Repair And Maintenance Of Ht / Lt Switch Gears , Transformers And Connected Accessories At Tibri Mil Stn Under Ge Gurdaspur, Gurdaspur-Punjab

Military Engineer Services-MES has published Repair And Maintenance Of Ht / Lt Switch Gears , Transformers And Connected Accessories At Tibri Mil Stn Under Ge Gurdaspur. Submission Date for this Tender is 27-10-2020. Switch Gear Tenders in Gurdaspur Punjab. Bidders can get complete Tender details and download the document.




Tender Notice

25617808
Repair And Maintenance Of Ht / Lt Switch Gears , Transformers And Connected Accessories At Tibri Mil Stn Under Ge Gurdaspur
Open Tender
Indian
Punjab
Gurdaspur
27-10-2020

Tender Details

Repair And Maintenance Of Ht / Lt Switch Gears , Transformers And Connected Accessories At Tibri Mil Stn Under Ge Gurdaspur

Key Value

Document Fees
INR 500 /-
EMD
INR 70000.0 /-
Tender Value
INR 35 Lakhs /-

BOQ Items

Name of Work: Repair and Maint of HT/LT switch gears, transformers and connected accessories at Tibri Mil Stn under GE Gurdaspur
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Taking down the defective unserviceable transformer from existing site from pole and Sub Stn with the help of man power & chain pully block or by crane etc including disconnecting all electrical and mechanical connections from the site and carrying to workshop for repair and replacement of old burnt u/s items as well as winding etc including transporting of capacity 50 KVA to 100 KVA Transformer (including 100 KVA) 4 Each Job
2 2 All as per srl item No.1 here in before but 125 KVA to 250 KVA (including 250 KVA). 3 Each Job
3 3 All as per srl item No.1 here in before but 315 KVA to 415 KVA (including 415 KVA).. 4 Each Job
4 4 All as per srl item No.1 here in before but 500 KVA to 750 KVA. 1 Each Job
5 5 Opening Dismantling the transformer of capacity 50 KVA to 100 (including 100 KVA capacity of transformers ) KVA by lifting the top cover taking out the HT/LT core and draining out the transformer oil in clean barral including cleaning the transformer chamber (body) inside and out side throwly with emery paper and cloth than checking the winding and other worn-out parts such as HT/LT coils silicor stamping and other connected items as Tap-changer, breather assembly etc and replacement of HT and LT coil winding with DPC enamelled copper/Aluminimu wire/ strip of edequate size guage and number of turn complete and connected to existing serviceable strip by jointing with soldring and re insulated of cotton tape over strip including using insulating material like varnish to limb coil fire proof type and sleeves etc by drying and baking of Insulating material in heating chamber in adequate temprature Reassenbling the transformer LT/HT connection with help of soldering..Testing of transformer after reassembly complete on No load at wkshop and on load at site incl painting to the transformer with super enammed paint all as specified anddirected. \nNote :- HT/LT coils and other connected items shall be measured & paid seperately. 4 Each Job
6 6 All as per srl item No.5 here in before but 125 KVA to 250 KVA. 3 Each Job
7 7 All as per srl item No.5 here in before but 300 KVA to 415 KVA. 4 Each Job
8 8 All as per srl item No.5 here in before but 500 KVA to 750 KVA. 1 Each Job
9 9 HT/LT coil winding with super enamelled copper wire/ strip of existing size & guage for winding the transformer HT/LT coils incl insulating materials all as specified and directed . 900 Kg
10 10 HT/LT coil winding with DPC or enamelled aluminium strip /wire of existing size & guage for winding the transformer coil HT/LT coils all as specified and directed . 300 Kg
11 11 Supply in replacement of HV bush Insulator complete with rod as per existing material & size and nut suitable for indoor/outdoor type transformer 50 KVA To 100 KVA . 8 Each
12 12 All as per srl item No.11 here in before but 125 KVA to 250 KVA. 6 Each
13 13 All as per srl item No.11 here in before but 300 KVA to 415 KVA. 6 Each
14 14 All as per srl item No.11 here in before but 500 KVA to 750 KVA. 4 Each
15 15 Supply and fix in replacement of LV bush Insulator complete with rod as per existing material & size and nut suitable for indoor/outdoor type transformer 50 KVA To 100 KVA makes witch gear Ltd. 8 Each
16 16 All as per srl item No.15 here in before but 125 KVA to 250 KVA. 6 Each
17 17 All as per srl item No.15 here in before but 300 KVA to 415 KVA. 6 Each
18 18 All as per srl item No.15 here in before but 500 KVA to 750 KVA. 4 Each
19 19 Supply and fix in replacement of tap changer for adjusting the voltage with brass parts as per sample of existing for indoor/ outdoor type transformer 50 KVA To 100 KVA all as specified and directed. 1 Each
20 20 All as per srl item No.19 here in before but 125 KVA to 250 KVA. 2 Each Job
21 21 All as per srl item No.19 here in before but 300 KVA to 415 KVA. 1 Each Job
22 22 All as per srl item No.19 here in before but 500 KVA to 750 KVA. 2 Each Job
23 23 Supply and fix in replacement of silica gel in breather assembly different capacity of transformer all as directed by Engineer in charge 50 Kg
24 24 Supply and fixing breather assembly complete of any type and capacity of transformer all as directed. 6 Each
25 25 Supply and fixing of the temperature gauge of the different type and capacity of tranformer all as directed 20 Each
26 26 Comprehensive maintenance of 66/11KV sub station equipment including replacement of unserviceable parts of following equipments all as specified and directed and testing by Punjab State Power Corporation Limited (PSPCL) authorised personal:-\n(a) Transformer 66/11 KV 8 MVA - 01 No\n(b) Transformer 66/11KV 5 MVA - 01 No \n(c) 66 KV SF-6 based Breakers 02 Nos \n(d) VCBs / OCBs- 12 Nos and any other relevant HT equipment.\nNotes:- \n(a) Checking of 11 KV functioning of all the tripping system / relay displayed on the control relay panel - such as differential O/C, earth fault, metering circuits and all othe protection from transformer - oil temp, trip, OLTC trip, winding temp gauge trip, bucholz relay, inter trip etc calibration of all the relays complete for time observed with respect to time set primary injection of all the CTs (Periodicity of testing half yearly). Deposite the charges levied / charged by the PSPCL authority for calibration / checking the protection system of 66 KV system all as directed.\n(b) Greasing / oiling of all the moving parts \n(c) Operation / working of charging motor and limit switch \n(d) Any part / spares found defective during testing shall be repared / replaced for which payment shall be made separately against respective items of Sch 'A' \n(e) Test sheet shall be prepared as specified and made part of RARs & final Bill. \n(f) The equipments shall be tested twice, 1st test will be carried out within two months from the date of commencement of contract and second test after six months from the 1st test. Payment shall be released on receipt of results/reports from PSPCL \n 2 Each Job
27 27 Supply and fixing, in replacement, current transformer CT ratio 600 / 1A, VA 2.5 , 50 Hz class SP, Short Circuit Current Capacity 21.0 KA for 3 sec complete all as specified and directed. 3 Each
28 28 Supply and fixing, in replacement, Digital Amp meter 0-100 Amp complete all as specified and directed. Make: Schnider/Crompton/ Legrand. 4 Each
29 29 Supply and fixing in replacement Digital volt meter 0-500 Volts complete all as specified and directed. Make : Schnider/Crompton/ Legrand or equivalent model of makes specified in App 'B' 4 Each
30 30 Supply and fixing in replacement Digital volt meter 0-500 Volts working in 220 DC Volts complete all as specified and directed. Make : Schnider/Crompton/ Legrand. 1 Each
31 31 Supply and fixing in replacement Digital volt meter 0-66 KVolts complete all as specified and directed. Make : Schnider/Crompton/ Legrand/L&T 1 Each
32 32 Supply and fixing in replacement Digital volt meter 0-11 KVolts complete all as specified and directed. Make : Schnider/Crompton/ Legrand. 4 Each
33 33 Supply and fixing in replacement of earth fault/over current relay set complete all as specified and directed. Make : ABB/Socomec/GE/ACE/L&T 2 Set of three
34 34 Supply and fixing in replacement NDR relay of existing specifications complete all as specified and directed. Make : ABB/Socomec/GE/ACE/L&T 1 Each
35 35 Supply and fixing in replacement of safe high voltage tape roll complete all as specified and directed. 10 Each
36 36 Supply and fixing in replacement of PG clamp size 66 KV line Horizontal and Vertical type complete all as specified and directed. 10 Each
37 37 Supply and fixing Male - female clamp suitable for 66 KV line complete all as specified and directed. 6 Each
38 38 Repair of the gear assembly of SF6 breaker, by taking out the same and including transportation and replace the worn out parts / defective parts and commissioning the same including testing complete all as directed by Engineer-ini-charge 1 Each Job
39 39 Supply and fixing of 66/11KV HT side bushes of 8 MVA transformer all as directed 3 Each
40 40 Supply and fixing of 66/11KV LT side bushes of 8 MVA transformer all as directed 3 Each
41 41 Supply and filling of SF-6 gas all as directed and specified 10 KG
42 42 Supply and fixing of Cells of capacitor bank of capacity 137/150KVAR all as directed by Engineer in charge 24 Each
43 43 Supply and fixing of barrel fuses of capacitor bank all as specified and directed 4 Each
44 44 Supply and fixing of oil winding temp gauge of 8 MVA transformer all as directed by Engineer in charge 1 Each
45 45 Supply and fixing of cable jointing kit 11 KV (earthed) grade cable indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 240 sqmm to 300 sqmm all as directed 6 Each
46 46 Supply and fixing of coarse aggregate in 20mm graded in layers at Main Receiving Station and appliying of lime solution before laying of coarese aggregate all as directed by Engineer in charge 30 Cum
47 47 Opening Dismantling the transformer of capacity 50 KVA to 500 KVA for repairing of transformer oil lekage from the top cover and HT/LT bushes, by lifting the top cover and draining out the transformer oil in barral including cleaning the transformer chamber (body) inside and out side throughly with emery paper and cloth than checked the winding and other parts for smooth functioning and replacement of top cover and LT and HT bush gasket and reassenbling the transformer LT/HT connection with help of soldering..Testing of transformer after reassembly complete on No load and full load at site incl painting to the transformer with super enammed paint all as specified and directed. \nNote :- The job includes the cost of gasket set, LT / HT bushes, nuts, bolts, washers etc required for the complete job. Only transformer oil will be measured and paid separately. 10 Each Job
48 48 Opening Dismantling the power transformer of capacity 5MVA and 8 MVA for repairing of transformer oil lekage from the top cover and HT/LT bushes, by lifting the top cover and draining out the transformer oil in barral including cleaning the transformer chamber (body) inside and out side throughly with emery paper and cloth than checked the winding and other parts for smooth functioning and replacement of top cover and LT and HT bush gasket and reassembling the transformer LT/HT connection with help of soldering..Testing of transformer after reassembly complete on No load and full load at site incl painting to the transformer with super enammed paint all as specified and directed. \nNote :- The job includes the cost of gasket set, LT / HT bushes, nuts, bolts, washers etc required for the complete job. Only transformer oil will be measured and paid separately. 2 Each Job
49 49 Earthing complete with galvanized steel earth plate electrods of size 60cmx60cmx6mm thick burried directly in ground vertically(earth pit not less than 3.35 mtr deep below normal ground level) with top edge of the plate not less than 2.75 mtr below normal ground level connected to galvanized iron 32x6mm by means of bolts nuts check nuts and GI washers of Galvanised iron protected by steel pipe 15mm (light grade) all as shown in elecrrical plate No.5 of SSR Part-I and connecting to earthing test point (earth test point to be provided at 5 mtr distance from earth pit) and testing on completion including necessary excavation and earth work. The rate also include charcoal dust and comman salt in alternate layers 40 mm dia light grade GI pipe,funnel,wire mesh.concrete 1:3:6 type C-1 for pit and RCC pit cover. PCC pit shall be provided 50 cm away from earth pit and not on the earth pit itself. The extra cost of the watering pipe,bends,elbows shall be included in the unit rate.Note : RCC pit cover shall be precast of RCC 1:2:4type B-1 80mm thick reinforced with XPM weighing not less than 4 Kg/Sqm. 12 Each
50 50 Earthing complete with galvansed steel earth plates electrode 60cmX600cmX6mm thick burried directly in ground ( earth pit not less than 2.25 mtr deep below the ground level ) with edge of the plate not less then 1.5 mtr below the ground level connection to GI galvanised Iron strp 25mmX3mm as earthing lead by means of bolts/nuts chick nut & washers of GI or steel all ghown in electrical plate No 5 of SSR part I connection to feeder piller all as specified including watering GI pipe 40mm bore medium grade PCC chamber using PCC 1:3:6 type C2 C1 cover funnel & wire mesh all as specified & directed by Engr-in-charge 10 Each
51 51 Supply and fixing earthing galvanised iron strip of size 32 x 6 mm all as dircted by Engineer in charge 200 RM
52 52 M & L in replacement danger notice plate for HT pole of size 20 cm x 15cm of 1.6 mm thick mild steel sheet viterious enamaled white with letter figur and conventional skull and bones "DANGER" (English, Punjabi and Hindi) in signal red colour and fixed with MS clamps made of 25mm x 3mm MS flat Iron bolts nuts complete including two coat of aluminium paint over a coat of red oxide primer complete all as specified and directed. 80 Each
53 53 Anti climbing device spikes type fabricated out of MS Bar (round square and flat) including nuts, bolts washer and welding in two halves made to shape to suit the cross section of the pole. 1 Qtl
54 54 Surface dressing n.exc 15cm deep of soft/loose soil site clearance ground sub stn and E/M installation complete all as specified and directed. 5000 Sqm
55 55 M & L in replacement pin type insulator porcelain vetreous white brown or green including one galvanised metal steel spindle two galvanised iron washer and one galvanised iron nuts 150mm height and 150 mm dia 11000 volt grade all as specified and directed. 20 Each
56 56 Supply and fixing in replacement disc type insulator porcelein vitreous 145 mm high and 255 mm dia ball and socket type white/brown or green single disc assemblely for 11000 volt grade complete all as specified and directed. 20 Each
57 57 Dehydratin and filteratin of transformer oil at site by using dehydration machine and fiteration to be carried out till the time the dielectric strength reached to min 40 KV complete all as specified and directed. Note : The transformer dehydration machine shall be arrange/brought by contractor at site no extra amount paid to the contractor. 8500 Ltr
58 58 Material and labour for toping up of the transformer and new with T/Oil having dielectric strength not less than 40 KV. Make - Power/Savita/Powerking. 4000 Ltr
59 59 Material & labour painting to HT PCC pole with one coat of synthetic enamel paint upto1.5 meter length from the PCC coping with black and white strip of 30 cm each including one coat of aluminium paint to all MS fitting / work such as channels, angles, bracing of MS flat, nuts, bolts with washer, street light fitting brackets etc. and numbering of poles as per existing size & shape including removing and cleaning of old panted surface complete all as specified and directed. 100 Each
60 60 Material & labour for preparation of old painted steel and iron surfaces and painting to 4 pole structure PCC poles of height 11 metre, any type (double swan / single swan) with two coats of synthetic enamel paint upto 1.5 m height above from ground level (in yellow and black strips of 30 cm wide each) and applying two coats of aluminium paint above 1.5 m height of poles and cross arms, bracing, clamps, chanels etc and writing pole number with black synthetic enamel paint complete all as specified and directed. 20 Each Job
61 61 All as per Srl Item No 60.00 here-in-before but two poles structure 20 Each Job
62 62 Material & labour for painting to panels & feeder pillar box, any sizes, installed at 66 KV Sub Stn with two coats of super enamelled paint of approved colour with spray painting machine including preparation of the surface complete all as specified and directed. 10 Each Job
63 63 Material & labourfor painting to transformer rating 8 MVA and 5 MVA, out door type installed at 66 KV Sub Stn including mounting channels and connected accessories with two coats of super enamelled paint of approved colour spray painting machine including preparation of the surface complete all as specified and directed. 2 Each Job
64 64 Material & labourfor painting to transformer rating 50KVA to 500 KVA, out door/indoor type installed at different Sub Stn including mounting channels and connected accessories with two coats of super enamelled paint of approved colour spray painting machine including preparation of the surface complete all as specified and directed. 12 Each Job
65 65 Supply and fix, in replacement, maintenance free battery, 2 Volt 60 to 100 AH (as per sample/existing capacity) complete all as specified.\nMake:- Amron / Exide / Amco. 80 Each
66 66 Supply and fixing of alluminium strip of 50mm x 12mm including bending and fixing at the terminals of transformer LT side whereever directeed for connectin the outgoing cables lugs of different sizes all as directed by Enginer-in-charge 10 RM
67 67 Supply & fixing replacement brass nut bolts and washers off sizes as per samles for HT/LT side of transformers all as specified and directed 10 Kg
68 68 Repair & replacement of Current Transformer moulded in epoxy compound with dual ratio 30/15/5/5 Amps complite connection with Auto wire 2.5 sqmm including beading as per existing in VCB at site all as per specified and directed by Engneer- in - Charge. (Note-: Circuit diagram will be produce after fixing the CT in VCB at site. 1 Each set of 3
69 69 All as per Ser Item No 68 but ratio 20/10/5/5 Amps. 1 Each Job
70 70 Disconnecting of HT connections & DC connection from existing busbar carefully and other parts carefully incl taking down the VCB trolly complete & disconnect the male/female contacts & clean the busbar with carbon tetra cholride liquid throughly busbar spout, trolly spout applying a one coat of 11 KV insulation quoting as per sample on busbar, spouts & other connected parts & reassembling the same re-connecting the HT & DC connection complete in functional order incl testing on existing load all as specified & directed. 8 Each Job
71 71 Repair/replacementof 11 KV/110 volt 3 Phase 3 Limb 3 wire resin cast ,drawout type Potential transformer having 100 VA output at CL -0.5 Accuracy complete with HT & LT fuses riser connection, plug in chamber and Rail all as directed by Engineer in charge 1 Each set of 3
72 72 Repair/replacementof Vacuum intruppter/vacuum bottle Type WL 33379 25 KA/ asper sample all as specified. 1 Each set of 3
73 73 Suppy in replacement the existing U/S auto battery charger suitable for charging of 12V/24 V/36V batteries all as specified and directed. 8 Each Job
74 74 supply in replacement Relay over current C&R Panel 66 KV Sub Station Make : ABB type : 1 cm 21 P ,W.D: 4 K- 421256,A : 0.5-2.0 ,f-50 Hz, operating 220 voltage,as per sample all specified & directed by Engr-in-charge. 1 Each
75 75 Supply and fixing of protection cover for LT and HT side of the outdoor type transformer of any capacity, the protection cover should be made out of 3mm dia CRCA sheet in rectangular or square shape directed by engineer in charge of size not more than 1mtr x 1mtr and fixing the same cover by means of nuts, bolts, welding etc including applying one coat of red oxide and two coat of paint over the exposed surface of the box all as directed by Engineer in charge 5 Each JOb
76 76 M&L for crossarms in replacement , bracing, supports, clamps and brick plates, fabricated from staructural steel section including nut bolts washers including welding, bending , cold or hot drilling holes for bolts in any shape or size as indicated in drawings or as directed, including two coats of aluminium paint over a coat of red oxide all specified. 3 Qtl
77 77 Suplly and fixing of perforated type cable tray of size 300mm x 25mm for arrangement of the LT/HT cables and control cables in cable duct of the Main Receiving Station cable duct, disconnecting the control cable from existing position, fixing the cable trays and arrangement of the control cable on the tray all as directed by Engineer in charge 120 RM
78 78 Supply and fixing of Mild steel Chequre plate of 5mm thick or over in thickness of Gde Fe 410 W A quality as directed by Engineer-in-charge for using as cable trench plate all as directed 800 KG
79 79 Supply and fixing of XLPE insulated PVC Sheathed single core Aluminium unarmoured of 11000 Volts grade cable for using as a jumber in HT overhead line whereever required of size 95/120 sqmm all as directec by engineer in charge 180 RM
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail