Special Repairs And Replacement Of Faulty Underground Lt Cables , Junction Boxes And Allied Accessories For Security Lights Along The Main Approach Roads And Inner Cicrle Roads At Afa Hyderabad, GE (AFA) HYDERABAD-Telangana

Military Engineer Services-MES has published Special Repairs And Replacement Of Faulty Underground Lt Cables , Junction Boxes And Allied Accessories For Security Lights Along The Main Approach Roads And Inner Cicrle Roads At Afa Hyderabad. Submission Date for this Tender is 07-11-2020. Distribution Box Tenders in GE (AFA) HYDERABAD Telangana. Bidders can get complete Tender details and download the document.




Tender Notice

25720612
Special Repairs And Replacement Of Faulty Underground Lt Cables , Junction Boxes And Allied Accessories For Security Lights Along The Main Approach Roads And Inner Cicrle Roads At Afa Hyderabad
Open Tender
Indian
Telangana
GE (AFA) HYDERABAD
07-11-2020

Tender Details

Special Repairs And Replacement Of Faulty Underground Lt Cables , Junction Boxes And Allied Accessories For Security Lights Along The Main Approach Roads And Inner Cicrle Roads At Afa Hyderabad

Key Value

Document Fees
INR 500 /-
EMD
INR 65600.0 /-
Tender Value
INR 32.80 Lakhs /-

BOQ Items

Name of Work : SPECIAL REPAIRS AND REPLACEMENT OF FAULTY UNDERGROUND LT CABLES, JUNCTION BOXES AND ALLIED ACCESSORIES FOR SECURITY LIGHTS ALONG THE MAIN APPROACH ROADS AND INNER CICRLE ROADS AT AFA HYDERABAD
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Excavation in trenches n.exc 1.5m wide and n.exc 1.5 m in depth for laying of cables. Foundation for Feeder Pillars etc n.exc 10 Sqm on plan and getting out in hard/dense soil (including taking out old sands / old bricks) complete all as specified and directed. 580 Cum
2 2 Demolition of plain cement concrete (including cement chequered tiles and bedding) complete all as specified and as directed. 4 Cum
3 3 Taking out old unserviceable cables of following sizes from the existing cable trenches and stacking aside for re-laying at other places or for removal from site complete all as directed by Engineer-in-Charge.
4 3.01 2 Core 10 Sqmm 430 RM
5 3.02 4 Core 10 Sqmm 430 RM
6 3.03 4 Core 16 Sqmm 540 RM
7 3.04 4 Core 25 Sqmm 640 RM
8 3.05 3.5 Core 35 Sqmm 440 RM
9 3.06 3.5 Core 50 Sqmm 350 RM
10 3.07 3.5 Core 70 Sqmm 240 RM
11 4 Horizontal Boring of holes, under road/ pavement / hard standing, not exceeding 20 Metres in length, suitable for passing through for 40 mm bore, galvanised steel tubing complete all as specified and directed.\nNote : GI pipe will be measured and paid seperately under relavent item of BOQ. 30 RM
12 5 S&F Tubes light grade, galvanized,with all fittings, fixed along the poles, under the roads etc. for bore of 40 mm including taking down old pipe complete all as specified and as directed 60 RM
13 6 Supply, laying and testing cable XLPE insulated, screened,PVC bedded,galvanized steel strip or wire armoured, electric power cables(heavy duty)1100 Volts grade with stranded aluminium conductor of size 10 Sqmm 2 core complete all as specified and directed. \n 370 RM
14 7 All as per item No. 6 above but of size 10 Sqmm 4 core -ditto-. 370 RM
15 8 All as per item No. 6 above but of size 16 Sqmm 4 core -ditto-. 450 RM
16 9 All as per item No. 6 above but of size 25 Sqmm 4 core -ditto-. 540 RM
17 10 All as per item No. 6 above but of size 35 Sqmm 3.5 core -ditto- . 350 RM
18 11 All as per item No. 6 above but of size 50 Sqmm 3.5 core-ditto- . 260 RM
19 12 All as per item No. 6 above but of size 70 Sqmm 3.5 core -ditto-. 170 RM
20 13 All as per item No 6 above but except cables -ditto- of the following sizes.\nNote : Cables are obtained from item No-3.01 to 3.07
21 13.01 2 Core 10 Sqmm 60 RM
22 13.02 4 Core 10 Sqmm 60 RM
23 13.03 4 Core 16 Sqmm 90 RM
24 13.04 4 Core 25 Sqmm 100 RM
25 13.05 3.5 Core 35 Sqmm 90 RM
26 13.06 3.5 Core 50 Sqmm 90 RM
27 13.07 3.5 Core 70 Sqmm 70 RM
28 14 Supply & spreading dry river sand in trenches before and after laying of the cables as sand cushioning including gently punning complete all as specified and directed. \nNote : Punned thickness shall be considered for payment purpose. 209 Cum
29 15 Supply and laying sub class 'B' bricks in trenches for cable protection complete all as specified and directed. 18 Per 1000 Nos
30 16 All as per ser item No-15 above but except bricks -ditto-. 4 Per 1000 Nos
31 17 Returning, filling in trenches in hard/dense soil in layers n.exc. 25 cm after laying of cables including spreading, levelling, and well ramming complete all as specified and directed. 324 Cum
32 18 Removing surplus excavated material (soil) to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and as directed 256 Cum
33 19 Supply & Laying Low Density Poly Ethylene (LDPE) flexible pipe of following dia and of pressure rating 6 Kg/cm² laid inside the P.C.C. coping of poles for easy bending and passing of cables complete all as specified and directed.
34 19.01 40 mm dia 250 RM
35 19.02 25 mm dia 150 RM
36 20 S & Fix in repair cable junction box 200 x 160 x 98 mm in size, made out of UV ray protected thermoplastic, having IP 65 protection for outdoor installation fixed with 4 way bakelite cable terminals fixed with steel poles with M.S flat iron clamps, nuts,bolts for terminating 4 core 16 sqmm copper cable complete all as specified and as directed \nMake : HENSEL(Cat No .K 8250) or equivalent in SPELSBERG / RITTAL. 200 Each
37 21 All as per item No.20 above but of size 167 x 125 x 82 mm -ditto-.\nMake : HENSEL (Cat No . K 8100) or equivalent in SPELSBERG / RITTAL. 100 Each
38 22 S & Fix in repair Polymide Cable Gland having Synthetic Light Grey RAL 7035 entry threaded metric with lock nut & one piece sealing ring having sealing range 17.0 mm - 25.00 mm\nMake : HENSEL (Cat No : 1555.32.25) 400 Each
39 23 Supply and fixing in repair astronomical time switch for lighting control on base on sunset/sunrise timming by latitude/ longitude (i.e. On /Off) of capacity 110 - 240 VAC single phase 2W-2 channel 02 NO BASE/DIN complete with necessary electrical connection with MCB-Contactor combination complete all as specified and as directed. \nMake : L& T (Cat No : T2DDT0) or equivallent model in SCHNEIDER /Legrand 6 Each
40 24 Supply and fix in repair astronomical time switch for lighting control on base on sunset/sunrise timming by latitude/ longitude (i.e. On /Off) of capacity 110 - 240 VAC single phase 4W-3 channel 03 NO BASE/DIN complete with necessary electrical connection with the MCB-Contactor combination complete all as specified and as directed. \nMake : L& T (Cat No : T3DDT0) or equivallent model in SCHNEIDER /Legrand 10 Each
41 25 M & L PCC (1:3:6) type C2 (using 40 mm graded stone aggregate) as in foot path complete all as specified and directed. 4 Cum
42 26 M&L Chequered cement concrete tiles 20 cm x 20 cm x 25 mm thick, set,jointed and pointed in neat cement grey with white cement and pigment in foot paths over and including 15mm thick screed bed in CM 1:6 complete all as specified and as directed. 80 Sqm
43 27 M&L for earthing complete with Galvanised steel earth plate eletrode 600 mm x 600 mm x 6 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below GL) with top edge of earth plate not less than 1.5 Mtr below normal ground level, earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common salt filled in alternate layers and electrode connections by using Galvanised iron 32 x 6 mm strip connected by means of bolts, nuts, check nuts and washer of galvanised iron or steel, provision of 40mm dia GI pipe medium grade for protection of GI earth strip and 20mm dia GI pipe medium grade for watering arrangement and PCC (1:3:6) type C1 chamber of size 45cm X 45cm X 45cm including, MS funnel, wire mesh, 50 mm thick RCC 1:2:4 type B1 earth pit cover with 6 Nos, 8 mm dia high strength deformed steel TMT bars on both ways including necessary excavation in any type of soil, returning, filling in, removal of surplus soil to distance n exc 50 mtr, provision of charcoal and salt complete all as shown in electrical plate No 3 of schedule Part-I. Including removing existing old rusted plate romoving from site. 20 Each Job
44 28 Supply and fix in repair cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 10 to 16 sqmm,Indoor/Outdoor type. \nMake:- 3M Cat No MHSX1.1KV (HSLA-1/4C) Or in equivalent in M seal etc 10 Each
45 29 Supply and fix in repair cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 25 to 50 sqmm,Indoor/Outdoor type. \nMake:- 3M Cat No MHSX1.1KV (HSLA-2/4C) Or in equivalent in M seal etc 10 Each
46 30 Supply and fix in repair cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 70 to 95 sqmm,Indoor/Outdoor type. \nMake:- 3M Cat No MHSX1.1KV (HSLA-3/4C) Or in equivalent in M seal etc 4 Each
47 31 Design, supply, erection, testing and commissioning of outdoor type LT feeder pillar box of suitable size platform mounted (to be mounted on the P.C.C. pedestal), suitable for 3 phase 4 wire, 415 volts AC supply and having 4 Nos Aluminium bus bars of rating 150 amps, Spreader link to incoming MCCB for termination of incoming cable and 4 way ebonite cable connector for outgoing cables, duly fabricated in a CPRI approved / certified factory having modern fabrication and testing facility which includes atleast seven (07) tanks pre treatment facility comprising of de-greasing, rinsing, de-rusting, rinsing, phosphating, rinsing and passivation followed by powder coated painting (thickness not less than 80 Micron) with approved shade of RAL 7032. The feeder pillar shall be provided with suitable Neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-55 and general construction conforming to IS : 13947. The feeder pillar shall be made out of 3.00mm thick CRCA mild steel sheet and 3.00mm thick gland plate and having front opening facility (with double layer shutter)and rear opening facility with single layer shutter with locking facility and 2 side slanting canopy type roof on top and mild steel angle (50x50x5mm) legs of length 30 cm at bottom, suitable for mounting on the pedestal, The feeder pillar shall be provided with ventilation facility in the form of louvers for better heat dissipation and including platform earth work, brick work, PCC work complete. Including dismentaling of existing UNSV Lt feeder pillar from site. The feeder pillar shall be comprising of the followings :- 6 Each Job
48 31.01 MCCB, 4 Pole, 63 Amps, Breaking Capacity 16 KA, Adjustable type (100% - 80%) - 01 No. (Incoming)
49 31.02 C.T having Ratio 100/5, tape wound,BPL, rated burden 5 VA-03 Nos.
50 31.03 Digital Volt Meter (96mm x 96mm), 4 1/2 digit, Accuracy Class 1% & Volt meter selector switch (6 Amps), 3 position with "OFF"-01 Each.
51 31.04 Digital Ammeter (96mm x 96mm), 4 1/2 digit, Accuracy Class 1% & Ammeter selector switch (6 Amps), 3 position with "OFF" - 01 Each.
52 31.05 LED Phase Indicating light, shrouded type, 22mm, with cluster LED (RED,YELLOW & BLUE) - 01 set
53 31.06 MCB SPN 20 Amps, 240 V, 50 Hz, AC - 03 Nos
54 31.07 Analog type 1 module time switch suitable for 230 volt AC 50 Hz supply suitable for 16 Amps rating.
55 31.08 Power contactor 3 Phase 40 Amps, with 02 Nos NO & NC auxiliary contacts 415 V, with No volt coil of voltage grade 240 V AC - 01 Nos
56 31.09 Aluminium Earth busbar (25mm x 4mm) for terminating 02 Nos earthing conductor strips - 01 No
57 32 Design, supply, erection, testing and commissioning of outdoor type LT feeder pillar box of suitable size platform mounted (to be mounted on the P.C.C. pedestal), suitable for 3 phase 4 wire, 415 volts AC supply and having 4 Nos Aluminium bus bars of rating 100 amps, Spreader link to incoming MCCB for termination of incoming cable and 4 way ebonite cable connector for outgoing cables, duly fabricated in a CPRI approved / certified factory having modern fabrication and testing facility which includes atleast seven (07) tanks pre treatment facility comprising of de-greasing, rinsing, de-rusting, rinsing, phosphating, rinsing and passivation followed by powder coated painting (thickness not less than 80 Micron) with approved shade of RAL 7032. The feeder pillar shall be provided with suitable Neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-55 and general construction conforming to IS : 13947. The feeder pillar shall be made out of 3.00mm thick CRCA mild steel sheet and 3.00mm thick gland plate and having front opening facility (with double layer shutter)and rear opening facility with single layer shutter with locking facility and 2 side slanting canopy type roof on top and mild steel angle (50x50x5mm) legs of length 30 cm at bottom, suitable for mounting on the pedestal, The feeder pillar shall be provided with ventilation facility in the form of louvers for better heat dissipation and including platform earth work, brick work, PCC work complete. Including dismentaling existing UNSv Lt feeder pillar from site. The feeder pillar shall be comprising of the followings :- 4 Each Job
58 32.01 MCCB, 4 Pole, 63 Amps, Breaking Capacity 16 KA, Adjustable type (100% - 80%) - 01 No. (Incoming)
59 32.02 Power contactor 3 Phase 40 Amps, with 02 Nos NO & NC auxiliary contacts 415 V, with No volt coil of voltage grade 240 V AC - 01 Nos
60 32.03 Astronomical type time switch 1 module, 16 amps rating with 1NO +1NC contacts and 28 programmable features - 01 No
61 32.04 MCB TPN 20 Amps, 415 V, 50 Hz AC - 03 Nos
62 32.05 LED Phase Indicating light, shrouded type, 22mm, with cluster LED (RED,YELLOW & BLUE) - 01 set
63 32.06 Digital Volt Meter (96mm x 96mm), 4 1/2 digit, Accuracy Class 1% - 01 No
64 32.07 Digital Ammeter (96mm x 96mm), 4 1/2 digit, Accuracy Class 1% - 01 No
65 32.08 Volt meter selector switch (6 Amps), 3 position with "OFF"-01 No.
66 32.09 Ammeter selector switch (6 Amps), 3 position with "OFF" - 01 No.
67 32.1 C.T having Ratio 100/5, tape wound,BPL, rated burden 5 VA-03 Nos.
68 32.11 Complete control wiring for all indicating instruments with 1100 V grade PVC insulated 1.5 sqmm, multi flexible type, Copper cable duly lugged and ferrule marked and with 3 Nos 3A SP MSB fpr protection- 01 Job
69 32.12 Alumunium danger notice plate (6" x 4") - 01 No.
70 32.13 Aluminium Earth busbar (25mm x 4mm) for terminating 02 Nos earthing conductor strips - 01 No
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy