Supply Installation Testing Commissioning Of Fire Detection System Const . Of G Plus 1 Storied Gamma Knife Neurosurgery Building Within The Campus Of Ipgmer_Sskm Hospital Electrical Installation Work And Other Utility Services_Sitc Of Fire Detection Sys, Kolkata-West Bengal

Public Works Department-PWD has published Supply Installation Testing Commissioning Of Fire Detection System Const . Of G Plus 1 Storied Gamma Knife Neurosurgery Building Within The Campus Of Ipgmer_Sskm Hospital Electrical Installation Work And Other Utility Services_Sitc Of Fire Detection Sys. Submission Date for this Tender is 06-11-2020. Flame Detectors Tenders in Kolkata West Bengal. Bidders can get complete Tender details and download the document.




Tender Notice

25650408
Supply Installation Testing Commissioning Of Fire Detection System Const . Of G Plus 1 Storied Gamma Knife Neurosurgery Building Within The Campus Of Ipgmer_Sskm Hospital Electrical Installation Work And Other Utility Services_Sitc Of Fire Detection Sys
Open Tender
Indian
West Bengal
Kolkata
06-11-2020

Tender Details

Supply Installation Testing Commissioning Of Fire Detection System Const . Of G Plus 1 Storied Gamma Knife Neurosurgery Building Within The Campus Of Ipgmer_Sskm Hospital Electrical Installation Work And Other Utility Services_Sitc Of Fire Detection System

Key Value

Document Fees
Refer document
EMD
INR 6078.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: Construction of (G+1) storied Gamma Knife Neurosurgery Building within the campus of IPGMER-SSKM Hospital, Electrical installation work and other utility services-SITC of Fire Detection System.
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Supply, Installation,Testing & Commisioning of Microprocessor based Intelligent, soft addressable, ( VDS / UL / FM / ULC approved ), ethernet ready fire alarm control panel, with each loop capable of taking minimum 120 devices. The panel shall be able to give pin point location of all fire/ fault conditions. The Panel should be able to store minimum 1000 log events in its Memory as per recommended standards. Item1
2 1.01 The panel shall have in-built rectifier, Loop cards, interface card for connecting external serial printer, 4 line, 40 charecter/line alphanumeric LCD unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working or capable of operating the system for 2 hours during alarm condition, with integral battery charger complete as required. The panel shall have extra loop card to serve as stand by in case of burntout or malfunctioning of any operating loop cards. The FACP shall be capable of being networked with other similar FACP located at different part of the premises through ethernet (LAN). The panel should have necessary Ethernet card installed in it for bidirectional communication with 3rd party BMS/Scada and 3rd party public address system. All necessary memory map (incl. device address) should be provided. Minimum 4 potential free spare contacts should be provided with the panel.\nThe system must be preloaded with licenced software. ( Approved Make: Esser/Cerberus Pro/Secutron/ Notifer / Edward / Bosch / Apollo / Morley / System Sensor / Johnson Controls / Securiton). Item2
3 1.02 2 Loops control panel Item3 1 Set
4 2 Supply, Installation, Testing & Commissioning of Analog Addressable Intelligent multisensor detector ( VDS / UL / FM / ULC approved ) with two inbuilt optical smoke sensors with backward & forward scattering light angles as well as additional heat detectors sensor with decentralize intelligence, soft addressable Photothermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard. [Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended standards ) without any additional cost].(Approved Make: Esser/Cerberus Pro/Secutron/ Notifer / Edward / Bosch / Apollo / Morley / System Sensor / Johnson Controls / Securiton) Item4 34 Nos
5 3 Supplying, installation, testing and commissioning of soft Addressable Heat Detector (Fixed temperature cum rate of rise) with twist lockable removal base, built - in fault isolator, drift compensation feature etc including connections as per specifications complete as reqd and having IP as per recommended standard [Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for each addressable devices (Numbers of addressable devices in a group will be as per latest recommended standards ) without any additional cost]. (Approved Make: Esser/Cerberus Pro/Secutron/ Notifer / Edward / Bosch / Apollo / Morley / System Sensor / Johnson Contros/ Securiton ) Item5 3 Nos
6 4 Supply, Installation,Testing & Commisioning of soft Addressable Manual Call Point ( VDS / UL / FM / ULC approved )soft addressable type with in built fault isolator as per NFPA style 7 wiring complete as required. (Approved Make: Esser/Cerberus Pro/Secutron/ Notifer / Edward / Bosch / Apollo/ Morley / System Sensor / Johnson Controls / Securiton ). Item6 3 Nos
7 5 Supply, Installation, Testing & Commissioning of soft Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd)complete with inbuilt isolator & IP65 base ( VDS / UL / FM / ULC approved) . (Approved Make: Esser/Cerberus Pro/Secutron/ Notifer / Edward / Bosch / Apollo / Morley / System Sensor /Johnson Controls / Securiton ). Item7 3 Nos
8 6 Supply, Installation, Testing & Commissioning of soft Addressable transponder/ Monitor Modules (1 in and 1 out) ( VDS / UL / FM / ULC approved ) for monitoring flow switches/Fire exit doors / AHU / Lift etc complete as required. ( Approved Make: (Approved Make: Esser/Cerberus Pro/Secutron/ Notifer / Edward / Bosch / Apollo / Morley / System Sensor / Johnson Controls/ Securiton ). Item8 3 Nos
9 7 Supply, Installation, Testing & Commissioning of Addressable Relay Modules (VDS / UL & FM approved) for switching / integration of Lift / AHU etc complete as required. Item9 4 Nos
10 8 Supplying, installation, testing and commissioning of LED type Response Indicator ( VDS / UL / FM / ULC approved) having red coloured LED lamps including connections etc.( Approved Make: Esser/Cerberus Pro/Secutron/ Notifer / Edward / Bosch / Apollo / Morley / System Sensor /Johnson Controls/ Securiton ). Item10 20 Nos
11 9 Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex / Polycab / RR Kabel) with 20 mm NB PVC rigid conduit pipe MMS (Make: Precisson / Polycab) on the surface of the wall. Item11 345 Mtrs
12 10 Supply, Installation, Testing & Commissioning of Power supply 230 V AC to 24V DC with all other accessories. (Make: Reputed) Item12 4 Nos
13 11 NOTE : 1. The Fire Alarm system shall comply with latest requirements of -- 1. National Fire Protection Association (NFPA) Standards. 2. IS 2189 3. NFPA 70 National Electric Code 4. NFPA 72 National Fire Alarm Code 5. local Statutory Regulations 6. Manufacturer Recommendation. Item13
14 12 TESTS:\n1.The system shall be tested and commissioned by a qualified competent, trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system under active monitoring of OEM. \n2. Before energizing the cables and wires, check for correct connections and test for short circuits, ground faults, continuity, and insulation and other tests as per above standards must be done. Before taking up the work necessary building drawing/ floor plan with layout should be prepared and to be approved from the appropriate authority of PWD according to the prevailing fire safety policy. After commissioning, necessary testing to be done in presence of the appropriate authority of PWD. Item14
15 13 Terms and condition Item15
16 14 The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. Item16
17 15 Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill. Item17
18 16 If any refurbished material is supplied and installed, penal action will be taken as per existing rules Item18