Military Engineer Services-MES has published Repair Replacement Of Lt Cables Panels , Feeder Pillars And Allied Works At Residential And Pxe Tech Area Chandipur. Submission Date for this Tender is 05-11-2020. Electrification Work Tenders in Chandipur Odisha. Bidders can get complete Tender details and download the document.




Tender Notice

25753528
Repair Replacement Of Lt Cables Panels , Feeder Pillars And Allied Works At Residential And Pxe Tech Area Chandipur
Open Tender
Indian
Odisha
Chandipur
05-11-2020

Tender Details

Repair Replacement Of Lt Cables Panels , Feeder Pillars And Allied Works At Residential And Pxe Tech Area Chandipur

Key Value

Document Fees
INR 500 /-
EMD
INR 69000.0 /-
Tender Value
INR 34.50 Lakhs /-

BOQ Items

Name of Work: REPAIR/REPLACEMENT OF LT CABLES PANELS, FEEDER PILLARS AND ALLIED WORKS AT RESIDENTIAL AND PXE TECH AREA CHANDIPUR
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Supply, install, testing & commissioning in repair CPRI approved LT Panel board, Indoor type, floor mounted, CRCA, made of sheet steel, factory made suitable for 415 volt, 3 Ph 4 wire, 50 HZ, AC supply system of size not less than 1800 mm x 1200mm x 500 mm,open on both back and front side having hinges and locking arrangements having busbars chamber with Aluminium bus bars with vertically arranged of 600 Amps rating duly insulated by insulation of RYB colour mounted on porcelain insulators .The panels shall be made out of 3.15 mm thick CRCA Sheet , powder coated based on MS channel for arrangement of foundation nuts , bolts and washers (Make:Universal Switch gear control/C&S/Neptune/Power system & Control). The Panel should be protected with IP 54 in accordance with IEC 60529. The gasket material shall be polyurethane,while the material shall be internally embedded. the Panel should be including with internal wiring with multistranded copper conductor cable of suitable size including lugs and cable gland to incoming and outgoing cable etc and supported on MS angle of size not less than 450 mm long, LED indicating lamps, current transformers, terminal block for cables and including making of suitable size foundations as per manufacturer recommendations and taking down old unserviceable panel /fidder pillars alongwith all accessories all as directed at site and to incorporate the following:- 1 Each Job
2 1.01 Note : (i) Existing all connections to be disconnected from old Panel and reconnected to New Panel complete testing and commissioning etc with all other connected civil works to be included in quoted rate.\n(A) IN COMING\n(i) MCCB four pole 415 Volts AC Supply,DU400N, 400 Amps, thermal magnetic release type 50kA,-01 No with Rotary handle and seperator link Make:- L&T,Cat No:- CM98404OORO or equivalent in Legrand/Schneider.\n(ii) Panel mounted multi function meter Consiting of Volt meter for measuring Voltage (0-500 Volts), Ampere meter for measuring Current(0-500 Amps) and Frequency meter of 50Hz and PF Meters- 01 No.Make-L&T,Cat No-WL411011OOOO or equivalent.\n(B) OUT GOING\n(i) MCCB 4 Pole 415 Volts DU250,36 kA 200 Amp .rating thermal magnetic release type- 03 Nos, Make:- L&T,Cat No:- CM98065OONO or equivalent of Legrand/Schneider\n(ii) MCCB 4 Pole 415 Volts DU250C,25 kA 160 Amp .rating thermal magnetic release type- 02 Nos, Make:- L&T,Cat No:- CM90634OOMO or equivalent of Legrand/Schneider\n(iii) MCCB 4 Pole 415 Volts DU100H,30 kA 63 Amp .rating thermal magnetic release type- 02 Nos, Make:- L&T,Cat No:- CM97933OOH2 or equivalent of Legrand/Schneider\nNote :- All MCCBs should be with rotary handle.
3 2 Supply, install, testing & commissioning in repair CPRI approved LT Panel board , outdoor type, floor mounted, CRCA, made of sheet steel ,factory made suitable for 415 volt, 3 Ph 4 wire, 50 HZ, AC supply system of size not less than 1800 mm x 1200mm x 500 mm,open on both back and front side having hinges and locking arrangements having busbars chamber with Aluminium bus bars with vertically arranged of 400 Amps rating duly insulated by insulation of RYB colour mounted on porcelain insulators .The panels shall be made out of 3.15 mm thick CRCA Sheet , powder coated based on MS channel for arrangement of foundation nuts , bolts and washers (Make:Universal Switch gear control/C&S/Neptune/Power system & Control). The Panel should be protected with IP 54 in accordance with IEC 60529. The gasket material shall be polyurethane,while the material shall be internally embedded. the Panel should be including with internal wiring with multistranded copper conductor cable of suitable size including lugs and cable gland to incoming and outgoing cable etc and supported on MS angle of size not less than 450 mm long, LED indicating lamps, current transformers, terminal block for cables and including making of suitable size foundations as per manufacturer recommendations and taking down old unserviceable panel /fidder pillars alongwith all accessories all as directed at site and to incorporate the following:- 1 Each Job
4 2.01 Note : (i) Existing all connections to be disconnected from old Panel and reconnected to New Panel complete testing and commissioning etc with all other connected civil works to be included in unit of works\n(A) IN COMING\n(i) MCCB 4 Pole 415 Volts, DU250,36 kA 200 Amp.rating thermal magnetic release type - 01 Nos with rotary handle and separator link Make:- L&T,Cat No:- CM98065OONO or equivalent of Legrand/Schneider\n(ii) Panel mounted multi function meter Consiting of Volt meter for measuring Voltage (0-500 Volts), Ampere meter for measuring Current(0-500 Amps) and Frequency meter of 50Hz and PF Meter - 01 No.Make-L&T,Cat No-WL411011OOOO\n(B) OUT GOING\n(i) MCCB four pole 415 Volts AC Supply,DU100H, 100 Amps, thermal magnetic release type 30kA,-01 Nos Rotary handle 2 Nos,Seperator link (Set of 8) 2 Nos.,Make:- L&T,Cat No:- CM97933OOK2 or equivalent of Legrand/Schneider.\n(ii) MCCB 4 Pole 415 Volts ,DU100H,30 kA 63 Amp .rating thermal magnetic release type- 03 Nos, Make:- L&T,Cat No:- CM97933OOH2 or equivalent of Legrand/Schneider\n
5 3 Taking down old Feeder Pillar Box and Fabrication , install, testing & commissioning of CPRI approved LT Feeder Pilar Box , outdoor type, floor mounted, factory made suitable for 415 volt, 3 Ph, 4 wire, 50 HZ, AC supply system of size not less than 1200 mm x 1000mm x 500 mm having busbars chamber with aluminium bus bars of 200 Amps rating duly insulated by insulation of RYB colour mounted on porcelain insulators and indicating lamps.The panels shall be made out of MS Sheet metal enclosures 3.15 mm thick including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable etc supported on MS angle and to be fixed on PCC foundation all as directed at site and to incorporate the following:-\n(A) INCOMMING\n(i) MCCB four pole 415 Volts AC Supply,DU100H, 100 Amps-01 Nos, thermal magnetic release type 30KA, Rotary handle 2 Nos,Seperator link (Set of 8) 2 Nos.,Make:- L&T,Cat No:- CM979OOK2 or equivalent of Legrand/Schneider\n(ii) Panel mounted Digital type,LED display,3phase, Volt meter for measuring Voltage (0-500 Volts)-01 Nos , flush mounting 96x96mm Make- L&T, Cat No- WL132010OOOO\n(iii)Panel mounted Digital type,LED display,3phase, Ampere meter for measuring of Current(0-500 Amps)-01 No, flush mounting 96x96mm Make- L&T, Cat No- WL131010OOOO\n(B) OUTGOING\n(i) MCCB 4 Pole 415 Volts ,DU100H, 30 kA 63 Amp rating thermal magnetic release type-02 Nos, Make:- L&T,Cat No:- CM97933OOH2 or equivalent of Legrand/Schneider \n(ii) MCB (SPN) 40 Amps,'C' Series-02 Nos, Make:- L&T,Cat No:- BB20400C or equivalent of Legrand/Schneider\n 2 Each Job
6 4 Taking down old Feeder Pillar Box and Fabrication, install, testing & commissioning of CPRI approved LT Feeder Pilar Box , outdoor type, floor mounted, factory made suitable for 415 volt, 3 Ph, 4 wire, 50 HZ, AC supply system of size not less than 1200 mm x 1000mm x 500 mm having busbars chamber with aluminiumbus bars of 200 Amps rating duly insulated by insulation of RYB colour mounted on porcelain insulators and indicating lamps .The panels shall be made out of MS Sheet metal enclosures 3.15 mm thick including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable etc all as directed at site and to incorporate the following:-\n(A) INCOMMING\n(i) MCCB four pole 415 Volts AC Supply,DU125H, 125 Amps, thermal magnetic release type 30KA, Rotary handle 2 Nos,Seperator link (Set of 8) 2 Nos.,Make:- L&T,Cat No:- CM90679OOLO or equivalent of Legrand/Schneider- 01 Nos\n(ii) Panel mounted Digital type,LED display,3phase, Volt meter for measuring Voltage (0-500 Volts)-01 Nos , flush mounting 96x96mm Make- L&T, Cat No- WL132010OOOO\n(iii)Panel mounted Digital type,LED display,3phase, Ampere meter for measuring of Current(0-500 Amps)-01 No, flush mounting 96x96mm Make- L&T, Cat No- WL131010OOOO\n(B) OUTGOING\n(i) MCCB four pole 415 Volts AC Supply,DU100H, 100 Amps, thermal magnetic release type 30kA-01 Nos, Rotary handle 2 Nos,Seperator link (Set of 8) 2 Nos.,Make:- L&T,Cat No:- CM97933OOK2 or equivalent of Legrand/Schneider \n(ii) MCCB 4 Pole 415 Volts ,DU100H, 30 kA 63 Amp rating-02 Nos thermal magnetic release type, Make:- L&T,Cat No:- CM97933OOH2 or equivalent of Legrand/Schneider \n(iii) MCB (SPN) 40 Amps,'C' Series-02 Nos, Make:- L&T,Cat No:- BB20400C or equivalent of Legrand/Schneider\n 1 Each Job
7 5 Taking down old Feeder Pillar Box and Fabrication , install, testing & commissioning of CPRI approved LT Feeder Pilar Box , outdoor type, floor mounted, factory made suitable for 415 volt, 3 Ph, 4 wire, 50 HZ, AC supply system of size not less than 900 mm x 600mm x 500 mm having busbars chamber with aluminiumbus bars of 200 Amps rating duly insulated by insulation of RYB colour mounted on porcelain insulators .The panels shall be made out of sheet metal enclosures 3.15 mm thick including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable etc all as directed at site and to incorporate the following:-\n(A) INCOMMING\n(i) MCCB four pole 415 Volts AC Supply,DU100, 63 Amps-01 Nos, thermal magnetic release type 36 KA, Rotary handle 2 Nos,Seperator link (Set of 8) 2 Nos.,Make:- L&T,Cat No:- CM97933OOH2 or equivalent of Legrand/Schneider\n(ii) Panel mounted Digital type,LED display,3phase, Volt meter for measuring Voltage (0-500 Volts)-01 Nos , flush mounting 96x96mm Make- L&T, Cat No- WL132010OOOO\n(iii) Panel mounted Digital type,LED display,3phase, Ampere meter for measuring of Current(0-500 Amps)-01 No, flush mounting 96x96mm Make- L&T, Cat No- WL131010OOOO\n(iv) Rotary handle 1 No,LED indicating Lamp (Red) 240V AC 2 Nos,LED indicating Lamp (Yellow) 240V AC- 2 Nos,LED indicating Lamp (Blue) 240V AC- 2 Nos,Current transformer 200/5A 5 VA -3 Nos, Control fuse with base 2/32A 6 Nos,Terminal Block 35-120 Sq MM 08 Nos.\n(B) OUTGOING\n(i) MCB (SPN) 40 Amps,'C' Series-02 Nos, Make:- L&T,Cat No:- BB20400C or equivalent of Legrand/Schneider\n 1 Each Job
8 6 Supply and fix Bus bar box 4 pole TPN 63 Amps including aluminium busbar and all accessories with MS angle and frames including taking down old unserviceable bus bar box all as specified and directed ,Make- C&S/Havells or Equivalent 2 Each
9 7 Supply and fix Bus bar box 4 pole TPN 100 Amps including aluminium busbar and all accessories with MS angle and frames including taking down old unserviceable bus bar box all as specified and directed ,Make- C&S/Havells or Equivalent 2 Each
10 8 Supply and fix Bus bar box 4 pole TPN 200 Amps including aluminium busbar and all accessories with MS angle and frames including taking down old unserviceable bus bar box all as specified and directed ,Make- C&S/Havells or Equivalent 2 Each
11 9 Repair and maintenance of broken door of LT outdoor feeder pillar box/ LT panel by welding or any other repair work as per site requirement repair/ maintenance of hinges, replacement of locking system and ensure open/close the door smoothly, repair/ maintenance of bus bar if any, replacement of MCBs & MCCBs where necessary , providing all necessary arrangement nut bolt thimbles, lugs ferrules, glands of suitable and replacing the old worn out internal wirings by suitable size of FRLS copper cable complete all as specified and directed( NOTE- The minor Spares like nuts, bolts,screws,washers,Insulation Tapes, Busbar Sleeves used in repair works are included in the scheduled item rates. The spare parts like MCBs,MCCBs etc. will be paid separately ) \n 20 EACH JOB
12 10 M&L for Painting of LT outdoor/indoor Feeder pillar box/ LT panel with two coats of synthetic enamel paint, smoke grey colour (1st quality) over a coat of primer by preparing the surface area by rubbing and scraping old rusted areas and welding/patching with new MS sheet make good as its won position before the 1st coat of complete all as specified and directed. 20 EACH JOB
13 11 Supply& Fixing MCB, SP, 40 Amps, 240 volt, 'C' Series, 10 kA ( Make L&T,Cat No.BB10400C or Standard/ Legrand ). 48 Each
14 12 Supply& Fixing MCB, SP, 6-32 Amps, 240 volt, 'C' Series, 10 kA ( Make L&T,Cat No.BB10320C or Standard/ Legrand ). 48 Each
15 13 Supply & Fixing MCB, SPN.40 Amps rating 240, volt, 'C' series, 10 kA (Make L&T,Cat No.BB20400C or Standard / Legrand ).. 36 Each
16 14 Supply & Fixing MCB, SPN. 6-32 Amps rating 240, volt, 'C' series, 10 kA (Make L&T,Cat No.BB20320C or Standard /Legrand ).. 36 Each
17 15 Supply & Fixing Isolator, TPN,63 Amps rating 240, volt, 'C' series, 10 kA (Make L&T/ Standard /Legrand ) 36 Each
18 16 Supply & Fixing Isolator, TPN,100 Amps rating 240, volt, 'C' series, 10 kA (Make L&T/ Standard / Legrand ) 36 Each
19 17 Supply & Fixing in repairs MCCB of 630 Amps,4 pole ,with Thermal -Magnetic Release , DN3-630D type with breaking capacity Icu at 415 volts AC,50Hz , 36 kA ,including connection and testing complete..(Make/ Model:-L&T,DN3-630D, Cat No . CM94106OOT1OG or equivalent make of Standard / Legrand ). 2 Each
20 18 Supply & Fixing in repairs MCCB of 400 Amps,4 pole ,with Thermal -Magnetic Release , DU400N type with breaking capacity Icu at 415 volts AC,50Hz , 50 kA ,including connection and testing complete..(Make/ Model:-L&T,DU400N, Cat No . CM98404OORO or equivalent make of Standard / Legrand ). 2 Each
21 19 Supply & Fixing in repairs MCCB of 320 Amps,4 pole ,with Thermal -Magnetic Release , DU400N type with breaking capacity Icu at 415 volts AC,50Hz ,50 kA ,including connection and testing complete..(Make/ Model:-L&T,DU400N, Cat No .CM98404OOQO or equivalent make of Standard / Legrand ). 2 Each
22 20 Supply & Fixing in repairs MCCB of 250 Amps,4 pole ,with Thermal -Magnetic Release , DU250 type with breaking capacity Icu at 415 volts AC,50Hz , 36 kA ,including connection and testing complete..(Make/ Model:-L&T,DU250, Cat No . CM98065OOPO or equivalent make of Standard / Legrand ). 3 Each
23 21 Supply & Fixing in repairs MCCB of 200 Amps,4 pole ,with Thermal -Magnetic Release , DU250 type with breaking capacity Icu at 415 volts AC,50Hz , 36 kA ,including connection and testing complete..(Make/ Model:-L&T,DU250, Cat No . CM98065OONO or equivalent make of Standard / Legrand ). 3 Each
24 22 Supply & Fixing in repairs MCCB of 160 Amps,4 pole ,with Thermal -Magnetic Release , DU250 type with breaking capacity Icu at 415 volts AC,50Hz , 36 kA ,including connection and testing complete..(Make/ Model:-L&T,DU250, Cat No . CM98065OOMO or equivalent make of Standard / Legrand ). 2 Each
25 23 Supply & Fixing in repairs MCCB of 125 Amps,4 pole ,with Thermal -Magnetic Release , DU125H type with breaking capacity Icu at 415 volts AC,50Hz , 30 kA ,including connection and testing complete..(Make/ Model:-L&T,DU125H, Cat No . CM90679OOLO or equivalent make of Standard Legrand ). 4 Each
26 24 Supply & Fixing in repairs MCCB of 100 Amps,4 pole ,with Thermal -Magnetic Release , DU100H type with breaking capacity Icu at 415 volts AC,50Hz , 30 kA ,including connection and testing complete..(Make/ Model:-L&T,DU100H, Cat No . CM97933OOK2 or equivalent make of Standard / Legrand ). 6 Each
27 25 Supply & Fixing in repairs MCCB of 63 Amps,4 pole ,with Thermal -Magnetic Release , DU100H type with breaking capacity Icu at 415 volts AC,50Hz , 30 kA ,including connection and testing complete..(Make/ Model:-L&T,DU100H, Cat No . CM97933OOH2 or equivalent make of Standard / Legrand ). 5 Each
28 26 Dismantling, removing of unused old HT.pre-stressed concrete poles/struts/two pole/four pole structure of 11.0 Mtrs.long with connected channel, cross arm, truss and insulators etc of any make, length and types from the site and reuse serviceable PCC pole only and making good disturbed surfaces all as specified and directed. 20 Each
29 27 Dismantling and removing iron angles, cross arms, channel etc of any make and types from the site all as specified and directed 5 Qtl
30 28 Dismantling old ACSR conductor from above unused pole all as specified and directed. 1.5 Qtl
31 29 Refixing serviceable PCC pole as retrieved from item No 26 above and fixing at desired site as specified and directed. Note- foundation PCC and coping shall be measured and paid separately. 4 Each
32 30 Supply,installation/irrection with PCC foundation of Pre-stressed concrete pole, 9.0 Mtrs. Long,102 mmx172 mm at top and 102 mm x 279 mm at bottom, class -10 all as specified and directed. 4 Each Job
33 31 Dismantling,removing of old/unserviceable Cross-arms of M.S. Channels or angle sections etc.complete from LT/HT.PCC/ Tubular poles of 9.0/11.0 Mtrs.long with all acessories all as specified and directed 4 Qtl
34 32 Material, Fabrication and Labour for Cross Arms, bracing,V Arms, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat and two under coat of synthetic enamel paint and incl removing rusted cross arm and clamps complete all as specified. 4 QTL
35 33 Dismantling,removing of old/unserviceable Insulators of any type and sizes from LT/HT.PCC/Tubular poles of 9.0/11.0 Mtrs.long for re-use all as specified and directed 60 Each
36 34 M & L for Pin type, porcelain,vitreous,white,brown or green insulators including one galvanised iron washers and one galvanised iron nut,100 mm height, 65 mm dia for LT 1100 volts grade all as specified and directed. 20 Each
37 35 Supply and Stringing ACSR (Aluminium Conductor Steel Rein - forced) Conductor and incl removing old ACSR conductor complete all as required and directed. 1 QTL
38 36 Dismantling of LT over head lines ACSR conductor & Restringing to the required tension incl. Replacement of worn out ACSR conductor, binding wires, Cross arms, Insulators, Clamps, nuts, bolts and washer etc, Note: ACSR Conductor, ross arms, insulators, clamps, nuts, bolts and washers to be meaasured and paid in respective items. 600 RM
39 37 M & L for Cradles , hexagonal/rectangular,fabricated with galvanised steel wire with 3.15 or 4 mm dia for guarding of LT overhead lines ,1100 volts grade from a safe height and distances on existing cross-arms all as specified and directed. 0.5 QTL
40 38 M & L for providing cement concrete for coping of PCC poles with type C1 ,1:3:6 (20 mm graded aggregates) not less than 60 cm in height all as specified and directed. 0.8 CUM
41 39 M&L for repair of damaged coping of PCC pole by plastering with cement mortar 1:4 and painting with 2 coats of Cement base paint over primer of PCC coping area all as specified and directed. 80 Each
42 40 M&L for cleaning,scrubing and preparation of surfaces of PCC pole and carrying out following phase of work all as directed\n(a) One coat of Cement base paint on all the sides of PCC pole, area above the zebra painting all as specified & directed.\n(b) carrying out painting by synthetic enamel paint one coat over the concrete surface of pole using black and yellow colour paint all as directed including pole coping upto 1.5 mtr and numbering the pole all as specified\n(c) Silver colour spray painting of mild steel bracket, clamps and nut, bolts all as specified and directed. \n. 350 Each Job
43 41 M & L for Stay assebly with stay rod of 16 mm dia complete with accessories as shown in Electrical plate No-1 ( Note- Loop insulators,stay clamps,excavation and concrete will be measured and paid separately in concerned items ) 14 Per Set
44 42 M&L for PCC 1:4:8 type D2, using 40mm graded stone aggregate for foundation,filling and mass concrete of poles 6 CUM
45 43 S&F in repairs for Loop type, porcelain,vitreous,white,brown or green insulators,small size, with overall dimensions 65x90 mm, clearance of hole 16 mm all as specified and directed. 20 Each
46 44 S&F in repairs for Loop type, porcelain,vitreous,white,brown or green insulators,large size, with overall dimensions 90x140 mm, clearance of hole 25.5mm all as specified and directed. 20 Each
47 45 M & L in repaires galvanised steel stay strand / wire of size 7/4.0 mm dia for stay assembly all as specified and directed. 2 QTL
48 46 M & L in replacement of Synthetic insulating mat of size 2mx1mx12mm all as specified and directed. 12 Each
49 47 M & L for standard Earth pit cover of 50mm thick precast RCC (1:1.5:3) type A1 as in cover slab duly reinforced with 8 mm dia TMT bar @ 100 mm c/c both way and two nos lifting handle made out of 10 mm dia TMT bar and set in cement mortar (1:4) complete all as specified in electrical plate No 3 of SSR part-I all as specified and directed. 30 Each
50 48 M & L for Ebonite sheet of 10 mm thick on the top of steel frame or on existing M.S.sheet or frame including necessary cutting, drilling complete used for fixing of MCCBs and switch gears all as specified and directed. 15 SQM
51 49 M&L in repairs test point terminal block made out of gun metal (or) phosphorus bronze size 75x75x25mm drilled and screwed with and including 3 Nos 8mm dia 25mm long hexagonal head screws complete all as directed by Engineer-in-Charge. 12 Each
52 50 S&F in repairs air termination single pointed Aluminium rod 12mm dia 300mm long fixed on GI pipe 40mm bore light grade 1.5mtr long fixed to floor complete all as specified and directed. 20 Each
53 51 S&F in repairs air termination single pointed Copper rod 12mm dia 300mm long fixed on GI pipe 40mm bore light grade 1.5mtr long fixed to floor complete all as specified and directed. 50 Each
54 52 S&F in repairs Lightning conductor strip of size 25 x 3.15 mm with saddles and fixing screws etc. for roof conductors and down conductors above the ground or any other indicated situation for loop lightning conductors from testing point to lightning arrestors etc. as required 25 x 3.15 mm Aluminium strip complete all as specified & directed. 200 RM
55 53 Taking down carefully undergound cables of any sizes for testing, meggering and keeping serviceable cable and cable protection old bricks in safe costody for re-use with making good distubed surfaces,trenches or walls, floors etc complete all as specified & directed . 3000 RM
56 54 Supply and laying XLPE insulated armoured heavy duty cable 1100 volt grade ISI marked with alumimium conductor multi strand cross sectional area 240 Sqmm x 3 1/2 Core complete all as specified and directed by Engr-in-charge..(Make Polycab/Finolex/Glostar) 100 RM
57 55 Supply and laying XLPE insulated armoured heavy duty cable 1100 volt grade ISI marked with alumimium conductor multi strand cross sectional area 150 Sqmm x 3 1/2 Core complete all as specified and directed by Engr-in-charge..(Make Polycab/Finolex/Glostar) 250 RM
58 56 Supply and laying XLPE insulated armoured heavy duty cable 1100 volt grade ISI marked with alumimium conductor multi strand cross sectional area 95 Sqmm x 3 1/2 Core complete all as specified and directed by Engr-in-charge..(Make Polycab/Finolex/Glostar) 150 RM
59 57 Supply and laying XLPE insulated armoured heavy duty cable 1100 volt grade ISI marked with alumimium conductor multi strand cross sectional area 70 Sqmm x 3 1/2 Core complete all as specified and directed by Engr-in-charge..(Make Polycab/Finolex/Glostar) 100 RM
60 58 Supply and laying XLPE insulated armoured heavy duty cable 1100 volt grade ISI marked with alumimium conductor multi strand cross sectional area 50 Sqmm x 3 1/2 Core complete all as specified and directed by Engr-in-charge..(Make Polycab/Finolex/Glostar) 150 RM
61 59 Supply and laying XLPE insulated armoured heavy duty cable 1100 volt grade ISI marked with alumimium conductor multi strand cross sectional area 35 Sqmm x 3 1/2 Core complete all as specified and directed by Engr-in-charge..(Make Polycab/Finolex/Glostar) 150 RM
62 60 Supply and laying XLPE insulated armoured heavy duty cable 1100 volt grade ISI marked with alumimium conductor multi strand cross sectional area 25 Sqmm x 3 1/2 Core complete all as specified and directed by Engr-in-charge..(Make Polycab/Finolex/Glostar) 150 RM
63 61 Supply and laying XLPE insulated armoured heavy duty cable 1100 volt grade ISI marked with alumimium conductor multi strand cross sectional area 16 Sqmm x 4 Core complete all as specified and directed by Engr-in-charge..(Make Polycab/Finolex/Glostar) 100 RM
64 62 Supply and laying XLPE insulated armoured heavy duty cable 1100 volt grade ISI marked with alumimium conductor multi strand cross sectional area 10 Sqmm x 4 Core complete all as specified and directed by Engr-in-charge..(Make Polycab/Finolex/Glostar) 100 RM
65 63 Supply and laying XLPE insulated armoured heavy duty cable 1100 volt grade ISI marked with alumimium conductor multi strand cross sectional area 10 Sqmm x 2 Core complete all as specified and directed by Engr-in-charge..(Make Polycab/Finolex/Glostar) 200 RM
66 64 Supply and laying XLPE insulated armoured heavy duty cable 1100 volt grade ISI marked with alumimium conductor multi strand cross sectional area 6 Sqmm x 4 Core complete all as specified and directed by Engr-in-charge..(Make Polycab/Finolex/Glostar) 100 RM
67 65 Supply and laying XLPE insulated armoured heavy duty cable 1100 volt grade ISI marked with alumimium conductor multi strand cross sectional area 6 Sqmm x 2 Core complete all as specified and directed by Engr-in-charge..(Make Polycab/Finolex/Glostar) 250 RM
68 66 Relying old serviceable cable any size and type as obtained from Ser No-53 above.\nNote :- Earth work to be measured and paid separately. 1200 RM
69 67 Excavation in trenches not exc 1.5m deep and n.exc 1.5m wide and getting out in soft/loose soil for laying of cable all as specified and directed. 485 Cum
70 68 M&L for local sand coushioning with dry and clean over and under the cable for protection of cable , 80 mm sand laid before laying the cable & 150 mm sand after laying the cable and filling the sand in cable duct inside the sub station building complete all as directed 190 Cum
71 69 Returning, filling in, including spreading, leveling watering and well ramming in layer not exceeding 25 Cm. 285 Cum
72 70 Removing of excavated material not exceeding 50 m and depositing where directed at level not exceeding 50 M and depositing where directed at a level not exceeding 1.5 M above the starting point. 200 Cum
73 71 M&L for laying of bricks locally available sub class 'B' bricks (old size) for cable protection cover laid flat and dry in trenches over the cable prependicular to the direction of cable all as directed. 13 Per 1000 Nos
74 72 Re-laying of old serviceable bricks retreived from Sl No.51 here-in before for cable protection cover laid flat and dry in trenches over the cable prependicular to the direction of cable all as directed. 7 Per 1000 Nos
75 73 Supply and laying of GI tubing light grade 40 mm with all fittings laid in trenches/road crossing/along the pole for protection of cable including taking out old GI tubing and making surface in condition all as specified and directed .(Make:- Jindal/Prakash/Tata) 60 RM
76 74 Supply and laying of GI tubing light grade 50 mm with all fittings laid in trenches/road crossing/along the pole for protection of cable including taking out old GI tubing and making surface in good codition all as specified and directed .(Make:- Jindal/Prakash/Tata) 70 RM
77 75 Supply and laying of GI tubing light grade 80 mm with all fittings laid in trenches/road crossing/along the pole for protection of cable including taking out old GI tubing and making surface in good codition all as specified and directed .(Make:- Jindal/Prakash/Tata) 80 RM
78 76 Cutting chases,pinning in,making good of PCC hard standing to facing where required and pointing in cement mortar 1:3 , exc.10 cm. but not exc.20 cm girth to ends or edges of landing,steps,cills,sunshades,shelves,lintels,etc.and cutting chases for concealed water tubing or concealed conduit wiring,laying of cables and making good with old shape and size all as specified and directed. 70 RM
79 77 Cutting Bituminous road in,making good with facing where required and pointing exc.30 cm. but not exc.1.0 mtr. girth to ends or edges of landing,steps,cills,sunshades,shelves,lintels,etc.and cutting chases for concealed water tubing or concealed conduit wiring,laying of cables and making good with old shape and size all as specified and directed. 80 RM
80 78 Repair/maintainace of LT cable faults by disconnecting and taking out old existing defective LT cable of any sizes,in any position from trench/duct, removing/excavating the outer surface of cable, examining cable and joints for defects and ascertaining suitability of cable for reuse, cutting out the defective portion of cable/joint, including taking out old serviceble PCC cable covers/Bricks or GI pipe of any type/sizeand relaying the cable with old bricks after repair/replacement of cable / jointing kit of any make or size of existing then make good the excavated area by returning/filling the same all as directed by the Engineer –in-Charge.( NOTE:- Using of new GI pipe or new jointing kit will be paid separately in concerned items ) 10 Each Job
81 79 Material and labour for heat shrikable type LT Jointing kit for 1.1 KV XLPE cables of size 10-16 sqmm 4 core straight through joint complete including taking down old one. (Make Densons,Item Code-XSSO-2/ Raychem/ 3M) 3 Each
82 80 Material and labour for heat shrikable type LT Jointing kit for 1.1 KV XLPE cables of size 25-50 sqmm 3.5/4 core straight through joint complete including taking down old one. (Make Densons,Item Code-XSSO-3/ Raychem/ 3M) 6 Each
83 81 Material and labour for heat shrikable type LT Jointing kit for 1.1 KV XLPE cables of size 70-150 sqmm 3.5/4 core straight through joint complete including taking down old one. (Make Densons,Item Code-XSSO-4/ Raychem/ 3M) 6 Each
84 82 Material and labour for heat shrikable type LT Jointing kit for 1.1 KV XLPE cables of size 300-400sqmm 3.5/4 core straight through joint complete including taking down old one. (Make Densons,Item Code-XSSO-6/ Raychem/ 3M) 4 Each
85 83 Trimming /cutting of tree branches /bushes obstructing the Street Light Poles/HT/LT lines making clear distance of 2.0 meter upto 5/6 branches at one site for one job from the outer conductors of OH Lines/ poles all around including removing of branches/bushes of trees from site upto 50 Mtrs from the site all as directed. 950 Each Job
86 84 M&L for taking down unserviceable change over switch and supply and fix on load change over switch disconnector confirms to IEC 60947-3, IS/IEC 60947-3, 4 pole, 415 V AC, 800 Amp Type-CO5-800 to mounted in existing LT panel. Cat part No-CO58000OOOO of make-L&T or equivalent in HPL/C&S. 1 Each
87 85 M&L for taking down unserviceable change over switch and supply and fix on load change over switch disconnector confirms to IEC 60947-3, IS/IEC 60947-3, 4 pole, 415 V AC, 630 Amp Type-CO4-630 to mounted in existing LT panel. Cat part No-CO46300OOOO of make-L&T or equivalent in HPL/C&S. 1 Each
88 86 M&L for fixing of 3 phase electric meter boxes on wall/ panel for customised solution including copper cable lugs/thimbles of required size, nut bolt ad washer etc and connection to meter with existing panel complete and taking down existing all as specified and directed. Note:- Existing energy meter is to be used and cable , MCCBs etc to be paid separetely. 10 Each Job
89 87 Supply only Energy meter boxes IP 66 of size 295x583x182 mm wth mounting plate (with transparent lid). Cat part No-KV9331 of Make-HENSEL or equivalent in Sintex/Polycab. 10 Each
90 88 Supply only PVC insulated single core,FRLS,Flexible copper cable of size 10 sqmm, 1100 volt of make-Finolaor equivalent of Polycab/Plaza 100 RM
91 89 Supply only PVC insulated single core,FRLS ,Flexible copper cable of size 25 sqmm, 1100 volt of make-Finolaor equivalent of Polycab/Plaza 25 RM
92 90 Supply only PVC insulated single core,FRLS ,Flexible copper cable of size 35 sqmm, 1100 volt of make-Finolaor equivalent of Polycab/Plaza 60 RM
93 91 M&L Earthing with galvanized steel earth plate electrode of size 60cm x 60cm x 6 mm thick,buried directly in ground(earth pit not less than 2.25 meters deep below ground Level) with top edge of the plate not less than 1.5 meters below normal ground level connected to galvanised iron strip size 25 mm x 4mm as earth lead by means of bolts, nuts, check nuts and washers etc, GI earth lead strip duly protected by 40 mm dia GI pipe (light grade) and 20 MM GI pipe (medium grade) for watering and connected to control switch as directed including necessary earth work in soft/loose soil and disposal of soil to a distance not exceeding 50 Mtrs, PCC (1:3: 6) type C1 as in concrete pit,50mm thick precast RCC (1:1.5:3) type A1 as in cover slab duly reinforced with 8 mm dia TMT bar @ 100 mm c/c both way and two nos lifting handle made cut of 10 mm dia TMT bar and set in cement mortar (1:4), testing etc complete and as specified in electrical plate No 3 of SSR part-I including taking down old earthing plate & strip. 7 Each Job
94 92 M&L Earthing with galvanized steel earth plate electrode of size 60cm x 60cm x 6 mm thick,buried directly in ground(earth pit not less than 2.25 meters deep below ground Level) with top edge of the plate not less than 1.5 meters below normal ground level connected to galvanised iron lead of size 4.0 mm as earth lead by means of bolts, nuts, check nuts and washers etc, GI earth lead duly protected by 20mm dia GI pipe (light grade) and 20 MM GI pipe (medium grade) for watering and connected to control switch as directed including necessary earth work in soft/loose soil and disposal of soil to a distance not exceeding 50 Mtrs, PCC (1:3: 6) type C1 as in concrete pit,50mm thick precast RCC (1:1.5:3) type A1 as in cover slab duly reinforced with 8 mm dia TMT bar @ 100 mm c/c both way and two nos lifting handle made cut of 10 mm dia TMT bar and set in cement mortar (1:4), testing etc complete and as specified in electrical plate No 3 of SSR part-I including taking down old earthing plate & GI lead. 5 Each Job
95 93 S&F in repairs Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 25 x 4 mm galvanised iron strip complete all as specified & directed. 180 RM
96 94 S&F in repairs Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4.0 mm dia galvanised iron lead/wire complete all as specified & directed. 120 RM
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail