}

Repair And Maint Of Overhead Line Ug Cable , Lt Panels And Allied Works At Zone-Ii Area Of Tibri Mil Stn Under Ge Gurdaspur ., Garrison Engineer, Gurdaspur (Tibri)-Punjab

Military Engineer Services-MES has published Repair And Maint Of Overhead Line Ug Cable , Lt Panels And Allied Works At Zone-Ii Area Of Tibri Mil Stn Under Ge Gurdaspur .. Submission Date for this Tender is 28-10-2020. LT Cable Tenders in Garrison Engineer, Gurdaspur (Tibri) Punjab. Bidders can get complete Tender details and download the document.




Tender Notice

25667520
Repair And Maint Of Overhead Line Ug Cable , Lt Panels And Allied Works At Zone-Ii Area Of Tibri Mil Stn Under Ge Gurdaspur .
Open Tender
Indian
Punjab
Garrison Engineer, Gurdaspur (Tibri)
28-10-2020

Tender Details

Repair And Maint Of Overhead Line Ug Cable , Lt Panels And Allied Works At Zone-Ii Area Of Tibri Mil Stn Under Ge Gurdaspur .

Key Value

Document Fees
INR 500 /-
EMD
INR 50000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: Repair and maint of overhead line, UG cable, LT panels and allied works of Zone-II area at Tibri Mil Stn under GE Gurdaspur.
Sl. No. Item Description Item Code / Make Quantity Units
1 1 BOQ
2 2 Excavation in trenches in soft/ loose soil including cutting road surfaces n.exc 1.5 mtr wide and n.exc. 1.5 mtr in depth for poles, stay, cable, pipe etc and getting out all as specified. 600 Cum
3 3 All as per item No.02 above but depth excd 1.5 mtr and n. exc 3 mtr. 3 Cum
4 4 Returning, filling in, including spreading, leveling,watering and well ramming in layers each n.exc 25 cm thick in soft loose soil all as specified. 450 Cum
5 5 Removal of excavated soil to a distance not exceeding 50 mtrs and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed. 150 Cum
6 6 Supply and lay brick common burnt sub class "B" old size (compressive strength not less than 75 kg per sqcm) for protection of cable laid in trenches for under ground cable all as specified. 40 Per 1000 Nos
7 7 M & L for sand cushioning trenches using fine sand to under ground cable, laid in two layers 15cm before laying the cable & 8cm after laying the cable complete all as specified and directed. 135 Cum
8 8 M&L for road cutting including excavation returning filling in spreading leveling , well ramming in layers, soiling with, broken boudders/ stones, WHB 7.5 cm thick coarse aggregate received from dismentling the existing road, premix, carpeting 25mm thick using mady mate material . rolled & compacted for road patch repair work, section/ cross section area of cuttng complete all as specified and directed. 30 RM
9 9 M&L for cable protection GI tubing light grade fixed long the pole/under road/along the wall of size 100mm bore with necessary clamps all as directed. 40 RM
10 10 M&L for cable protection GI tubing light grade fixed long the pole/under road/along the wall of size 80mm bore with necessary clamps all as directed. 50 RM
11 11 M&L for cable protection GI tubing light grade fixed long the pole/under road/along the wall of size 50mm bore with necessary clamps all as directed. 50 RM
12 12 M&L for cross arms in replacement , bracing, supports, clamps and brick plates, fabricated from staructural steel section including nut bolts washers including welding, bending , cold or hot drilling holes for bolts in any shape or size as indicated in drawings or as directed, including two coats of aluminium paint over a coat of red oxide all specified. 3 Qtl
13 13 M & L lightening arrestor in replacement expulsion type for out door use complete with all fitting transmission class discharge capacity 65 Kilo Amp suitable for 11000 volts including bracket, clamps, nuts, bolts washer and connection to each wire complete all as specified. Make-Rashtria/Oblum. 4 Set of three
14 14 Surface dressing by cutting grass, thorn bushes and congress grass upto the root level surrounding the installation incl the same not less than 200 mtr away all as directed by Engineer- in -Charge. 4000 Sqm
15 15 Stringing/ Stretching of existing ACSR conductor of any size any type as required sag fixed on OH line incl unwindinding the conductor & insulators/cross arms on poles properly binding with aluminum all as specified and directed. 10 Qtl
16 16 M & L aluminium conductor steel reinforced (ACSR) over size of ferret, weasels, mink, beaver etc fixing stretching and jumpering joining with aluminium wire complete all as specified. 3 Qtl
17 17 M&L galvanised steel wire of 3.15mm dia as earth wire for overhead line fixing of the same on the pole complete all as specified and directed. 3 Qtl
18 18 Supply and laying in replacement XLPE insulated armoured (under ground) heavy duty electic cablewith stranded aluminum conductor 1100 volts grade of cross- sectional area 240 Sqmm 3.5 core laid in trenches/ducts/through pipes/in floor road/along the pole etc all as specified & directed by Engr-in-Charge. Note : (a) Excavation earth work, brick protection and cushioning shall be measured & paid separately. 70 RM
19 19 All as per srl item No. 18 here in before but 185 Sqmm 3.5 core 100 RM
20 20 All as per srl item No. 18 here in before but 120 Sqmm 3.5 core 100 RM
21 21 All as per srl item No. 18 here in before but 95 Sqmm 3.5 core 300 RM
22 22 All as per srl item No. 18 here in before but 70 Sqmm 3.5 core 300 RM
23 23 All as per srl item No. 18 here in before but 50 Sqmm 3.5 core 300 RM
24 24 All as per srl item No. 18 here in before but 35 Sqmm 3.5 core 350 RM
25 25 All as per srl item No. 18 here in beore but 25 Sqmm 4 core 300 RM
26 26 All as per srl item No. 18 here in before but 16 Sqmm 2 core 200 RM
27 27 All as per srl item No. 18 here in before but 10 Sqmm 2 core 200 RM
28 28 Providing PCC 1:4:8 type D-2 using 40mm graded crushed stone aggreate as in foundation for pole/stay assembly foundation coping of poles etc. 10 Cum
29 29 Providing PCC 1:2:4 type B:2 using 40mm graded crushed stone aggreate as in foundation for pole/stay assembly foundation coping of poles etc. 1 Cum
30 30 M&L for stay assembly complete with accessories as shown in electrical plate No.1 with 20 mm rod including stay wire stand 7/4/3, 15, incl disc insulator, stay assembly clamp etc complete all as specified and directed. (Excavation earth work concrete shall measured & paid separately ) 5 Each
31 31 Supply , installing, testing of LT outdoor pillar box double door type with neoprene rubber gasket and locking arrangement vermin/ dust/ weather proof, self ventilation with wire mesh at suitable interval on both side, totally enclosed bus bar chamber fully comparted type, front openable hinged independent door for each compartment with locking arrangement and common openable hinged door from rear side of suitable size made out of 3.15 mm thick CRCA sheet duly powder coated paint, 415 volts, TPN, 50 Hz both sides properly welded MS angular supported with MS angle of size 50 x 50 x6mm 4 Nos, at all vertical comers grouted in PCC 1:3:6 type C-1 (using 20mm graded stone aggregate) and connecting the incoming/ out going feeders by providing cable glands and cable lugs complete all as specified and didrected compprising of following accessories. Make of Panel :- ABB/ Siemens/ L&T . Note :- Panel should be TTA in accordance with IEC 61439 . Minium size of panel (2200 x 600 x 800mm)\n(i) Incomer: ACB 4 Pole, 415 volt with thermal magnetic relesse (Manual fixed type) of capacity 630 Amps. Make :- Havells/ Stranderd/ L&T/ Indoasian.\n(ii) Bus Bars : 800A TPN + E aluminium busbars suitable for 50 KA for 1 Sec. Outgoing Feeders.\n(iii) 2 Nos 250 Amp 4P 25KA MCCB with adjustable thermal setting. (iv) 1 No 160 Amp 4P 25KA MCCB adjustable thermal setting. (v) 2 No 100 Amp 4P 25KA MCCB adjustable thermal setting. (vi) Volt meter 0 to 500 volts digital type with slector switch = 1 No.\n(vii) Ampere meter 0 to 500 Amp digital type slector - 1 No. (viii) Phase indicator lamp - Set of three.\n(ix) All connections from MCCBs to bus bar & bus bar to MCCB shall be made with suitable size of aluminium strip thimble lugs cost of which included in the quoted rate of item. (x) All acessories prewired with copper conductor cable single strand PVC insulated with copper thimbe lugs etc all as specified and directed (xi) Above all complete in all respect including installation of panel including supply and installation of frame pedestal 450 mm high above ground level\n 1 Each
32 32 Supply , installing, testing of LT outdoor pillar box double door type with neoprene rubber gasket and locking arrangement vermin/ dust/ weather proof, self ventilation with wire mesh at suitable interval on both side, totally enclosed bus bar chamber fully comparted type, front openable hinged independent door for each compartment with locking arrangement and common openable hinged door from rear side of suitable size made out of 3.15 mm thick CRCA sheet duly powder coated paint, 415 volts, TPN, 50 Hz both sides properly welded MS angular supported with MS angle of size 50 x 50 x6mm 4 Nos, at all vertical comers grouted in PCC 1:3:6 type C-1 (using 20mm graded stone aggregate) and connecting the incoming/ out going feeders by providing cable glands and cable lugs complete all as specified and didrected compprising of following accessories. Make of Panel :- ABB/ Siemens/ L&T . Note :- Panel should be TTA in accordance with IEC 61439 . Minium size of panel (2200 x 600 x 800mm)\n(i) Incomer: 1 No MCCB 500A, 4 Pole, 35 KA with adjustable thermal setting (as incoming).\n(ii) Bus Bars : 600A TPN + E aluminium busbars suitable for 50 KA for 1 Sec. Outgoing Feeders.\n(iii) 1 Nos 250 Amp 4P 25KA MCCB with adjustable thermal setting. (iv) 1 No 160 Amp 4P 25KA MCCB adjustable thermal setting. (v) 2 No 100 Amp 4P 25KA MCCB adjustable thermal setting. (vi) Volt meter 0 to 500 volts digital type with slector switch = 1 No.\n(vii) Ampere meter 0 to 500 Amp digital type slector - 1 No. (viii) Phase indicator lamp - Set of three.\n(ix) All connections from MCCBs to bus bar & bus bar to MCCB shall be made with suitable size of aluminium strip thimble lugs cost of which included in the quoted rate of item. (x) All acessories prewired with copper conductor cable single strand PVC insulated with copper thimbe lugs etc all as specified and directed (xi) Above all complete in all respect including installation of panel including supply and installation of frame pedestal 450 mm high above ground level.\n 1 Each
33 33 Supply , installing, testing of LT outdoor pillar box double door type with neoprene rubber gasket and locking arrangement vermin/ dust/ weather proof, self ventilation with wire mesh at suitable interval on both side, totally enclosed bus bar chamber fully comparted type, front openable hinged independent door for each compartment with locking arrangement and common openable hinged door from rear side of suitable size made out of 3.15 mm thick CRCA sheet duly powder coated paint, 415 volts, TPN, 50 Hz both sides properly welded MS angular supported with MS angle of size 50 x 50 x6mm 4 Nos, at all vertical comers grouted in PCC 1:3:6 type C-1 (using 20mm graded stone aggregate) and connecting the incoming/ out going feeders by providing cable glands and cable lugs complete all as specified and didrected compprising of following accessories. Make of Panel :- ABB/ Siemens/ L&T . Note :- Panel should be TTA in accordance with IEC 61439 . Minium size of panel (2200 x 600 x 800mm)\n(i) Incomer: 1 No 160A, 4 Pole, 25 KA with adjustable thermal setting (as incoming).\n(ii) Bus Bars : 300A TPN + E aluminium busbars suitable for 25 KA for 1 Sec. Outgoing Feeders.\n(iii) 1 Nos 160 Amp 4P 25KA MCCB with adjustable thermal setting. (iv) 2 No 100 Amp 4P 25KA MCCB adjustable thermal setting. (v) Volt meter 0 to 500 volts digital type with slector switch = 1 No.\n(vi) Ampere meter 0 to 200 Amp digital type slector - 1 No. (vii) Phase indicator lamp - Set of three.\n(viii) All connections from MCCBs to bus bar & bus bar to MCCB shall be made with suitable size of aluminium strip thimble lugs cost of which included in the quoted rate of item. (x) All acessories prewired with copper conductor cable single strand PVC insulated with copper thimbe lugs etc all as specified and directed (xi) Above all complete in all respect including installation of panel including supply and installation of frame pedestal 450 mm high above ground level.\n 1 Each
34 34 M&L steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9.00 meters long) complete all as specified and directed. 4 Each
35 35 Supply and erecting in vertically prestressed concrete pole LT pole 9.0 mtr long 102 x 172mm at top and 102mm x 279mm at bottom class 10 all as specified and directed. 6 Each
36 36 Supply and fixing shackle type insulator porcelain vitrous white, brown or green insulator incl galvanised mild steel straps washers insulators bolts washers of size 75x90 mm all as specified and directed. 50 Each
37 37 S&F ACB 4 pole, 415 volt, with thermal magnetic release (Manual fixed type) of capacity 630 Amps. Make :- Havells/ Standard/ L&T/ Indoasian. 2 Each
38 38 S&F MCCB 500 Amp 36 KA 415 volt FP. Make :- C&S or equvalent in Legrand/ ABB/ L&T/ Indo Asian/ Havells. 1 Each
39 39 S & F MCCB 400 Amp 35 KA 415 volt FP. Make :- C&S or equvalent in Legrand/ ABB/ L&T/ Indo Asian/ Havells. 2 Each
40 40 S & F MCCB 315 Amp 35 KA 415 volt FP. Make :- C&S or equvalent in Legrand/ ABB/ L&T/ Indo Asian/ Havells. 3 Each
41 41 S & F MCCB 250 Amp 35 KA 415 volt FP. Make :- C&S or equvalent in Legrand/ ABB/ L&T/ Indo Asian/ Havells. 3 Each
42 42 S & F MCCB 100 Amp 16 KA, 415 volt FP. Make :- C&S or equvalent in Legrand/ ABB/ L&T/ Indo Asian/ Havells. 5 Each
43 43 S&F MCCB 250 Amp 25 KA 415 volt FP with enclosure for fixing the MCCB independently whereeve required including necessary connections. Make :- C&S or equivalent in Legrand/ ABB/ L&T/ Indo Asian/ Havells. 2 Each
44 44 S&F MCCB 160 Amp 25 KA 415 volt FP with enclosure for fixing the MCCB independently whereeve required including necessary connections. Make :- C&S or equivalent in Legrand/ ABB/ L&T/ Indo Asian/ Havells. 2 Each
45 45 S&F MCCB 100 Amp 25 KA 415 volt FP with enclosure for fixing the MCCB independently whereeve required including necessary connections. Make :- C&S or equivalent in Legrand/ ABB/ L&T/ Indo Asian/ Havells. 2 Each
46 46 M&L for LT cable straight through joint kit of size 240 sqmm 3.5 core complete all as specified and directed 2 Each
47 47 M&L for LT cable straight through joint kit of size 185 sqmm 3.5 core complete all as specified and directed 3 Each
48 48 M&L for LT cable straight through joint kit of size 150 Sqmm/ 120 Sqmm 3.5 core complete all as specified and directed 3 Each
49 49 M&L for LT cable straight through joint kit of size 95 Sqmm 3.5 core complete all as specified and directed 3 Each
50 50 M&L for LT cable end joint kit of size 240 Sqmm 3.5 core complete all as specified and directed 2 Each
51 51 M&L for LT cable end joint kit of size 185 Sqmm 3.5 core complete all as specified and directed 3 Each
52 52 M&L for LT cable end joint kit of size 150 Sqmm / 120 Sqmm 3.5 core complete all as specified and directed 3 Each
53 53 M&L for LT cable end joint kit of size 95 Sqmm 3.5 core complete all as specified and directed 3 Each
54 54 M&L for reflective tape Red and Yellow colour 50mm Red. Note : 2 run of yellow colour and 1 run of red colour will be considered as one run all as specified and directed. 200 RM
55 55 M&L for synthetic chequered insulated mat, ISI marked of size 2m x 1m x 19mm conforming to IS-15652/2006 4 RM
56 56 Cutting/ trimming of tree branches of any width/ girth upto 3 mtr distance on both sides of HT/LT over load lines including collection and depositing the retrived timber at a place as directed by Engr-in-Charge. Note :- (i) Each span have a distance 50 mtr approximately. (ii) All cutting branches of tree shall be thrown away/ burnt at approximately 200 to 500 mtr away as directed. 200 Each Span
57 57 Repair and maintenance of Air circuit breaker by disconnecting the breaker form existing position and replacement the defective minor parts with new one i.e trippling coil, spring , holder, push button etc and checking for smooth functioning after installation at existing position all as directed by Engineer-in-Charge. 3 Each Job
58 58 M&L for repairing of LT pannel of any make type/ size an including Gas/ Arc welding, fill up rusted patches with 3mm MS sheet lugs, Lt aluminium conductor cable lead and bus bar of suitable capacity, front and rear door lock set replace, RYB and black colour wise insulation tape for bus bar, nut bolt, washers , hinges, grinding and scraping of old paint/ rust etc by wire bursh from body of LT pannel and apply base material for smooth surface and applying 2 coat of synthetic enameled spray paint over one coat of primer after denting etc complete all as specified and directed by Engineer-in-Charge. 6 Each Job
59 59 M&L Earthing complete with galvanized steel earth plate electrode 600cmx600cmx6mm thick burried directly in ground ( earth pit not less than 2.25 mtr deep below the ground level) with edge of the plate not less then 1.5 mtr below the ground level, connection to GI galvanised iron strip 25mm x 4mm as earthing lead by means of bolts/ nut & washers of GI or steel all shown in electrical plate No 5 of SSr Part-I connection to feeder piller all as specified including watewring GI Pipe 40mm bore medium grade PCC chamber using PCC 1:3:6 type C2 C1 cover funnel & wire mesh complete all as specified and directed by Engineer-in-Charge.\n 8 Each
60 60 M & L of painting to LT/HT steel tublar pole with one coat of aluminium paint complete above ground level including all MS fitting street light brackets MS flate angle iron GI pipe etc and numbering of poles as marked by existing number with correct size including removing and cleaning of old panted surface all as specified and directed 100 Each
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail