Military Engineer Services-MES has published Repair Maintenance Of Different Type Capacity Of Centrifugal Submersible Pump Sets And Starter Panels At Af Stn Naliya. Submission Date for this Tender is 04-11-2020. Starter Tenders in GE (AF) Naliya NO 01 Gujarat. Bidders can get complete Tender details and download the document.
Name of Work : Repair/maintenance of different type/capacity of centrifugal/submersible pump sets and starter panels at AF stn Naliya. | |||||
---|---|---|---|---|---|
Sl. No. | Description of work | Item Code / Make | No. Or Qty | Units | |
1 | 1 | Disconnect the existing 60 HP, 3 Phase capacity the electric / water connections and removing centrifugal motor from base plate of pumpset and transporting motor to workshop to carryout repairs including replacement of any parts which are damaged and required to be replaced and bringing back after repair, servicing etc and refixing in its original position, testing and commissioning complete all as specified and as directed | 4 | Each Job | |
2 | 2 | All as per Item No. 1 above but 35 to 40 HP , 3 Phase capacity | 6 | Each Job | |
3 | 3 | All as per Item No.1 above but 15 HP , 3 Phase capacity | 1 | Each Job | |
4 | 4 | All as per Item No.1 above but 10 HP , 3 Phase capacity | 2 | Each Job | |
5 | 5 | Disconnect the existing 5 HP, 3 Phase capacity electric /water connections and removing centrifugal monoblock pumpset from any type existing location, and transporting motor to workshop to carryout repairs including replacement of any parts which are damaged and required to be replaced and bringing back after repair, servicing etc and refixing in its original position, testing and commissioning complete all as specified and as directed. | 3 | Each Job | |
6 | 6 | All as per Item No.5 above but 2 HP, 1 Phase capacity | 3 | Each Job | |
7 | 7 | All as per Item No.5 above but 1 HP, 1 Phase capacity | 4 | Each Job | |
8 | 8 | All as per Item No.5 above but 0.25 to 0.50 HP , 1 Phase capacity\nNote for Item No. 1 to 8 : - The parts, winding etc replaced if any shall be measured and paid separately as supply only under relevant item. | 4 | Each Job | |
9 | 9 | M & L in repairs for rewinding of induction motor of 60 HP , 3 Phase capacity by means of cutting and removing existing burnt out winding completely cleaning and repair of slots and rewinding with new copper wire of existing gauge and size / turns, varnishing with class 'B' insulation assembling the motor complete testing at workshop complete all as specified and as directed. | 4 | Each Job | |
10 | 10 | All as per Item No.9 above but 35 to 40 HP , 3 Phase capacity | 4 | Each Job | |
11 | 11 | All as per Item No.9 above but 15 HP , 3 Phase capacity | 1 | Each Job | |
12 | 12 | All as per Item No.9 above but 10 HP , 3 Phase capacity | 4 | Each Job | |
13 | 13 | M & L in repairs for rewinding of centrifugal monoblock pumpset of 5 HP, 3 Phase capacity by means of cutting and removing existing burnt out winding completely cleaning and repair of slots and rewinding with new copper wire of existing gauge and size/turns, varnishing with class 'B' insulation assembling the motor complete testing at workshop complete all as specified and as directed. | 3 | Each Job | |
14 | 14 | All as per Item No.13 above but 2 HP, 1 Phase capacity | 3 | Each Job | |
15 | 15 | All as per Item No.13 above but 1 HP, 1 Phase capacity | 4 | Each Job | |
16 | 16 | All as per Item No.13 above but 0.25 to 0.50 HP , 1 Phase capacity | 4 | Each Job | |
17 | 17 | S & F in repairs ball bearing in centrifugal motor of 60 HP , 3 Phase capacity after taking out broken/wear and tear unserviceable baering complete all as specified and as directed | 6 | Each Job | |
18 | 18 | All as per Item No.17 above but 35 to 40 HP , 3 Phase capacity | 6 | Each Job | |
19 | 19 | All as per Item No.17 above but 15 HP , 3 Phase capacity | 2 | Each Job | |
20 | 20 | All as per Item No.17 above but 10 HP , 3 Phase capacity | 6 | Each Job | |
21 | 21 | S & F in repairs ball bearing in centrifugal monoblock pump sets of 5 HP, 3 Phase capacity after taking out broken/wear and tear unserviceable bearing complete all as specified and as directed | 3 | Each Job | |
22 | 22 | All as per Item No.21 above but 2 HP, 1 Phase capacity | 3 | Each Job | |
23 | 23 | All as per Item No.21 above but 1 HP, 1 Phase capacity | 4 | Each Job | |
24 | 24 | All as per Item No.21 above but 0.25 to 0.50 HP , 1 Phase capacity | 4 | Each Job | |
