MIL STN UNDER GE SEVOKE ROAD | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Taking down carefully old unserviciable copper /aluminium point wiring (light, fan, socket or power) complete including fittings and fixtures, removing materials to store for keeping in safe custody or for taking credit all as directed making good disturbed surfaces of walls with putty, cement and matching the colour of the surface as per existing. | 1790 | PER POINT | |
2 | 2 | M&L for concealed point wiring with two single core PVC insulated, FRLSH unsheathed, multistranded copper conductor of size 1.5 sqmm and one single core PVC insulated FRLSH unsheathed stranded copper conductor of size 1.50 sqmm green in colour as earth lead in and including PVC rigid conduit (medium grade) with all fittings & accessories including provn of MS sunk terminal box of appropriate size suitable for flush to wall for mounting switch, sockets, fan regulators etc with 3mm thick hylum sheet top cover with screws & cup washers for one light / fan point / call bell complete. . \nNote: Cost of making good the disturbed surfaces (if any) & matching with the existing surface is deemed to be included in the unit quoted rates.\n | 650 | PER POINT | |
3 | 3 | All as per Item Sl No - 02 here in before but for one light point controlled by two 2 way switches complete | 10 | PER POINT | |
4 | 4 | All as per Item Sl No - 02 here in before but for 5 pin, 5/6 A socket point on the independent board complete. | 150 | PER POINT | |
5 | 5 | All as per Item Sl No - 02 here in before but for 5 pin, 5/6 A socket point on the same board complete. | 30 | PER POINT | |
6 | 6 | All as per Item Sl No - 02 here in before but with two single core PVC insulated, unsheathed, multistranded copper conductor of size 2.5 sqmm and one single core PVC insulated unsheathed stranded copper conductor of size 2.5 sqmm green in colour as earth lead for 15/16 A switch-socket point on independent board complete. | 50 | PER POINT | |
7 | 7 | M&L for wiring in existing conduit with two single core PVC insulated, unsheathed, multistranded copper conductor FRLSH of size 1.5 sqmm and one single core PVC insulated unsheathed stranded copper conductor FRLSH of size 1.50 sqmm green in colour as earth lead in and including provn of MS sunk terminal box of appropriate size suitable for flush to wall for mounting switch, sockets, fan regulators etc with 3mm thick hylum sheet top cover with screws & cup washers for one light / fan point / call bell complete including of old unserviceable aluminium/coper wiring from existing concealed conduit all as per specified and directed by Eng-in-charge.\n | 180 | PER POINT | |
8 | 8 | M&L for point wiring with two single core PVC insulated, unsheathed, multistranded copper conductor of size 1.5 sqmm and one single core PVC insulated unsheathed stranded copper conductor of size 1.50 sqmm green in colour as earth lead in and including PVC rigid casing caping (medium grade) with all fittings & accessories including provn of MS sunk terminal box of minimum size 75 x75 mm fixed flush to wall for mounting switch, socket, fan regulator etc with 3mm thick hylum sheet top cover with screws & cup washers for one light / fan point / complete.. \nNOTE : Cost of making good the disturbed surfaces (if any) matching with the existing surface is deemed to be included in the unit quoted rates. | 500 | PER POINT | |
9 | 9 | All as per Item Sl No - 08 here in before but for 5 pin, 5/6 A socket point on the independent board complete. | 150 | PER POINT | |
10 | 10 | All as per Item Sl No - 08 here in before but for 5 pin, 5/6 A socket point on the same board complete. | 20 | PER POINT | |
11 | 11 | All as per Item Sl No - 08 here in before but with two single core PVC insulated, unsheathed, multistranded copper conductor of size 2.5 sqmm and one single core PVC insulated unsheathed stranded copper conductor of size 2.5sqmm green in colour as earth lead for 15/16 A switch-socket point on independent board complete. | 50 | PER POINT | |
12 | 12 | S & F switch piano flush type single, pole one way, 5 Amp complete.\n \n | 1380 | EACH | |
13 | 13 | S&F ceiling rose, surface bakelite 3/2 terminals. | 1510 | EACH | |
14 | 14 | S & F switch socket combination 5 in 1, 5/6A.\n | 300 | EACH | |
15 | 15 | S & F switch socket combination 5 in 1, 15/16A.\n | 100 | EACH | |
16 | 16 | S & F socket outlet 5 in 1,5A.\n | 50 | EACH | |
17 | 17 | S &F electronic step regulator (speed regulation in 5 steps) suitable for ceiling fan 1200/1400mm sweep, 120 watt complete | 150 | EACH | |
18 | 18 | Taking down existing unservisiable FTL light fitting and S&F in repair decorative box type fitting with LED light fitting 9 watt 2 feet Aluminium extruded batten luminaire for 230 volt AC all as directed by EIC. | 100 | EACH | |
19 | 19 | Taking down existing unserviceable FTL light fitting and S&F in repair decorative box type fitting with LED light fitting 20 watt 4 feet Aluminium extruded batten luminaire for 230 volt AC all as directed by EIC. | 1250 | EACH | |
20 | 20 | S & F energy saving surface mounted round decorative LED luminaries 12 W with PDC Aluminium housing, soft moon light effect produced when in operation complete all as specified and directed. | 25 | EACH | |
21 | 21 | Fixing only serviceable light fittings, any type recovered from item no.1 including making necessery end connections with suitable wire all as directed. | 50 | EACH | |
22 | 22 | S&F MCB, DB, TPN, 4 ways double door, IP-42, IK-09 with metal door, 160 Amp rated bus bars, earth bar, neutral links complete including blanking plates as required & fixed flush to wall and making good the disturbed surfaces complete all as specified and as directed including taking down unserviceable one with MCBs complete all as specified and directed. | 10 | EACH | |
23 | 23 | All as per item No. 22 here in before but SPN 12 way complete all as specified and directed. | 10 | EACH | |
24 | 24 | All as per item No. 22 here in before but SPN 8 way complete all as specified and directed. | 8 | EACH | |
25 | 25 | S&F MCB, SP, 10KA, 230V, "C" curve, 06-32 A, ISI Marked complete all as specified and directed. | 96 | EACH | |
26 | 26 | S&F MCB, DP, 10KA, 415V, "C" curve, 06-32 A, ISI Marked complete all as specified and directed. | 20 | EACH | |
27 | 27 | S&F MCB, TPN, 10KA, 440V, "C" curve, 40/63 A, ISI Marked complete all as specified and directed. | 10 | EACH | |
28 | 28 | M&L for submain wiring in and including casing caping (medium grade) with two single core PVC insulated, FRLSH unsheathed, stranded copper conductor of size 6.0 Sqmm and one single core PVC insulated, FRLSH unsheathed solid copper conductor 6.0 Sqmm green in colour as earth lead including taking down old unserviceable aluminium sub-main wiring complete all as specified and directed by Eng-in-Charge. \n | 150 | RM | |
29 | 29 | M&L for submain concealed wiring with two single core PVC insulated, FRLSH unsheathed, stranded copper conductor of size 4.0 Sqmm and one single core PVC insulated, FRLSH unsheathed solid copper conductor 4.0 Sqmm green in colour as earth continuity conductor drawn into and including PVC conduit (medium grade) with all fitting & accessories including taking down old unserviceable sub-main wiring complete all as specified. \n | 150 | RM | |
30 | 30 | M&L for submain wiring in existing conduit with two single core PVC insulated, unsheathed, FRLSH stranded copper conductor of size 6.0 Sqmm and one single core PVC insulated, unsheathed solid copper conductor 6.0 Sqmm green in colour as earth lead in existing cancealed PVC conduit wiring with all fitting & accessories incl taking down old unsv aluminium sub-main wiring from existing concealed conduit complete all as specified and directed by Eng-in-Charge. | 150 | RM | |
31 | 31 | M&L for submain wiring with and including casing caping (medium grade) with two single core PVC insulated, FRLSH unsheathed, stranded copper conductor of size 4.0 Sqmm one single core PVC insulated, FRLSH unsheathed solid copper conductor 4.0 Sqmm and green in colour as earth lead incl taking down old unserviceable aluminium sub-main wiring complete all as specified and directed by Eng-in-Charge. \n | 150 | RM | |
32 | 32 | M&L for earthing complete with galvanized steel earth plate electrode 600x600x 6mm burried directly in ground (in vertical position) earth pit not less then 2.25 mtr below normal ground level with the top edge of the earth plate not less than 1.5 mtr (B.G.L) and connected to galvanized iron earth wire of 4mm dia GI wire with GI protection pipe upto pole junction box by means of bolts, nuts, check nuits, and washer of galvanized iron including PCC (1:2:4) type B1 precast RCC cover slab with suitable handle made of 6 mm round bar, including necessary excavation and earth work in any type of soil, 20 mm dia medIum grade galvanized steel tube for watering with one end fixed with cast iron funnel and wire mess, 15mm bore light grade galvanized steel tubing up to 7.5 mtr lenght for drawing earth lead GI wire protection including common salt, charcoal in alternate layers etc. complete all as shown in EP No. 3 of SSR part 1 and testing on completion including taking out old unsv earthing complete all as specified and directed. | 5 | EACH | |
33 | 33 | Taking down existing unserviceable light fitting and S&F in repair surface mounted square pattern LED luminare 40W, 230 Volts including driver and necessary fixing arrangements complete all as specified and directed | 50 | EACH | |
34 | 34 | Taking down existing unserviceable light fitting and S&F in repair surface mounted square pattern LED luminare 20W, 230 Volts including driver and necessary fixing arrangements complete all as specified and directed | 40 | EACH | |
35 | 35 | S&F energy saving decorative LED bollard with optical diffuser and aluminium reflector 9 W with inbuilt driver including making necessary fixing on PCC foundation and connection arrangements complete all as specified and directed | 25 | EACH | |
36 | 36 | S&F energy saving decorative LED post top lantern with diffuser and painted aluminium deflector 30 W with base including making necessary fixing and connection arrangements complete all as specified and directed | 10 | EACH | |
37 | 37 | S&F in repair exhuast fan AC, single phase, 230/240 V, of size 300 mm Sweep heavy duty steel/aluminium metal body incl making holes on wall & making good the distrubed surfaces with all connecting arrangements complete all as specified and directed. | 10 | EACH |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy