Supply Installation Testing And Commissioning Of 1000 Kva/0 . 430 Kva Ht Sub Station Along With Allied Works At Govt . Kashmir Nursing Home , Srinagar, KASHMIR NURSING HOME-Jammu And Kashmir

Public Works Department-PWD has published Supply Installation Testing And Commissioning Of 1000 Kva/0 . 430 Kva Ht Sub Station Along With Allied Works At Govt . Kashmir Nursing Home , Srinagar. Submission Date for this Tender is 06-11-2020. Current Transformer Tenders in KASHMIR NURSING HOME Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

25753218
Corrigendum : Supply Installation Testing And Commissioning Of 1000 Kva/0 . 430 Kva Ht Sub Station Along With Allied Works At Govt . Kashmir Nursing Home , Srinagar
Open Tender
Indian
Jammu And Kashmir
KASHMIR NURSING HOME
06-11-2020

Tender Details

supply installation testing and commissioning of 1000 kva / 0 . 430 kva ht sub station along with allied works at govt . kashmir nursing home , srinagar

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 22-Oct-2020 TECHINICAL Technical Bid 06-11-2020
2 27-Oct-2020 frve4 Financial Bid 06-11-2020

Key Value

Document Fees
INR 1000 /-
EMD
INR 30000.0 /-
Tender Value
INR 15 Lakhs /-

BOQ Items

Name of Work: S.I.T.C of 1000 Kva/0.430 Kv HT Sub Station along with allied works at Govt.Kashmir Nursing Home
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Supply, Installation , Testing and Commissioning of 1000 kVA Transformer, 11/0.433 kV, ONAN Cooled, BIS Level 2 conforming to IS 1180-2014, Three phase Copper Wound with CRGO Core complete with first filling of oil, LT/HT Cable Boxes and Off Circuit Tap Changer. The Transformer to be ISI Marked and as per detailed technical specifications given in Annexure to the tender document 1 Job
2 2 Supply, Erection, Testing and Commissining of Sub Station on 2 Pole Structure with the following items and specifications:\na.Steel Tubular Pole - 9 Meter Long Fitted with base plate and top cover as per IS 410 SP-33 - 2 No.\nb. Set of GI MS Channel fixed with the help of GI/MS Clamps and GI Nuts & Bolts as per the approved drawings of REC/Inspection agencies (Excluding Cost of Material) 1 Set\nc. 11 kV Gang Operated Switch 3 Pole Vertical Type 600 A With Operating Pipe GI B Class 25 mm Dia With Operating Handle Lockable type as per amended IS Standards (Polymer/Porcelain) 1 Set\nD. 11 kV Dropout Fuse Set 3 Pole Vertical Type as per amended updated IS Standards (Polymer/Porcelain) 1 Set\nE.v) Surge Arrestor Station Type Suitable for 11 kV Substation as per IS Specifications amended updated. The test certificate of the company along with the proof of dispatch has to provided before installation of the same (Polymer/Porcelain). Reputed Make 1 Set\nF.vi) Earthing Station with 4 No. GI to Copper 50mm Dia x 3meter Chemical Earthing with Chemical Bags duly drilled as per site requirement, each having earth 1 no. 25mm Dia B Class GI Pipe to be fitted with termination of earthing terminal including cost of earthing chamber as per IS standards. The earthing for Surge Arrestor to be carried through epoxy insulators with the help of GI Clamps and Nuts and Bolts. 1 Job.\nG.Cement Concreting in 1:2:4 for grouting of 2 No. Poles upto ground level and above ground cement pedestal of the same ratio as per requirements. \nH.Spiral Earthing for 2 No. Poles\nI.GI Strip 25 x 5 mm for extension of earthing from earthing station to all equipment. 1 Lot\nJ.Set of Aluminium lugs with ACSR Conductor of required size and lenghth for connecting the accesories on 2 Pole structure. 1 Lot\nK.Painting of 2 Poles with 2 coat Red Oxide Steel Primer and 2 coats silver paint of repued make. 1 Lot\nL. Set of danger plates and anti climbing device. 1 Lot\nNote: Before erection of the structure the approved drawing of the inspection agencies has to be submitted to the authorities and the work has to completed strictly in accordance to the drawings. 1 Job
3 3 Supply, Installation, Testing and commisioning of Disc Insulator with fitting 45 KN suitable for 11 kV as per updated amended IS standard. 3 NO
4 4 Supply, Installation, Testing and commisioning Pin Insulator with hardware fitting suitable for 11 kV as per updated amended IS standards. 3 NO
5 5 Supply, Fabrication, Installation, Testing and Commisioning of Structure for mounting of Transformer made of GI Pipe of required size, MS Channels of sizes, MS Plates/Chequered plates including cost of GI nuts and bolts. The MS part is to be painted with 2 coats Red Oxide Steel Paint and 2 Coat Paint. (The design of the structure as per weight of the Transformer should be submitted before its fabrication). 700 KG
6 6 Providing and laying of cement concreting 1:2:4 for mounting for transformer structure. 2 CUM
7 7 Supply, Design, Installation, Testing & Commissioning at site of metering Unit for 11 KV 3 Phase Trivector Meter, made of MS Sheet steel duly power coated paint. The foundation base is MS Channel used not less than 75 x 40 mm. The Unit is suitable for outdoor as well as indoor as per the site requirement having two chambers, HV chamber and LV chamber,both chambers having one sided hinged door arrangements.The LV chamber has installed Trivector Meter, HV chamber installed CT/PT units and termination of 11 KV cable. the unit is provided port outside the chamber for taking reading manually through CMRI and computer without opening the LV chamber door. The unit have also the sealing arrangement for port. Each panel have the following items:-\n1 Set (3 No) single phase indoor type resin cast current transfomer suitable for 11 KV, metering having required ratio\n1 Set 11 KV / 110 Volt, 3 Phase Potential Transformer Resin Cast.\n1 Set Copper Bus Bar duly insulated by the monoplast tape\n1 Lot of nuts & bolts brass with washers.\n1 Lot of PVC copper wire flexible multistand of required size for secondary connections. For CT wiring the minimum wire size shall be 4mm² (RYB) and for PT wiring minimum wire size shall be 2.5mm² (RYB) \n1 Lot of Copper lugs preferably ring type duly crimped for termination of wire & cables.\nGrounding bus of minimum 40mm copper, 25cm long fixed to the unit in HV chamber.The CTs, PT meter and 11KV cable sheath shall be grounded to the bus through grounding wire (green)\nSupply, Fixing, Testing & Commissioning of HT,Trivector Meter 3 Phase 4 wire -- 5 Amp & -- 110 Volts with RS 45 Port Secure Make.\nSupply, Fabrication & Installation of Pedestal made out of MS channel of size 75 x 40mm or angle iron of size 65 x 65 x 5, duly painted as per site requirement for mounting of metering panel including concrete foundation wherever required including cost of nuts & bolts.\nSupply, Fixing of grounding to the metering unit 40mm GI pipe or 20mm rod, as per drawing. Grounding of metering cubicle through two no 25 x 5mm MS flat iron including cost of cement concreting as per requirement for mounting of Meter Panel\n\n\n\n\n\n\n\n\n 1 Job
8 8 Supply, Laying, Testing and Commisioning of 3 Core 95 sq. mm 11 kV earthed Aluminium Armoured XLPE Cable as per amended updated IS. 20 MTR
9 9 Supply, Laying, Testing and Commisioning of Air Bunched Cable 3 x 95 sq. mm as per amended updated IS. 15 MTR
10 10 Supply, Making, Testing and Commisioning of Cable Termination Kit Heat Shrinkable suitable for 3 x 95 sq. mm Aluminuim Cable XLPE Armoured indoor/outdoor of reputed make. The contractor has to submit the the test certificate of the cable kit before its installation. 5 NO
11 11 Supply, Making, Testing and Commisioning of Cable Termination Kit Heat Shrinkable suitable for Air Bunched Cable 3 x 95 sq. mm Armour outdoor of reputed make. The contractor has to submit the the test certificate of the cable kit before its installation. 2 SET
12 12 Supply,fixing & installation of Manual Drawout type(MDO) Air circuit breaker (ACB) for 1600 amp 3pole 50ka , Ics=Icu=Icw = 50k for 1 sec , microprocessor based released with adjustable short ckt, overload & earth fault protection . The Operational voltage should be 690 v . ACB Should be provided with display for provision of past parameters like fault history. The cost including outdoor type MS Steel Enclosure duly power coated paint made out of 14 SWG, earthing terminal with extension Al. Bus Bar for taking multiple connections for outgoing. The indication lamp LED type to be provided for RYB. 1 Job
13 13 Supply, Laying, Testing and Commisioning of LT Cable Al. Armoured XLPE Single Core 630 sq. mm Cable including cost of cable glands, Al. lugs duly crimped with allied material from Transformer to ACB. Two runs for each phase. 48 MTR
Disclaimer :