25 | 25 | Supply and fix of CI sleeve in bearing housing of 60 HP , 3 Phase capacity centrifugal motor complete all as specified and as directed | 2 | Each | |
26 | 26 | All as per Item No.25 above but 35 to 40 HP , 3 Phase capacity | 2 | Each | |
27 | 27 | All as per Item No.25 above but 15 HP , 3 Phase capacity | 2 | Each | |
28 | 28 | All as per Item No.25 above but 10 HP , 3 Phase capacity | 1 | Each | |
29 | 29 | Supply and fixing of terminal connection plate for 60 HP , 3 Phase capacity C/F Motor complete all as specified and as directed | 3 | Each | |
30 | 30 | All as per Item No.29 above but 35 to 40 HP , 3 Phase capacity | 2 | Each | |
31 | 31 | All as per Item No.29 above but 15 HP , 3 Phase capacity | 2 | Each | |
32 | 32 | All as per Item No.29 above but 10 HP , 3 Phase capacity | 1 | Each | |
33 | 33 | Supply and fix of terminal box for 60 HP , 3 Phase capacity C/F Motor complete all as specified and as directed | 3 | Each | |
34 | 34 | All as per Item No.33 above but 35 to 40 HP , 3 Phase capacity | 2 | Each | |
35 | 35 | All as per Item No.33 above but 15 HP , 3 Phase capacity | 2 | Each | |
36 | 36 | All as per Item No.33 above but 10 HP , 3 Phase capacity | 1 | Each | |
37 | 37 | Supply and fix bearing plate & bolt of bearing plate size 8 x 100 mm complete all as specified and as directed | 50 | Nos | |
38 | 38 | Disconnecting electric/water connection and removing centrifugal pump 60 HP , 3 Phase capacity from base plate of pumpset and transporting pump to workshop to carry out repair and bringing back after carrying out repair, servicing etc and refixing in its original position , testing and commissioning complete all as specified and as directed | 4 | Each Job | |
39 | 39 | All as per Item No.38 above but 35 to 40 HP , 3 Phase capacity | 4 | Each Job | |
40 | 40 | All as per Item No.38 above but 15 HP , 3 Phase capacity | 1 | Each Job | |
41 | 41 | All as per Item No.38 above but 10 HP , 3 Phase capacity | 2 | Each Job | |
42 | 42 | Supply and fix,coupling flexible cushion I/C making bore and key way complete Set with tyre, nut bolts etc,type TC/P/011, | 2 | Each Set | |
43 | 43 | All as per Item No.42 above but type TC/P/013 | 2 | Each Set | |
44 | 44 | All as per Item No.42 above but type TC/P/014 | 4 | Each Set | |
45 | 45 | All as per Item No.42 above but type TC/P/015 | 4 | Each Set | |
46 | 46 | All as per Item No.42 above but type TC/P/017 | 4 | Each Set | |
47 | 47 | All as per Item No.42 above but type TC/P/018 | 4 | Each Set | |
48 | 48 | Supply and fix spare tyre for coupling Type TC/P/011 to TC/P/017 all as per existing size and make required at site , complete all as specified and directed. | 10 | Each | |
49 | 49 | S & F in repair stainless steel shaft of centrifugal pump of 60 HP , 3 Phase capacity after taking out broken/wear and tear unserviceable shaft as per the sample and existing type and size complete all as specified and as directed. | 2 | Each Job | |
50 | 50 | All as per Item No.49 above but 35 to 40 HP , 3 Phase capacity | 4 | Each Job | |
51 | 51 | All as per Item No.49 above but 15 HP , 3 Phase capacity | 1 | Each Job | |
52 | 52 | All as per Item No.49 above but 10 HP , 3 Phase capacity | 1 | Each Job | |
53 | 53 | S & F in repairs ball bearing in centrifugal pump of 60 HP , 3 Phase capacity after taking out broken/wear and tear unserviceable baering complete all as specified and as directed. | 10 | Each Job | |
54 | 54 | All as per Item No.53 above but 35 to 40 HP , 3 Phase capacity | 6 | Each Job | |
55 | 55 | All as per Item No.53 above but 15 HP , 3 Phase capacity | 3 | Each Job | |
56 | 56 | All as per Item No.53 above but 10 HP , 3 Phase capacity | 3 | Each Job | |
57 | 57 | S & F in repairs impeller in centrifugal pump of 60 HP , 3 Phase capacity after taking out broken/wear and tear unserviceable impeller as per the sample and existing size complete all as specified and as directed. | 2 | Each Job | |
58 | 58 | All as per Item No.57 above but 35 to 40 HP , 3 Phase capacity | 2 | Each Job | |
59 | 59 | All as per Item No.57 above but 15 HP , 3 Phase capacity | 1 | Each Job | |
60 | 60 | All as per Item No.57 above but 10 HP , 3 Phase capacity | 1 | Each Job | |
61 | 61 | Supply only CI casing wear ring DE/NDE spare part for centrifugal pump set of 35 to 60 HP | 4 | Each | |
62 | 62 | All as per Item No.61 above but CI Interstage Ring | 4 | Each | |
63 | 63 | All as per Item No.61 above but CI stuffing box bush | 4 | Each | |
64 | 64 | All as per Item No.61 above but CI gland plate | 4 | Nos | |
65 | 65 | All as per Item No.61 above but Lentern Ring | 6 | Each | |
66 | 66 | All as per Item No.61 above but Eye bolt with Nut | 10 | Each | |
67 | 67 | All as per Item No.61 above but CI shaft sleeve | 6 | Each | |
68 | 68 | All as per Item No.61 above but Gasket packing sheet | 4 | Set | |
69 | 69 | All as per Item No.61 above but Gland packing champion | 6 | Set | |
70 | 70 | All as per Item No.61 above but Remetling of pump shaft turning and balancing | 4 | Job | |
71 | 71 | All as per Item No.61 above but Impeller Key | 4 | Nos | |
72 | 72 | All as per Item No.61 above but Coupling Key | 4 | Nos | |
73 | 73 | All as per Item No.61 above but Water liquid Defletor | 8 | Nos | |
74 | 74 | All as per Item No.61 above but CI bearing cartiage DE/NDE | 4 | Nos | |
75 | 75 | All as per Item No.61 above but CI bearing Plate | 4 | Nos | |
76 | 76 | All as per Item No.61 above but Coupling nut | 4 | Nos | |
77 | 77 | All as per Item No.61 above but MS stud with nut | 24 | Nos | |
78 | 78 | All as per Item No.61 above but G.M Impeller nut | 4 | Nos | |
79 | 79 | Taking out of any capacity submersible pump set carefully from bore well alongwith existing submersible cable MS/GI/HDPE, Column pipe of dia 80mm/ 100mm , flanged type , 3 meters each length (depth of submersible pump is 80 m to 115 m) and shifting column pipe , pumpset and submersible cable aside for reuse and lowering into bore well after repair work including of submersible cable jointing initial pump set testing binding of submersible cable with column pipe by using aluminium wire complete and final testing complete all as specified and as directed.\nNote :- (i) The quoted rate deemed to be included the cost of rubber gaskets, nuts, bolts , washers aluminium wire etc.\n(ii) Any damage to pump set column pipe submersible cable etc while taking out and lowering of pump set will be repaired/replaced by contractor on his own cost and GE's decision shall be final and binding in this regard. | 16 | Each Job | |
80 | 80 | Complete opening of submersible bore well pump set of 40 HP/30 HP/27.5 HP capacity for repair /replacement of unserviceable worn out bearing/worn out unserviceable shaft/burned out copper winding /worn out strainer/bush/sleeve/thrust pad/thrust bearing/thrust bearing lock nut etc , including re-assembling and testing complete all as specified and as directed.\nNote :- (i) Cost of transportation of pump set from site to workshop and back to site after repair is deemed to be included in the quoted rate.\n(ii) Repair/replacement of parts/winding shall be measured and paid separately. | 12 | Each Job | |
81 | 81 | M & L in repairs for rewinding of submersible bore well motor of 40 HP capacity by means of cutting and removing existing burnt out winding completely , cleaning and repair of slots and rewinding with new copper wire of existing gauge and size /turns, varnishing assembling the motor complete testing at workshop complete all as specified and as directed | 5 | Each Job | |
82 | 82 | All as per Item No.81 above but 30 HP capacity | 3 | Each Job | |
83 | 83 | All as per Item No.81 above but 27.5/25 HP capacity | 2 | Each Job | |
84 | 84 | Supply only Bearing bush for submersible Pump set of capacity 25 HP to 40 HP. | 8 | Nos | |
85 | 85 | All as per Item No.84 above but Rotar Sleeve | 8 | Nos | |
86 | 86 | All as per Item No.84 above but Water seal and cable seal | 10 | Nos | |
87 | 87 | All as per Item No.84 above but Thrust bearing | 10 | Nos | |
88 | 88 | All as per Item No.84 above but Revolving Disc | 4 | Nos | |
89 | 89 | All as per Item No.84 above but CI Connection piece | 4 | Nos | |
90 | 90 | All as per Item No.84 above but Motor sand guard | 4 | Nos | |
91 | 91 | All as per Item No.84 above but Sealing ring | 4 | Nos | |
92 | 92 | All as per Item No.84 above but CI upper housing | 6 | Nos | |
93 | 93 | All as per Item No.84 above but CI Lower housing | 6 | Nos | |
94 | 94 | All as per Item No.84 above but Rotar Sleeve turming and polishing | 4 | Job | |
95 | 95 | All as per Item No.84 above but Remetling of Rotar end turming and making key way | 4 | Job | |
96 | 96 | All as per Item No.84 above but Repairing of starter stamping | 4 | Job | |
97 | 97 | All as per Item No.84 above but Seal bush | 4 | Nos | |
98 | 98 | All as per Item No.84 above but CI Motor Base | 4 | Nos | |
99 | 99 | All as per Item No.84 above but Thrust plate | 6 | Nos | |
100 | 100 | All as per Item No.84 above but S.S coupling | 4 | Nos | |
101 | 101 | All as per Item No.84 above but Key for S.S coupling | 4 | Nos | |
102 | 102 | All as per Item No.84 above but Stud and nut for connection piece | 8 | Nos | |
103 | 103 | All as per Item No.84 above but Balancing of Rotar | 6 | Job | |
104 | 104 | All as per Item No.84 above but T-Bolt with nut | 20 | Nos | |
105 | 105 | All as per Item No.84 above but LNK Bolt S.S | 20 | Nos | |
106 | 106 | All as per Item No.84 above but Submersible cable jointing | 8 | Nos | |
107 | 107 | All as per Item No.84 above but CI Suction chamber | 4 | Nos | |
108 | 108 | All as per Item No.84 above but CI stage bowl | 12 | Nos | |
109 | 109 | All as per Item No.84 above but GM Impeller | 12 | Nos | |
110 | 110 | All as per Item No.84 above but Guid Bush | 12 | Nos | |
111 | 111 | All as per Item No.84 above but DOL Bush | 6 | Nos | |
112 | 112 | All as per Item No.84 above but S.S DOL Sleeve | 6 | Nos | |
113 | 113 | All as per Item No.84 above but Inter Ring | 6 | Nos | |
114 | 114 | All as per Item No.84 above but CI DOL Piece | 2 | Nos | |
115 | 115 | All as per Item No.84 above but CI NRV Body | 2 | Nos | |
116 | 116 | All as per Item No.84 above but Impeller Key | 12 | Nos | |
117 | 117 | All as per Item No.84 above but S.S Pump shaft single stage | 8 | Nos | |
118 | 118 | All as per Item No.84 above but Remetling of G.M Impeller and turming | 10 | Nos | |
119 | 119 | All as per Item No.84 above but Pump sand guard | 4 | Nos | |
120 | 120 | All as per Item No.84 above but S.S Distance sleeve | 12 | Nos | |
121 | 121 | All as per Item No.84 above but G.M Neck Ring | 12 | Nos | |
122 | 122 | All as per Item No.84 above but M.S Stud with nut | 40 | Nos | |
123 | 123 | All as per Item No.84 above but Coise mesh | 4 | Nos | |
124 | 124 | All as per Item No.84 above but Drain Plug | 10 | Nos | |
125 | 125 | Taking out submersible 15 HP/10HP/5 HP/3 HP Non-clog sewage pumpset from sewage well/STP pump duly disconnecting electric /sewage connections along with existing submersible cable , pipe etc and shifting pump set cable and pipe aside for reuse and lowering into sewage well after repair works including initial testing water proof cable jointing/sewage line connecting , final testing etc complete all as specified and as directed | 6 | Each Job | |
126 | 126 | Taking out of horizontal submersible 40 HP/20 HP/ 15 HP/7.5 HP pump set from open well UG sump duly disconnecting electric /water connections , alongwith existing submersible cable pipe etc and shifting pump set cable and pipe aside for reuse and lowering into sewage well after repair works including initial testing water proof cable jointing water line connecting final testing etc complete all as specified all as directed by Engr-in-Charge.\nNote for item No 125 & 126 :- (i) The quoted rate deemed to be included the cost of rubber gaskets, nuts bolts, washers etc.\n(ii) Any damage to pump set pipe submersible cable etc while taking out and lowering of pump set will be repaired/replaced by contractor on his own cost and GE's decision shall be final and binding in this regard. | 6 | Each Job | |
127 | 127 | Complete opening of 15 HP/ 10 HP capacity submersible non-clog sewage pump set for repair /replacement of unserviceable worn out bearing/worn out unserviceable shaft/burned out copper winding /worn out strainer/bush/sleeve/thrust pad/thrust bearing/thrust bearing lock nut etc including transportation complete all as specified and as directed | 1 | Each Job | |
128 | 128 | All as per Item No.127 above but 5 HP/3 HP | 4 | Each Job | |
129 | 129 | Complete opening of horizontal submersible 40 HP / 20HP/ 15 HP/7.5 HP pump set for repair /replacement of unserviceable worn out bearing/worn out unserviceable shaft/burned out copper winding /worn out strainer/bush/sleeve/thrust pad/thrust bearing/thrust bearing lock nut etc including transportation complete all as specified and as directed by Engr-in-Charge.\nNote :- (i) Cost of transportation of pump set from from site to workshop and back to site after repair is deemed to be included in the quoted rate. \n(ii) Repairs/replacement of parts/winding shall be measured and paid separetly. | 6 | Each Job | |
130 | 130 | S & F in repairs impeller for 15 HP capacity Submersible non clog sewage pump set submersible Non-Clog sewage pump set all as provided by the original manufacturer complete all as specified and as directed | 1 | Each Job | |
131 | 131 | All as per Item No.130 above but 10 HP Submersible non clog sewage pump set | 2 | Each Job | |
132 | 132 | All as per Item No.130 above but 5 HP/3 HP Submersible non clog sewage pump set | 4 | Each Job | |
133 | 133 | S & F in repairs impeller for 40 HP capacity Horizontal Submersible pump set horizontal submersible pump set all as provided by the original manufacturer complete all as specified and as directed by Engr-in-Charge. | 2 | Each Job | |
134 | 134 | All as per Item No.133 above but 20 HP Horizontal Submersible pump set | 1 | Each Job | |
135 | 135 | All as per Item No.133 above but 15 HP Horizontal Submersible pump set | 1 | Each Job | |
136 | 136 | All as per Item No.133 above but 7.5 HP Horizontal Submersible pump set | 1 | Each Job | |
137 | 137 | S & F in repairs ball bearing for 15 HP capacity Submersible non clog sewage pump set submersible Non-Clog sewage pump set all as provided by the original manufacturer complete all as specified and as directed | 1 | Each Job | |
138 | 138 | All as per Item No.137 above but 10 HP Submersible non clog sewage pump set | 2 | Each Job | |
139 | 139 | All as per Item No.137 above but 5 HP/ 3 HP Submersible non clog sewage pump set | 3 | Each Job | |
140 | 140 | S & F in repairs ball bearing for 40 HP capacity Horizontal Submersible pump set horizontal submersible pump set all as provided by the original manufacturer complete all as specified and as directed by Engr-in-Charge. | 3 | Each Job | |
141 | 141 | All as per Item No.140 above but 20 HP Horizontal Submersible pump set | 1 | Each Job | |
142 | 142 | All as per Item No.140 above but 15 HP Horizontal Submersible pump set | 1 | Each Job | |
143 | 143 | All as per Item No.140 above but 7.5 HP Horizontal Submersible pump set | 1 | Each Job | |
144 | 144 | M & L in repairs for rewinding for 15 HP capacity Submersible non clog sewage pump set submersible non-clog sewage pump set motor by means of cutting and removing existing burnt out winding completely cleaning and repair of slots and rewinding with new copper wire of existing gauge and size/turns, varnishing, assembling the motor complete testing at workshop complete all as specified and as directed | 1 | Each Job | |
145 | 145 | All as per Item No.144 above but 10 HP Submersible non clog sewage pump set | 4 | Each Job | |
146 | 146 | All as per Item No.144 above but 5 HP/ 3 HP Submersible non clog sewage pump set | 4 | Each Job | |
147 | 147 | M & L in repairs for rewinding for 40 HP capacity Horizontal Submersible pump set horizontal submersible pump set motor by means of cutting and removing existing burnt out winding completely cleaning and repair of slots and rewinding with new copper wire of existing gauge and size/turns, varnishing, assembling the motor complete testing at workshop complete all as specified and as directed | 2 | Each Job | |
148 | 148 | All as per Item No.147 above but 20 HP Horizontal Submersible pump set | 1 | Each Job | |
149 | 149 | All as per Item No.147 above but 15 HP Horizontal Submersible pump set | 1 | Each Job | |
150 | 150 | All as per Item No.147 above but 7.5 HP Horizontal Submersible pump set | 1 | Each Job | |
151 | 151 | S & F in repairs PVC insulated 3 core 10 Sqmm copper multistranded PVC sheathed submersible flexible cable ISI marked and conforming to IS : 694 and connecting to submersible pump and to LT panel after taking out old unserviceable cable complete all as specified and as directed. | 300 | RM | |
152 | 152 | All as per Item No.151 above but 3 core 16 Sqmm | 550 | RM | |
153 | 153 | S & F in repairs GI pipe light grade of 50 mm dia for cable protection complete all as specified and as directed. | 48 | RM | |
154 | 154 | Supply, fix, jointing and testing of Cast iron Non Return valve 100 mm bore without by pass arrangement , Swing type, confirming to IS 5312, flanged ends pressure rating PN 1.0 complete including taking out unserviceable NRV complete all as specified and as directed\nNote:- Flanged joints complete with jointing material shall deemed to be included in the unit rate of this item. | 8 | Each | |
155 | 155 | All as per Item No.154 above but 150 mm bore | 2 | Each | |
156 | 156 | Supply and fix CI foot valve of size 100mm bore, flanged ends, swing type opration with rubber sheet, as per IS : 4038. Complete including taking out unserviceable foot valve all as specified and directed \nNote:- Flanged joints complete with jointing material shall deemed to be included in the unit rate of this item. | 4 | Each | |
157 | 157 | All as per Item No.156 above but above but size 150 mm bore. | 1 | Each | |
158 | 158 | All as per Item No.156 above but size 80 mm bore. | 1 | Each | |
159 | 159 | All as per Item No.156 above but size 50 mm bore. | 1 | Each | |
160 | 160 | S& F in repair MCCB 3 pole , 415 volts , fixed thermal and fixed magnetic setting 100 Amps with braking capacity 16 KA complete all as specified and as directed . \n | 2 | Each | |
161 | 161 | All as per Item No.160 above but 160 Amps , with braking capacity 25 KA. | 2 | Each | |
162 | 162 | All as per Item No.160 above but 250 Amps , with braking capacity 35 KA. | 1 | Each | |
163 | 163 | S& F in repair MCCB 4 pole , 415 volts , fixed thermal and fixed magnetic setting 250 Amps with braking capacity 35 KA complete all as specified and as directed . | 1 | Each | |
164 | 164 | S & F in repairs electronic timer for star-delta time delay 3 to 30 seconds all as per existing sample complete all as specified and as directed. | 8 | Each | |
165 | 165 | S& F in repairs 3 pole power contactor type ML-1.5 , range 25 Amps , AC -3 complete all as specified and directed. | 1 | Each | |
166 | 166 | All as per item No. 165 herein-before but type ML-2, 32 Amps 415Volts, 50 Hz. | 1 | Each | |
167 | 167 | All as per item No 165 herein-before but type ML-3, 40 Amps 415Volts, 50 Hz. | 1 | Each | |
168 | 168 | All as per item No 165 herein-before but type ML-4, 70 Amps 415Volts, 50 Hz. | 2 | Each | |
169 | 169 | All as per item No 165 herein-before but type ML-6, 110 Amps 415Volts, 50 Hz. | 4 | Each | |
170 | 170 | Supply and fix in replacement overload relay type MN-2 relay range 14-23 Amps complete all as specified and directed. | 2 | Each | |
171 | 171 | All as per item No 170 here-in-before but type ML 2/3 Range 28-42 Amps . | 2 | Each | |
172 | 172 | All as per item No 170 here-in-before but type ML 5 Range 45-75 Amps . | 2 | Each | |
173 | 173 | All as per item No 170 here-in-before but type ML 5 Range 66-110 Amps . | 4 | Each | |
174 | 174 | S&F in repairs DOL starter in sheet metal enclosure max motor output at 415 Volt, 3 phase, 5 HP, relay range 7-10 Amps complete all as specified and as directed.\n | 2 | Each | |
175 | 175 | S&F in repairs star delta starter max motor output at 415 Volt, 3 phase, relay range 45-75 in sheet metal enclosure type ML-4 for 3 phase induction motor complete all as specified and as directed. | 1 | Each | |
176 | 176 | S&F in repairs star delta starter max motor output at 415 Volt, 3 phase, relay range 28-42 in sheet metal enclosure type ML-3 for 3 phase induction motor complete all as specified and as directed. | 1 | Each | |
177 | 177 | S&F in repairs star delta starter max motor output at 415 Volt, 3 phase relay range 20-32 in sheet metal enclosure type ML-2 for 3 phase induction motor complete all as specified and as directed. \n | 1 | Each | |
178 | 178 | S&F in repairs star delta starter max motor output at 415 Volt, 3 phase relay range 9--14 Amps in sheet metal enclosure type MK-1 for 3 phase induction motor complete all as specified and as directed. | 1 | Each | |
179 | 179 | S&F in repairs Single Phasing Preventer Relay type VSP-II, 415V complete all as specified and as directed. | 4 | Each | |
180 | 180 | S&F in repair ammeter 415 volt, 3 phase 0 to 120 Amps rating, analogue type complete all as specified and as directed. | 4 | Each | |
181 | 181 | S&F in repair voltmeter 415 volt,3 phase 0 to 500 volts rating, analogue type complete all as specified and as directed. | 4 | Each | |
182 | 182 | Supply and fix of terminal strip 100 Amps 6 way complete all as specified and as directed. | 2 | Nos | |
183 | 183 | Supply and fix of Digital Amp meter 96 x 96 Sqmm analogue type 0 to 100 amps complete all as specified and as directed. | 2 | Nos | |
184 | 184 | Supply and fix in replacement of current transformer ratio 100/5 complete all as specified and as directed. | 2 | Nos | |
185 | 185 | Supply and fix in replacement of current transformer ratio 60/5 complete all as specified and as directed | 2 | Nos | |
186 | 186 | Supply and fix in replacement PVC insulated multristranded copper conductor wire 1100 volts, single core of size 10.00 Sqmm complete all as specified and as directed. | 100 | RM | |
187 | 187 | All as per item No. 186 here-in-before but of size 16.00 Sqmm | 100 | RM | |
188 | 188 | All as per item No 186 here-in-before but of size 25.00 Sqmm | 150 | RM | |
189 | 189 | All as per item No 186 here-in-before but of size 35.00 Sqmm | 200 | RM | |
190 | 190 | M&L for servicing of 30 KVA DG set Engine situated/ installed at site at different locations, including replacement of fuel filters, oil filters, air filters, air filter element, changing lubricating oil, cleaning of fuel lines, checking leakage if any, repair the leakage replacement of exhaust main fold gasket etc complete all as specified and as directed. \nNote:- (i) Lubrication oil shall be supplied free under Sch.'B'.\n(ii) Spare parts required for maintenance shall be measured and paid separately under relevant item. | 1 | Each | |
191 | 191 | All as per item No 190 here-in-before but 125 KVA | 1 | Each | |
192 | 192 | All as per item No 190 here-in-before but 160 KVA | 1 | Each | |
193 | 193 | All as per Item No.190 here-in-before but 200/ 250 KVA | 2 | Each | |
194 | 194 | All as per Item No. 190 but for Non -clog sewage Diesel Engine driven pump set 5 HP capacity | 3 | Each | |
195 | 195 | Supply only diesel filter with gasket for 30 KVA capacity DG sets complete all as specified and as directed. | 1 | Each | |
196 | 196 | All as per Item No.195 above but 125 KVA | 1 | Each | |
197 | 197 | All as per Item No.195 above but 160 KVA | 1 | Each | |
198 | 198 | All as per Item No.195 above but 200/ 250 KVA | 2 | Each | |
199 | 199 | All as per Item No. 195 but for Non -clog sewage Diesel Engine driven pump set 5 HP | 3 | Each | |
200 | 200 | Supply only engine oil filter with gasket for 30 KVA capacity DG sets complete all as specified and directed. | 1 | Each | |
201 | 201 | All as per Item No.200 above but 125 KVA | 1 | Each | |
202 | 202 | All as per Item No.200 above but 160 KVA | 1 | Each | |
203 | 203 | All as per Item No.200 above but 200/ 250 KVA | 2 | Each | |
204 | 204 | All as per Item No.200 above but for Non -clog sewage Diesel Engine driven pump set 5 HP | 3 | Each | |
205 | 205 | Supply only high pressure fuel line with end coupler complete from FIP to injector complete all as specified and directed. | 2 | Each Job | |
206 | 206 | Supply only flexible fuel pipe set all as per existing sample complete all as specified and directed. | 2 | Each Job | |
207 | 207 | Supply only water hose pipes all as per existing sample complete all as specified and directed. | 2 | Each | |
208 | 208 | Supply only Thermostat element all as per existing sample complete all as specified and directed. | 2 | Each | |
209 | 209 | Replace the rubber coupling bush consist of rubber ring of suitable size and model (plate/ cup) with nuts bolts complete all as specified and directed. | 2 | Each Set | |
210 | 210 | Supply only anti vibration pads of suitable size complete all as specified and directed. | 2 | Each | |
211 | 211 | Supply and fill coolant of standard specification for top up in radiator of Diesel Engine of any size complete all as specified and directed. | 50 | Litre | |
212 | 212 | S&F in repair Automatic Voltage Regulator (AVR) complete all as specified and as directed. \n | 1 | Each | |
213 | 213 | S&F in repair stop solenoid switch complete all as specified and directed. | 1 | Each Set | |
214 | 214 | S&F in repair copper terminal heavy duty for battery (length 1.5 mtr) connection with suitable size of copper lugs on one side brass lead on other end complete all as specified and as directed. | 4 | Each | |
215 | 215 | M&L for complete removal and preparation of old painted surfaces of centrifugal pump set of 60 HP 3 phase capacity and applying two coats of synthetic enamel paint over a coat of red oxide primer complete and writing of MES/ SM No. complete all as specified and as directed | 6 | Each Job | |
216 | 216 | All as per Item No.215 above but 40 HP 3 phase capacity | 4 | Each Job | |
217 | 217 | All as per Item No.215 above but 15 HP 3 phase capacity | 2 | Each Job | |
218 | 218 | All as per Item No.215 above but 10 HP 3 phase capacity | 3 | Each Job | |
219 | 219 | M & L for providing gland packing as per existing size and make/model, of 60 HP 3 phase capacity C/F Motor Pump, complete all as specified and as directed | 10 | Each Job | |
220 | 220 | All as per Item No.219 above but 40 HP 3 phase capacity | 8 | Each Job | |
221 | 221 | All as per Item No.219 above but 15 HP 3 phase capacity | 4 | Each Job | |
222 | 222 | All as per Item No.219 above but 10 HP 3 phase capacity | 4 | Each Job | |
223 | 223 | Supply only greasing for bearing of centrifugal Pumps complete all as specified and as directed. \n | 100 | Kg | |
224 | 224 | Clear site of from all rubbish, cut down shrubs, under growth and small trees not exceeding 600mm girth, grub up roots and burn or remove from site complete all as specified and as directed. | 400 | Sqm | |
225 | 225 | Surface dressing of uneven surfaces of the natural ground, rough excavated surfaces and filled area where ordered shall be trimed to an even surface horizontal or slopping, by removing vegetation and by scrapping high patches and filling low patches with the scrapping soil to given an even and neat look to the site, depth of cutting not exceeding 15 cm complete all as specified and as directed. | 400 | Sqm | |
226 | 226 | S&F in repair off-load change over switch of rating 400 Amps, in sheet metal enclosure, 415V, AC, 50 Hz, side handle complete all as specified and as directed. | 1 | Each | |
227 | 227 | All as per Item No.226 above but of capacity 250 Amps , 415 Volts, AC 50 Hz. | 1 | Each | |
228 | 228 | All as per Item No.226 above but of capacity 200 Amps , 415 Volts, AC 50 Hz. | 1 | Each | |
229 | 229 | All as per Item No.226 above but of capacity 100 Amps , 415 Volts, AC 50 Hz. | 1 | Each | |
230 | 230 | Supply and fix in replacemenet of MS base channel for foundation as per existing size including cutting, welding, making hole, and paint (two coat of synthatic enamel paint over a coat of red oxide) complete all as specified and as directed. | 300 | Kg | |
231 | 231 | Supply and fix of all type of MS foundation bolt with nut and washers of size 20 x 450 mm complete all as specified and as directed. | 32 | Nos | |
232 | 232 | Supply and fix of Indicating light LED type R,Y,B complete all as specified and as directed. | 12 | Nos | |
233 | 233 | Labour only for attending of Electric compliants of existing water supply Pump house panels /Borewells LT Panels/CF Motors/Subemrsible moters/Non-clog motors/Horizontal submesible , including connecting electrical accessories / spares of water supply installation, electrical fitting & short circuits in Pump house panel/CF Motors/Submersible motors/ Panels complete all as specified and as directed. \nNote :- (i) Any material required for attending complaints shall be measured & paid separately under respectvie item \n(ii) The complaints shall be attended and the defects shall be rectified by a team of expert and experienced electrician as applicable assisted with adequate No of helpers as directed by Enginner-in-charge.\n(iii) The rectifiable complaints shall be attended and defect shall be rectified within 08 hrs commencing from date and time of notifying the complaint failing which a penalty @ Rs 250/- per complaint per day (08 hrs) shall be levied upon/imposed on the contractor and recovery shall be made from contractor's dues.Contractor rep shall be available wef 0800 hrs to 2000 Hrs to receive and notify the complaint. Time required to complete the defect shll be intimated to Engineer in chrge well in advance \n(iv) All machinery, T & P required for attending the complaints shall be arranged by the contracor on his own. \n(v) The elecrician shall always be in possession of all Electrician tools , LT Megger, Earth tester , Multimeter , Crimping tool, insulation tape, Hand gloves etc required at site. | 50 | Each Job | |
234 | 234 | Supply and fix clamps in MS flat 100 mm x 6 mm with two Nos of MS nut bolts for 100 mm dia column pipe complete all as specified and as directed. | 6 | Nos | |
235 | 235 | Supply and fix in replacement of Pully V Belt SPB-1800 in STP Compressor (blower), twin lobe positive displacement type and pressure rating upto 0.8Kg/cm2 of exisitng make and model complete all as specified and as directed. | 1 | Nos | |
236 | 236 | All as per Item No.235 above but Ball Bearing 6311/C3 Make-SKF/ZKL | 2 | Nos | |
237 | 237 | All as per Item No.235 above but Roller bearing 3213A | 2 | Nos | |
238 | 238 | All as per Item No.235 above but Piston ring | 4 | Nos | |
239 | 239 | All as per Item No.235 above but Set of Gasket | 4 | Nos | |
240 | 240 | All as per Item No.235 above but Gear set | 1 | Each set | |
241 | 241 | All as per Item No.235 above but Oil seal | 3 | Nos | |
242 | 242 | All as per Item No.235 above but Oil level glass | 2 | Nos | |
243 | 243 | All as per Item No.235 above but Suction air filter | 2 | Each | |
244 | 244 | All as per Item No.235 above but Air compressor shaft werlding , turning , grinding | 2 | Job | |
245 | 245 | All as per Item No.235 above but Bearing tapper bush for roller bearing 22213 EK/C3 | 1 | Each | |
246 | 246 | All as per Item No.235 above but Outer distance bush | 1 | Nos | |
247 | 247 | All as per Item No.235 above but Pressure ring | 4 | Nos | |
248 | 248 | All as per Item No.235 above but Asbestos graphite packing(casing cover) | 2 | Nos | |
249 | 249 | All as per Item No.235 above but Asbestos graphite packing(stuffing box) | 2 | Nos |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy