Military Engineer Services-MES has published Comprehensive Repair And Maintenance Of Dg Sets , External Electrification Services , Earthing Pits And Certain E/M Maintenance Works At Vsn Chiloda. Submission Date for this Tender is 05-10-2020. Electromechanical Work Tenders in VAYU SHAKTI NAGAR CHILODA Gujarat. Bidders can get complete Tender details and download the document.
Name of Work: COMPREHENSIVE REPAIR AND MAINTENANCE OF DG SETS, EXTERNAL ELECTRIFICATION SERVICES, EARTHING PITS AND CERTAIN E/M MAINTENANCE WORKS AT VSN CHILODA | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Excavation in trenches not exceeding 1.5m width and not exceeding 1.5 m in depth and getting out in soft/loose soil for taking up/laying cable/pipe etc completed all as apecified and directed. | 145.8 | CUM | |
2 | 2 | M & L for dry Sand cushioning to underground cable with screened, washed river sand, including punning gently all as specified and directed.\nNote: - Thickness after punning will be measured for payment. | 43.74 | CUM | |
3 | 3 | Supply and lay burnt brick sub class `B' old size in trenches abouting each other width equal to length of brick etc complete as directed | 4.5 | 1000 NOS | |
4 | 4 | Returning, filling including spreading, leveling watering & well ramming in laying not exceeding 25cm for Soft/loose soil. | 117.36 | CUM | |
5 | 5 | Removal of excavated material at a distance not exc 50 mtr and dipositing where directed at a level not exc. 1.5 mtr above the starting point for Soft / loose soil. | 28.44 | CUM | |
6 | 6 | Laying only burnt bricks (old size) retrieved from item No.7,8 and 9, laid in trenches as cable protection complete. | 4 | PER 1000 NOS | |
7 | 7 | Labour only for boring under road/drain by manual method for inserting the light grade pipe GI tubing up to 50 mm dia for cable protection all as specified and directed by Engineer In Charge. | 24 | RM | |
8 | 8 | Supply and laying in trenches in road cross / floors tube galvanished iron light grade with all fittings for protection of cable of following dia/bore of pipe | |||
9 | 8.01 | 40 mm bore | 12 | RM | |
10 | 8.02 | 50 mm bore | 12 | RM | |
11 | 9 | Supply and lay in repairs and testing cable LT XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable heavy duty with stranded aluminum conductor, 1100 Volts grade, of size 25 Sqmm 4 Core.\nNote:-Excavation, earthwork, will be measured and paid separately under respective items of this Schedule. | 150 | RM | |
12 | 10 | All as per Item no.9.00 above, but cable of size 35 Sqmm 3.5 Core complete.\n | 150 | RM | |
13 | 11 | All as per Item no.9.00 above, but cable of size 50 Sqmm 3.5 Core complete.\n | 150 | RM | |
14 | 12 | All as per Item no.9.00 above, but cable of size 70 Sqmm 3.5 Core complete.\n | 150 | RM | |
15 | 13 | Repairs/ servicing to 1250 KVA DG set (Make- Cummins) including radiator servicing, intercooler servicing, general maintenance work such as belt, valve clearance, hose pipe set, bearing greasing connection of terminal ,replacement of the worn out spares and drain out engine oil from the sump, cleaning with kerosene oil and filling up with new engine oil as per recommended grade & quality, and testing for smooth running at rated speed complete all as per manufacturer’s specification and as directed by Engineer-in-charge.\n\n\n\n\n | 5 | VISITS | |
16 | 13.01 | Element Fuel filter | 2 | EACH | |
17 | 13.02 | Element lube Oil filter | 4 | EACH | |
18 | 13.03 | Corrossion inhibitor | 1 | EACH | |
19 | 13.04 | Fan Belt | 3 | NOS | |
20 | 13.05 | Main Supply fuel Pipe | 2 | NOS | |
21 | 13.06 | Set of O-Ring | 1 | EACH SET | |
22 | 14 | All as per item No.13.00 above, but for 82.5 KVA DG Set (for HQ SWAC AFNET and DSC Lift Make- Kirloskar) and consisting replacement of following parts:- | 10 | VISITS | |
23 | 14.01 | Element Fuel filter | 2 | EACH SET | |
24 | 14.02 | Element lube Oil filter | 2 | EACH SET | |
25 | 15 | All as per item No.13.00 above, but 82.5 KVA DG Set (for Telephone exchange HQ SWAC Make- Ashok Leyland) and consisting replacement of following parts:- | 5 | VISITS | |
26 | 15.01 | Element Fuel filter | 1 | EACH SET | |
27 | 15.02 | Element lube Oil filter | 1 | EACH SET | |
28 | 16 | All as per item No.13.00 above, but 82.5 KVA DG Set (for Alpha Block Officers Qtrs at S/Stn No.2 Make- Cummins) and consisting replacement of following parts:- | 5 | VISITS | |
29 | 16.01 | Element Fuel filter | 1 | EACH SET | |
30 | 16.02 | Element lube Oil filter | 1 | EACH SET | |
31 | 17 | All as per item No.13.00 above, but 200 KVA DG Set (for SWAC officers mess Make- Cummins) and consisting replacement of following parts:- | 5 | VISITS | |
32 | 17.01 | Element Fuel filter | 1 | EACH SET | |
33 | 17.02 | Element lube Oil filter | 1 | EACH SET | |
34 | 18 | All as per item No.13.00 above, but 200 KVA DG Set (for HQ SWAC B Wing Make- Greaves) and consisting replacement of following parts:- | 5 | VISITS | |
35 | 18.01 | Element Fuel filter | 1 | EACH SET | |
36 | 18.02 | Element lube Oil filter | 1 | EACH SET | |
37 | 18.03 | Air filter Inner | 1 | NOS | |
38 | 18.04 | Air filter Outer | 1 | NOS | |
39 | 19 | All as per item No.13.00 above, but 250 KVA DG Set (for HQ SWAC Server room C Wing Make- Greaves) and consisting replacement of following parts:- | 5 | VISITS | |
40 | 19.01 | Element Fuel filter | 1 | EACH SET | |
41 | 19.02 | Element lube Oil filter | 1 | EACH SET | |
42 | 19.03 | Air filter Inner | 1 | NOS | |
43 | 19.04 | Air filter Outer | 1 | NOS | |
44 | 20 | All as per item No.13.00 above, but 125 KVA DG Set (for STP and DSC P/H Make- Greaves) and consisting replacement of following parts:- | 10 | VISITS | |
45 | 20.01 | Element Fuel filter | 2 | EACH SET | |
46 | 20.02 | Element lube Oil filter | 2 | EACH SET | |
47 | 20.03 | Air filter Inner | 2 | NOS | |
48 | 20.04 | Air filter Outer | 2 | NOS | |
49 | 21 | All as per item No.13.00 above, but 10 KVA DG Set (for Sewage lifting pumps Make- Greaves) and consisting replacement of following parts:- | 10 | VISITS | |
50 | 21.01 | Element Fuel filter | 2 | EACH SET | |
51 | 21.02 | Element lube Oil filter | 2 | EACH SET | |
52 | 21.03 | Air filter Inner | 2 | NOS | |
53 | 21.04 | Air filter Outer | 2 | NOS | |
54 | 22 | All as per item No.13.00 above, but 380 KVA DG Set (for Neelamber Auditorium, MAP Guard room and MAP P/H Make- Cummins) and consisting replacement of following parts:- | 15 | VISITS | |
55 | 22.01 | Element Fuel filter | 3 | EACH SET | |
56 | 22.02 | Element lube Oil filter | 3 | EACH SET | |
57 | 22.03 | Air filter Inner/outer | 3 | NOS | |
58 | 22.04 | Coolant filter | 2 | NOS | |
59 | 23 | All as per item No.13.00 above, but 62.5 KVA DG Set (for type -II and III Make- Greaves) and consisting replacement of following parts:- | 10 | VISITS | |
60 | 23.01 | Element Fuel filter | 2 | EACH SET | |
61 | 23.02 | Element lube Oil filter | 2 | EACH SET | |
62 | 23.03 | Air filter Inner | 2 | NOS | |
63 | 23.04 | Air filter Outer | 2 | NOS | |
64 | 24 | All as per item No.13.00 above, but 62.5 KVA DG Set (for SWAC P/H Make- Kirloskar) and consisting replacement of following parts:- | 5 | VISITS | |
65 | 24.01 | Element Fuel filter | 1 | EACH SET | |
66 | 24.02 | Element lube Oil filter | 1 | EACH SET | |
67 | 24.03 | Air filter Inner | 1 | NOS | |
68 | 24.04 | Air filter Outer | 1 | NOS | |
69 | 25 | All as per item No.13.00 above, but 30 KVA DG Set (for perimeter security lights Make- Kirloskar) and consisting replacement of following parts:- | 5 | VISITS | |
70 | 25.01 | Element Fuel filter | 1 | EACH SET | |
71 | 25.02 | Element lube Oil filter | 1 | EACH SET | |
72 | 25.03 | Air filter Inner | 1 | NOS | |
73 | 25.04 | Air filter Outer | 1 | NOS | |
74 | 26 | All as per item No.13.00 above, but 125 KVA DG Set (for Neelamber Auditorium light load Make- Kirloskar) and consisting replacement of following parts:- | 5 | VISITS | |
75 | 26.01 | Element Fuel filter | 1 | EACH SET | |
76 | 26.02 | Element lube Oil filter | 1 | EACH SET | |
77 | 27 | All as per item No.13.00 above, but 35 KVA DG Set (for perimeter security lights at S/Stn No.2 and MES IB - Mahindra and consisting replacement of following parts:- | 10 | VISITS | |
78 | 27.01 | Element Fuel filter | 2 | EACH SET | |
79 | 27.02 | Element lube Oil filter | 2 | EACH SET | |
80 | 27.03 | Air filter Inner | 2 | NOS | |
81 | 27.04 | Air filter Outer | 2 | NOS | |
82 | 28 | All as per item No.13.00 above, but 250 KVA DG Set installed behind swimming pool Make-Kirloskar and consisting replacement of following parts:- | 5 | VISITS | |
83 | 28.01 | Element Fuel filter | 1 | EACH SET | |
84 | 28.02 | Element lube Oil filter | 1 | EACH SET | |
85 | 29 | All as per item No.13.00 above, but 140 KVA DG Set installed at station medicare centrer Make-Mahindra & Mahindra and consisting replacement of following parts:- | 5 | VISITS | |
86 | 29.01 | Element Fuel filter | 1 | EACH SET | |
87 | 29.02 | Element lube Oil filter | 1 | EACH SET | |
88 | 30 | All as per item No.13.00 above, but 250 KVA DG Set (MRS Make- Cummins) and consisting replacement of following parts:- | 10 | VISITS | |
89 | 30.01 | Element Fuel filter | 2 | EACH SET | |
90 | 30.02 | Element lube Oil filter | 2 | EACH SET | |
91 | 30.03 | Air filter Inner/outer | 2 | NOS | |
92 | 30.04 | Coolant filter | 2 | NOS | |
93 | 30.05 | O ring Prefilter | 2 | NOS | |
94 | 30.06 | Magnetic Pick Up unit | 2 | NOS | |
95 | 30.07 | Note: for item no 13 to 30:-\n (i) The contractor should carry out servicing through authorised DG Service provider & not by any local mechanic (ii) The contractor should be responsible to maintain the DG set in serviceable condition for entire contract period & additional worn out spare parts like O Rings, gasket, screws, fuel pipe, fuel & oil pressure gauge, fan belt etc if found unserviceable should be replaced by contractor without additional cost .(iii) Proper servicing certificate should be produced immediately after servicing (d) Proper register for running of DG set should be maintained (e) The authorised mechanic should visit once in two months for preventive maintenance & any no of emergency breakdown. (f) Total number of serevice visit will be limited upto 5 Nos during the entire contract period including attending any emergency fault in DG Set. | |||
96 | 31 | Supply only coolant for Cummins DG sets Make- Fleet Guard. | 200 | LTRS | |
97 | 32 | Supply only engine Oil 15W 40 Valvoline for all DG Sets | 600 | LTRS | |
98 | 33 | Supply, install,testing & commissioning in repairs exide battery 12 V, 130 AH.\nMake- AMCO/EXIDE/SUKAM/LUMINOUS | 2 | EACH | |
99 | 34 | Supply, install,testing & commissioning in repairs exide battery 12 V, 150 AH.\nMake- AMCO/EXIDE/SUKAM/LUMINOUS | 2 | EACH | |
100 | 35 | Supply, install, testing & commissioning in repairs controller- HMI211 including Display, replacing contactors/Connectors and making all electrical connections good and renewed for DG set 250 KVA (Make-Cummins) | 2 | EACH | |
101 | 36 | Supply, install, testing & commissioning in repairs controller- GC 1202 Auto Mains failure control Module including Display, replacing contactors/Connectors and making all electrical connections good and renewed for DG set 82.5 KVA (Make-Ashok Leyland) | 1 | EACH | |
102 | 37 | Supply, install, testing & commissioning in repairs controller- DSE 6120 Auto Mains failure control module including Display, replacing contactors/Connectors and making all electrical connections good and renewed for DG set 200 KVA (Make-Greaves) | 1 | EACH | |
103 | 38 | Supply, install, testing & commissioning in repairs controller- Procom DGC-6D Auto Mains failure control Module including Display, replacing contactors/Connectors and making all electrical connections good and renewed for DG set 200 KVA (Make-Greaves) | 1 | EACH | |
104 | 39 | Supply,install,testing & comissioning in repairs PLA relay 24 volt DC for DG set including making all electrical connections and checking by running the DG set for 02 hours. | 2 | EACH | |
105 | 40 | Supply,install,testing & comissioning in repairs PLA relay 110-220 volt AC for DG set including making all electrical connections and checking by running the DG set for 02 hours. | 2 | EACH | |
106 | 41 | Supply,install,testing & comissioning in repairs Battery charger 24 volt 10 Amp (Maxpower or equivelent) for DG set including making all electrical connections and checking by running the DG set for 02 hours. | 2 | EACH | |
107 | 42 | Supply,install,testing & comissioning in repairs SMPS Battery charger 12 volt 10 Amp (Maxpower or equivelent) for DG set including making all electrical connections and checking by running the DG set for 02 hours. | 2 | EACH | |
108 | 43 | Supply,install,testing & comissioning in repairs Automatic Voltage Regulator(AVR) for DG sets of capacity from 10 KVA upto 380 KVA of existing make including making all electrical connections and checking by running the DG set for 02 hours. | 2 | EACH | |
109 | 44 | Supply and fix in replacement of Copper Strip of size 20 X 3 mm buried/laid in trenches/fixed on wall/tower etc complete all as specified. | 10 | RM | |
110 | 45 | Supply and fix in replacement of Copper Strip of size 32 X 6 mm buried/laid in trenches/fixed on wall/tower etc complete all as specified. | 20 | RM | |
111 | 46 | M & L for copper brazing with copper strip/copper rod complete all as specified. | 10 | EACH | |
112 | 47 | M&L for earthing complete with galvanised steel earth plate electrode 60 x 60cm x 6.3mm burried directly in ground level with top edge of earth plate at a depth not less than 1.5m below ground level connected to and including galvanised iron strip 25 x 4 mm as earthing lead by means of bolts, nuts, check nuts and washers etc made of GI and connected to earthing test point all as shown in electric plate No.3 of SSR indicated and testing on completion including excavation and earth work in any type of soil/rock, PCC (1:3:6) type C-1 earthing chamber, precast RCC slab 50mm thick in cement concrete (1:2:4) type B-1 reinforce with welded steel wire babric (APM) weight not less than 4 Kg/Sqm, funnel with GI watering pipe of 20mm bore medium grade, wire mesh and lugs, GI protection pipe of 40mm bore medium grade 7.5 m long test point etc complete. | 6 | EACH SET | |
113 | 48 | All as per item No.47.00 above, but using copper plate 60 cm X 60 cm X 3.15 mm thick electrode and 20 X 3 mm copper strip as eathing lead including earth test point all as directed by Engr-In-Charge. (For Transformer Neutral). | 2 | EACH | |
114 | 49 | Supply and fix in replacement copper lead 35 Sqmm fixed with Copper terminal lugs and clamps plus minus for 12V lead acid battery all as specified and directed. \n | 4 | SET OF TWO | |
115 | 50 | M & L for Internal wiring with copper conductor incl necessary lugs and thimbles -01 Job | 4 | EACH | |
116 | 51 | M&L oil pressure gauge with oil sensor for 82.5/62.5/125/140/200/250/380 KVA DG set complete all as specified and directed. | 4 | EACH | |
117 | 52 | M&L solenoid switch for 82.5/62.5/125/140/200/250/380 KVA DG set complete all as specified and directed. | 2 | EACH | |
118 | 53 | M&L for fan belt for 82.5/62.5/125/140/200/250/380 KVA DG set complete all as directed and specified by Engr-in-charge.\nMake : FENNER/NISSAN/ARRORA | 4 | EACH | |
119 | 54 | M & L Fuel gauge with sensor suitable for 82.5/62.5/125/200/250/380 KVA DG set as per existing make of DG Set.\n | 4 | EACH | |
120 | 55 | Taking down of existing unserviceable Contactor of main supply from existing AMF Panel (behind swimming pool) including opening the existing cable coneections and connecting nut bolts and jointing accessoreis all as specified and directed by Engineer-In- Charge | 7 | EACH | |
121 | 56 | Supply, install, testing & commissioning in replacement of faulty TC contactor LC1FDP1154AEM5 AC-1 of 200 A, 415 Volt rated capacity with coil voltage 220 V 50 Hz DIN switch TA1 DN 22 and connected relays all as specified and directed by E-in-Charge | 1 | EACH | |
122 | 57 | Supply, install, testing & commissioning in replacement of faulty TC contactor MCX 46 of 100 A, 415 Volt rated capacity with coil voltage 220 V 50 Hz DIN switch TA1 DN 22 and connected relays all as specified and directed by E-in-Charge | 2 | EACH | |
123 | 58 | Supply, install, testing & commissioning in replacement of faulty TC contactor MNX 32 of 200 A, 415 Volt rated capacity with coil voltage 220 V 50 Hz DIN switch TA1 DN 22 and connected relays all as specified and directed by E-in-Charge | 2 | EACH | |
124 | 59 | Supply, install, testing & commissioning in replacement of faulty TC contactor MNX 33 of 200 A, 415 Volt rated capacity with coil voltage 220 V 50 Hz DIN switch TA1 DN 22 and connected relays all as specified and directed by E-in-Charge | 2 | EACH | |
125 | 60 | S&F in repair digital three phase voltmeter 0-500 volts of size 96x96mm complete all as specified and directed by Engr in Charge. \nMake :Ebrit/C&S/BHEL/ABB/SIEMENS | 2 | EACH | |
126 | 61 | S&F in repair digital three phase Ampere meter 0-500 volts of size 96x96mm complete all as specified and directed by Engr in Charge. Make : Ebrit/C&S/BHEL/ABB/SIEMENS | 2 | EACH | |
127 | 62 | S&F in repair digital AC three phase, 04 Wire Electronic KWH meter CT-2E LCD,240 volts, 50 Hz upto 15000 Imp/KWH, IEC 61036 all as specified and directed by Engr in Charge. \nMake :HPL/C&S/BHEL/ABB/SIEMENS | 2 | EACH | |
128 | 63 | S&F in repair digital AC three phase,Emfis HT Digital functionmeter 220/440 volts, 50 Hz all as specified and directed by Engr in Charge. \nMake :HPL/C&S/BHEL/ABB/SIEMENS | 2 | EACH | |
129 | 64 | Radiator cleaning -(washing and flushing ) with chemical & throughly Testing and flush that removes grease, scum, rust, scale and oil deposits and coolant restore flow etc. | 15 | EACH | |
130 | 65 | M & L for servicing of AMF Panels for DG Set including internal wiring connections, relay setting, setting of pick up time for auto start of DG Set, arranging the doors of panels by welding to the compartment, rearranging and tightening of lugs for cable connections, cleaning dust by vacumm cleaner, replacing the contactors for Main/DG Supply if found unserviceable under the respective item of this schedule testing the DG Set for auto/manual start by running the DG Set for 01 Hrs all as specified and directed by Eng-In-Charge Note : The additional cost for internal wiring, PCB service, lugs and programming of the ckt will be included in this item | 4 | EACH | |
131 | 66 | Supply and Laying 3 core flexible copper conductor cable of size 2.5 Sqmm dia. | 100 | RM | |
132 | 67 | Supply and fix Rigid Non metallic PVC Conduit of 40 mm dia exclusive of boxes but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock, nuts, saddles all as specified and directed | 50 | RM | |
133 | 68 | Supply and fix in repair off load change over switch of 400 Amp Capacity with sheet Steel enclosure all as specified and directed by Eng-In- Charge | 1 | EACH | |
134 | 69 | Supply and fix in repair off load change over switch of 200 Amp Capacity with sheet Steel enclosure all as specified and directed by Eng-In- Charge | 1 | EACH | |
135 | 70 | Supply and fix in repair off load change over switch of 100 Amp Capacity with sheet Steel enclosure all as specified and directed by Eng-In- Charge | 1 | EACH | |
136 | 71 | Supply & install, testing & commissioning in repairs LT feeder panel box compartmental type,Lockable fabrication with dimension 800(H) x 500(W) x 500(D) made by 3.15 mm thick sheet CRCA approved weather proof design framed on angle iron (40mmx40mmx6mm) double door front and rear openable both side opening shutters duly painted two coat with siemens gray color, cable entry with glands, foundation /grouting on & including PCC as per site requirement with the following :-\n(a)Automatic transfer Switch 125 Amp - 1 Nos (b)MCB SPN DP 16 Amp, - 2 Nos(Outgoing)\n(c)Internal wiring 4 Sqmm copper wire (d) indicating Lamp LED type R,Y,B - 3 Nos (e) Voltmeter 0-500 Volt-01 Nos f) Amperemeter 0-500 Amps-01 Nos | 2 | EACH | |
137 | 72 | Supply & install, testing & commissioning in repairs LT feeder panel box compartmental type,Lockable fabrication with dimension 800(H) x 500(W) x 500(D) made by 3.15 mm thick sheet CRCA approved weather proof design framed on angle iron (40mmx40mmx6mm) double door front and rear openable both side opening shutters duly painted two coat with siemens gray color, cable entry with glands, foundation /grouting on & including PCC as per site requirement with the following :-\n(a)Automatic transfer Switch 200- Amp - 1 Nos (b)MCB SPN DP 16 Amp, - 2 Nos (Outgoing) (c)Internal wiring 4 Sqmm copper wire (d) indicating Lamp LED type R,Y,B - 3 Nos (e) Voltmeter 0-500 Volt-01 Nos (f) Amperemeter 0-500 Amps-01 Nos | 2 | EACH | |
138 | 73 | Supply & install, testing & commissioning in repairs LT feeder panel box compartmental type,Lockable fabrication with dimension 800(H) x 500(W) x 500(D) made by 3.15 mm thick sheet CRCA approved weather proof design framed on angle iron (40mmx40mmx6mm) double door front and rear openable both side opening shutters duly painted two coat with siemens gray color, cable entry with glands, foundation /grouting on & including PCC as per site requirement .including indicator lamps voltmeter and amperemeter with one set of Aluminium Bus bar 200 Amp Cap and fixing the existing change over switches into that Panel box and making all incoming outgoing electrical cable connections good by fitting new lugs all as specified and directed by Eng-In-Charge\n\n | 2 | EACH | |
139 | 74 | S & F in repair glass sheet of existing size for AMF Panels display board all fitted with glass beeding ensuring the clear visibility of electrical data all as specified and directed | 6 | EACH | |
140 | 75 | Comprehensive maintenance of sliding doors including greasing and oiling of rack and pinion gears and wheels of doors, and replacing the wheels and supportiong rollers if found unservceable at HQ SWAC all as specified and directed by Eng-In-Charge | 4 | EACH JOB | |
141 | 76 | M & L for servicing of LT Control panels of sliding doors including wiring and making all electrical connections good and tight to avoid chances of any shortcircuiting and replacing the faulty PCB, sensors and relays and making functional all sensors to control any obstruction in between in moving door if found unservceable at HQ SWAC all as specified and directed by Eng-In-Charge | 4 | EACH JOB | |
142 | 77 | M&L for taking out & rewinding the existing unserviceable burnt motors of Sliding Doors of Cap 03 HP,Three phase, 50 cycles by disconnecting electrically and mechanically and transporting to the locally workshop. Dismantling the motor and removing the old burnt copper winding & demoisturise, cleaning, rewinding the coils with same gauge supper enamelled copper wire, with suitable F class paper insulation, varnishing, and reassembling by replacing bearings reinstalling at the installation and testing, commissioning etc complete.\n | 4 | EACH JOB | |
143 | 78 | M&L for servicing of Sliding door motors of Cap- 3 HP operated on 240V, 50 Hz with replacing of box set-04 nos, mechanical seal -01 no, cut off switch 01 no, bearing 02 nos, Air filling in tank complete as per site requirement or as directed by Engr-in-charge. | 4 | EACH | |
144 | 79 | M&L for servicing of Sliding door gear boxes by replacing of oil seal-02 nos, mechanical seal -01 no, refilling of lubrication oil 15W40, bearing 02 nos,complete as per site requirement or as directed by Engr-in-charge. | 4 | EACH | |
145 | 80 | S & F in repair MS Support Rollers for sliding doors at HQ SWAC Chiloda proper support of sliding doors all as specified and directed by Engr-in-charge. | 4 | EACH | |
146 | 81 | S & F in repair rack of sliding doors with milled/hobbed gear tooths as existing pattern and welding the rack to the Gates at HQ SWAC Chiloda for proper movement of pinion over the rack so that any chances for sliping may get avoided complete all as specified and directed by Engr-in-charge. | 5 | RM | |
147 | 82 | Supply and Fix in repair MS gears wheel of Dia upto 80 mm with hobbed/milled spur gear tooths and fixing to the motor shafts by inserting sunk key and making provision for key way complete all as specified and directed by Eng-In-Charge | 2 | EACH | |
148 | 83 | Disconnecting terminals of HT cable and locating pin point fault in HT cable 11000 Volts grade of any size including to and fro hire charge of special T & P all as directed by the Engr-in-Charge. | 4 | EACH JOB | |
149 | 84 | Disconnecting terminals of LT cable of any size and locating pin point fault in LT cable 1100 Volts grade of any size including to and fro hire charge of special T & P all as directed by the Engr-in-Charge. | 4 | EACH JOB | |
150 | 85 | S&F in repair cable jointing kit for 11000 volts grade cable for straight through joints, heat shrinkable type joint complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 120 Sqmm to 185 Sqmm 3 core. | 2 | EACH | |
151 | 86 | S&F in repair cable jointing kit for 11000 volts grade cable for straight through joints, heat shrinkable type joint complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 240 Sqmm to 400 Sqmm 3 core. | 1 | EACH | |
152 | 87 | S&F in repair cable jointing kit epoxy type for 1100 volts grade cable for straight through joints with jointing material and accessories suitable for LT armoured aluminium conductor cable of size 95 Sqmm 3.5 core. | 2 | EACH | |
153 | 88 | All as per Item no 87.00 above, but cable jointing kit for LT armoured aluminium conductor cable of size 70 Sqmm 3.5 core. | 2 | EACH | |
154 | 89 | All as per Item no 87.00 above, but cable jointing kit for LT armoured aluminium conductor cable of size 50 Sqmm 3.5 core. | 2 | EACH | |
155 | 90 | All as per Item no 87.00 above, but cable jointing kit for LT armoured aluminium conductor cable of size 35 Sqmm 3.5 core. | 2 | EACH | |
156 | 91 | All as per Item no 87.00 above, but cable jointing kit for LT armoured aluminium conductor cable of size 25 Sqmm 4.0 core. | 2 | EACH | |
157 | 92 | All as per Item no 87.00 above, but cable jointing kit for LT armoured aluminium conductor cable of size 16 Sqmm 4.0 core. | 2 | EACH | |
158 | 93 | M & L for danger notice plate of 1.6 mm thick mild steel sheet viterous enammeled white with letters figures and conventional skulls and bones in single red colour and fixed with MS Clamps, bolts and nuts of approved size for LT 20 X 15 CM Size | 4 | EACH | |
159 | 94 | M & L for danger notice plate of 1.6 mm thick mild steel sheet viterous enammeled white with letters figures and conventional skulls and bones in single red colour and fixed with MS Clamps, bolts and nuts of approved size for HT 25 X 20 CM Size | 4 | EACH | |
160 | 95 | Disconnecting the existing Unserviceable MCCB from the cable, taking out from the panel board and S&F new MCCB triple pole with neutral, 250 Amps, 35 / 36 KA breaking capacity suitable for 415 Volt, 50 Hz, 3 phase supply, fixed in existing panel and connecting with existing cable, including nuts, bolts and washer etc complete. | 1 | EACH | |
161 | 96 | All as per Item no 95.00 above, but for MCCB 200 Amps complete. | 1 | EACH | |
162 | 97 | All as per Item no 95.00 above, but for MCCB 160 Amps 35 KA breaking capacity complete. | 1 | EACH | |
163 | 98 | All as per Item no 95.00 above, but for MCCB 125 Amps 35 KA breaking capacity complete. | 1 | EACH | |
164 | 99 | All as per Item no 95.00 above, but for MCCB 125 Amps 25 KA breaking capacity complete. | 1 | EACH | |
165 | 100 | All as per Item no 95.00 above, but for MCCB 100 Amps 35 KA breaking capacity complete. | 1 | EACH | |
166 | 101 | All as per Item no 95.00 above, but for MCCB 40 Amps 25 KA breaking capacity complete. | 1 | EACH | |
167 | 102 | All as per Item no 95.00 above, but for MCCB 100 Amps 25 KA breaking capacity complete. | 1 | EACH | |
168 | 103 | All as per Item no 95.00 above, but for MCCB 63 Amps 25 KA breaking capacity complete. | 1 | EACH | |
169 | 104 | Comprehensive Maintenance / Servicing of existing VCB, 3 phase, 11 KV, 630 / 400 Amps by authorised dealer.The scope of work includes :\n(a)Calibration of metering system, checking, setting, adjustment of over current relay, earth fault and tripping relay complete all as specified and directed by Engr in charge.The contractor should immediately approach mechanic of authorised dealer as soon as fault occurs/resetting required.\n(b) Checking of heater mechanism, IR value,14 KV hypotest at site,replacement of locking arrangement & testing for smooth functioning at rated voltage. \n (c) Making all indicator bulbs and push buttons functional at no additional cost (d) Making all electrical connections to voltmeter and ameter good and ensure the proper functioning of ameters and voltmeters with proper caliberation/adjustment of voltage and current of outgoing VCB,s with main Incomer VCB\nNote: (1) The contractor should ensure the proper functioning of VCB's and should approach with authorised dealer for carrying of servicing of breaker periodically & when fault /breakdown occurs. (2) Contractor shall produce all purchase voucher and test certificate before submitting the RAR. (3) The contractor will be responsible for serviceability of VCB for the entire contract period. (4) Unserviceable Spare Part will be paid and measured separately under respective items of schedule. | 10 | EACH | |
170 | 105 | Supply only 1 Amp PT fuze (set of three fuzes) | 2 | EACH SET | |
171 | 106 | Supply only tripping coil and close coil for healthy functioning of HT VCB complete all as specified and directed by Engr in charge. | 1 | EACH SET | |
172 | 107 | M & L for Opening the HT 11 KV, Bus bar chamber of HT panel/VCB , cleaning the HT bus bar , inspect the nuts, bolts, bus bar insulator and tighting/replace with new one if required and heating up for removal of moisture , record its IR value with the help of 5 KV megger and applying thick coating of Z931 strippex B and Z955 Strippex (SL) of stanvac product for preventing from flush over and fire hazard , including replacement of 3/2 mm thick gasket, closing of all holes and charging the same complete all as directed by Engineering -in- charge . | 10 | EACH | |
173 | 108 | M & L for Over hauling and secondary injection of over current and earth fault relay of HT VCB 11 KV panel on each multiple setting , readjustment and calibration the same complete all as specified including testing on completion . | 4 | EACH | |
174 | 109 | M & L for Testing of primary injection by artificial load through CTs on each multiple setting of over current and earth fault relay , testing CTs polarities , relay calibration and co-ordination complete . | 4 | EACH | |
175 | 110 | Comprehensive Maintenance / Servicing of existing RMU's SF 6, 3 phase, 11 KV, 630 / 400 Amps by authorised dealer only.The scope of work includes :\n(a)Calibration of metering system, checking, setting, adjustment of over current relay, earth fault and tripping relay complete all as specified and directed by Engr in charge.The contractor should immediately approach mechanic of authorised dealer as soon as fault occurs/resetting required.\n(b) Checking of all incoming and outgoing HT Terminals for any looseness and ensuring the proper tightness for all terminals. \n (c) Checking the nominsl operating gas presssure as per manufactures standard of RMU and testing for any leakage of insulation gas and rectify the same if found \n (d) Operating gas pressure should be suitable to satisfy the rated dielectric strength (e) Testing for CT's, PT's, Relays , Breakers and cable glands \n (f) Anti oxide greasing should be done at all connections of cable and bus bars \nNote: (1) The contractor should ensure the proper functioning of RMU's and should approach with authorised dealer for carrying of servicing of breaker periodically & when fault /breakdown occurs. (2) Contractor shall produce all purchase voucher and test certificate before submitting the RAR. (3) The contractor will be responsible for serviceability of RMU's for the entire contract period. (4) Unserviceable Spare Part will be paid and measured separately under respective items of schedule. | 5 | EACH | |
176 | 111 | Servicing for maintenance of Air Circuit Breaker up to capacity 2000 Amps by cleaning of interphase barriers, Draw out contacts on the circuit breaker and stationary contacts in the cubicle should be cleaned and inspected for overheating, alignment and broken and weak springs. Coat contact surfaces with contact lubricant to ease mating, ensure lubrication is done according to the manufacturer specification, protective relays and circuit breaker trip devices should be inspected and tested according to manufacturer specifications including testing complete. | 10 | EACH | |
177 | 112 | Servicing of transformer 1000/630/500 /400/315/200/100 KVA at carrying out insulation resistant test(HT-LT,HT-E & LT-E), BDV of Oil (top & bottom sample), Filtration & topping up of oil, test, quaterly resistance check of earth pits, arresting of leakage by proper tightening of terminals& joints,replacement of loose or burnt out gasket & proper sealing of valves etc as directed by Engineer-in-Charge | 20 | EACH JOB | |
178 | 113 | Note for Item No 111 and 112.00 above: \n(i)The cost involved for oil filtration & topping with new mineral oil will be measured & paid separately.\n(ii) The contractor should produce all testing certificates immediately after testing .Moreover testing should be carried out by authorized OEM only\n(iii) The contracted labour manning the substation should immediately inform any oil leakage,change in colour of silica gel,level down of oil in conservator etc | |||
179 | 114 | Dehydration / filtration of transformer oil of transformers, of various capacities installed in different locations under GE ( AF ) chiloda, by recirculation existing transformer oil with trolley mounted filtration plant till dielectric strength is up to 40 KV to 50 KV.\nNote- Quoted rates shall be deem to include for following :-\n(i) Oil shall be tested after filtration and test result will be recorded before & after filtration of oil. (ii) Contractor should make his own arrangement for oil filtration plant including transportation complete. (iii) Transformer oil will be issued under Sch ‘B’ free for topping up | 3000 | LTRS | |
180 | 115 | S&F in replacement worn out HT terminal with bush of existing size for transfomers upto 1000 KVA capacity to arrest leakage by opening top cover and refixing the same with replacement of worn out gasket complete. | 2 | EACH | |
181 | 116 | S&F in replacement worn out LT terminal with bush of existing size for transfomers upto 1000 KVA capacity to arrest leackage by opening top cover and refixing the same with replacement of worn out gasket complete. | 2 | EACH | |
182 | 117 | S&F in replacement breather with accessories of transformer as existing including filling of silca jel complete. | 10 | EACH | |
183 | 118 | Repairs maintenance of APFC panel of capacity 90KVAR to 200KVAR including replacement of wiring with copper conductor cable with lugs etc calibration of relay, digital meter including testing complete.\nNote : Unserviceable Spare Part will be paid and measured separately under respective items | 10 | EACH | |
184 | 119 | S&F in repair Red/Yellow/Blue LED indicating lamp (Set of three lamp), 240 volts, AC | 10 | EACH | |
185 | 120 | S&F in repair Red luminous push button with LED indicating lamp and 1NC Element complete all as specified and directed by Engr in Charge. \nMake : Schneider/Siemens/L&T | 10 | EACH | |
186 | 121 | S&F in repair Green luminous push button with LED indicating lamp and 1NC Element complete all as specified and directed by Engr in Charge. \nMake : Schneider/Siemens/L&T | 10 | EACH | |
187 | 122 | S&F in repair 50 KVAR capacitor duty contactor , 240 volts, AC coil complete all as specified and directed by Engr in Charge. \n | 1 | EACH | |
188 | 123 | S&F in repair 40 KVAR capacitor duty contactor , 240 volts, AC coil complete all as specified and directed by Engr in Charge. | 1 | EACH | |
189 | 124 | S&F in repair 25 KVAR capacitor duty contactor , 240 volts, AC coil complete all as specified and directed by Engr in Charge. | 1 | EACH | |
190 | 125 | S&F in repair 25 KVAR cylindrical capacitor , 440 volts, 3 phase, 50 Hz complete all as specified and directed by Engr in Charge. | 1 | EACH | |
191 | 126 | S&F in repair 12.5 KVAR capacitor duty contactor , 240 volts, AC coil complete all as specified and directed by Engr in Charge. | 1 | EACH | |
192 | 127 | S&F in repair 12.5 KVAR cylindrical capacitor , 440 volts, 3 phase, 50 Hz complete all as specified and directed by Engr in Charge. | 1 | EACH | |
193 | 128 | S&F in repair 25 KVAR splendid duty square capacitor , 440 volts, 3 phase, 50 Hz complete all as specified and directed by Engr in Charge. | 1 | EACH | |
194 | 129 | S&F in repair 50 KVAR splendid duty square capacitor , 440 volts, 3 phase, 50 Hz complete all as specified and directed by Engr in Charge. | 1 | EACH | |
195 | 130 | S&F in repair 12.5 KVAR splendid duty square capacitor , 440 volts, 3 phase, 50 Hz complete all as specified and directed by Engr in Charge. | 2 | EACH | |
196 | 131 | S&F in repair digital voltmeter 0-500 volts of size 96x96mm complete all as specified and directed by Engr in Charge. \nMake : C&S/BHEL/ABB/SIEMENS | 4 | EACH | |
197 | 132 | S&F in repair digital Ampere meter 0-500 volts of size 96x96mm complete all as specified and directed by Engr in Charge. Make : C&S/BHEL/ABB/SIEMENS | 4 | EACH | |
198 | 133 | Repairing of LT panel of size 2.0 m x 1.5 m x 0.5 m by welding of door replacement of hinges wherever required and re-arrange the internal fitting/fixture including replacing of nut bolt and locking arrangement , replace of door sheet thickness 3.15mm size, bottom plate including cable gland upto size 150mm cable (1+4) one incomming and four outgoing cables and disconnection of unserviceable internal cables of any size rewiring/reconnection by suitable size of wire/cable including fixing of panel in PCC 1:2:4 type B-2 using 20 mm graded stone aggregate complete including one coat of red oxide primer and one coat smoke gray colour paint all as specified and directed. | 4 | EACH JOB | |
199 | 134 | Supply only aggregate for loose filling of gauge 40 mm to 80 mm graded at electric supply sub stations at AF Stn Chiloda and MAP Sub Stns complete all as specified and directed | 20 | CUM | |
200 | 135 | Supply and fix RCC cable trench covers of size 1000x500x50mm with lifting handle arrangement covering the open trenches at MRS, Sub Stn No.1 and 2 and all other electric supply installations all as specified and directed by E-in- Charge | 20 | EACH | |
201 | 136 | Supply and fix in repair PVC insulated copper conductor wire of 3 core 1.5 sqmm from existing syntex box to light fitting complete. | 100 | RM | |
202 | 137 | Supply and fix Aluminiun strip of existing size 32 x 6 mm with saddles and fixing screws etc for earthing connection to bus bar trunking system of existing LT Panels at MAP power stations | 20 | RM | |
203 | 138 | S&F in repair 25 Watt LED Strip Cool White for HQ SWAC WERSTERN AIR COMMAND signage board each letter 3.5 Feet Height and upto 2.0 Feet Width to be illuminated with equal intensity Lumen 300 Lux Complete including replacing old LED Strip, and fitting rthe new the amount quoted by the tenderer shall be deemed to include the cost for Scai Folding Required to work with safety complete all as specified and directed by Eng-In-Charge | 250 | RM | |
204 | 139 | M&L for shampoo washing of all letters of HQ SWAC Signage board and Logo Complete all as specified and directed by Eng-In-Charge | 22 | EACH | |
205 | 140 | S&F in repair SMPS Driver 12 V 10 Amp Capacity for controlling electric Supply to LED Strip of HQ SWAC Signage Board complete all as specified and directed by Eng-In- Charge | 8 | EACH | |
206 | 141 | S&F in repair Waterproof Electrical enclosures for water protection of SMPS Drivers 12 V 10 Amp wall mounted complete all as specified and directed by Eng-In-Charge | 8 | EACH | |
207 | 142 | S& F in repair Casing Capping Patti 50 mm x 25 mm for all loose hanging electrical wires for connection of LED Strip to the Signage board Complete all as specified and directed | 100 | RM | |
208 | 143 | Taking out U/S LT underground cable of any size (4x16 Sq mm to 3.5x300 Sq mm) 1100 volt grade & bricks, tracing out the defects, rectify the same, making serviceable by removing/cutting U/S & burnt out part, jointing with straight through joint of suitable size, testing with megger etc complete all as specified and directed by Eng-In-Charge (Straight through joints and all associated earth work like excavation/returning filling/removal of excavated material and sand filling will be measured and paid separately under respective item of this schedule.) | 400 | RM | |
209 | 144 | Relaying of serviceable LT cable retrieved from item No 143.00 above after cutting into pieces serviceable portion complete all as specified and directed by Eng-In-Charge (Straight through joints and all associated earth work like excavation/returning filling/removal of excavated material and sand filling will be measured and paid separately under respective item of this schedule.) | 400 | RM | |
210 | 145 | Taking out U/S HT underground cable of any size (3x95 Sq mm to 3x300 Sq mm) 1100 volt grade & bricks, tracing out the defects, rectify the same, making servicable by removing/cutting U/S & burnt out part jointing with straight through joint of suitable size, testing with megger etc complete all as specified and directed by Eng-In-Charge (Straight through joints and all associated earth work like excavation/returning filling/removal of excavated material and sand filling will be measured and paid separately under respective item of this schedule.) | 100 | RM | |
211 | 146 | Relaying of serviceable HT cable retrieved from item No.144 above after cutting into pieces serviceable portion complete all as specified and directed by Eng-In-Charge (Straight through joints and all associated earth work like excavation/returning filling/removal of excavated material and sand filling will be measured and paid separately under respective item of this schedule.) | 100 | RM | |
212 | 147 | Supply and lay in repairs and testing cable HT XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable heavy duty with stranded aluminum conductor, 1100 Volts grade, of size 95 Sqmm 3 Core.\nNote:-Excavation, earthwork, will be measured and paid separately under respective items of this Schedule. | 20 | RM | |
213 | 148 | All as per Item no 147.00 above, but cable of size 120 Sqmm 3 Core.\n | 20 | RM | |
214 | 149 | S&F in repair cable jointing kit for 11000 volts grade cable for straight through joints, heat shrinkable type joint complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm 3 core. | 2 | EACH | |
215 | 150 | All as per Item no 149.00 above, but cable jointing kit for XLPE armoured aluminium conductor cable of size 120 Sqmm to 185 Sqmm 3 core. | 2 | EACH | |
216 | 151 | All as per Item no 149.00 above, but cable jointing kit for XLPE armoured aluminium conductor cable of size 240 Sqmm to 400 Sqmm 3 core. | 2 | EACH | |
217 | 152 | S&F in repair cable jointing kit for 11000 volts grade cable for Outdoor termination joints, heat shrinkable type joint complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 240 sqmm to 300 sqmm 3 core. | 2 | EACH | |
218 | 153 | S&F in repair cable jointing kit for 11000 volts grade cable for Outdoor termination joints, heat shrinkable type joint complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm 3 core. | 2 | EACH | |
219 | 154 | S&F in repair cable jointing kit for 11000 volts grade cable for Outdoor termination joints, heat shrinkable type joint complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 50 Sqmm to 95 sqmm 3 core. | 2 | EACH | |
220 | 155 | S&F in repair cable jointing kit for 11000 volts grade cable for Indoor termination joints, heat shrinkable type joint complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 50 Sqmm to 95 sqmm 3 core. | 2 | EACH | |
221 | 156 | S&F in repair cable jointing kit for 11000 volts grade cable for Indoor termination joints, heat shrinkable type joint complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 120 Sqmm to 185 sqmm 3 core. | 2 | EACH |