Military Engineer Services-MES has published Repair And Replacement Of Internal Electrical Fittings Fixtures Dbs Sub Main Wiring And Other Connected Misc Em Works At Hq Fleet Satavahana Area Virabahu Area And Dockyard Area Under Ge Nb Visakhapatnam. Submission Date for this Tender is 29-08-2020. Electromechanical Work Tenders in VISAKHAPATNAM Andhra Pradesh. Bidders can get complete Tender details and download the document.
Name of Work: REPAIR AND REPLACEMENT OF INTERNAL ELECTRICAL FITTINGS, FIXTURES, DBS, SUB MAIN WIRING AND OTHER CONNECTED MISC E/M WORKS AT HQ FLEET, SATAVAHANA AREA, VIRABAHU AREA AND DOCKYARD AREA UNDER GE (NB) VISAKHAPATNAM | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | M & L for point wiring with two runs of single core 1.5 Sqmm (nominal area) PVC insulated unsheathed multistranded copper conductor cable FR (ISI marked) drawn through and including non metallic PVC conduit 20 mm bore medium grade (ISI marked) Concealed including flush type metal GI boxes for fixing modular switches, sockets, regulators etc. including provision of multistranded 1.5 Sqmm. copper conductor FR (ISI marked) as earth wire connected to common earth dolly and earth in distribution board, including tee bend, elbows, junction boxes etc including taking down existing point wiring along with fittings and fixtures except ligh fittings and making good the disturbed surfaces to match with adjoining surface complete all as specified and as directed, for one light/exhaust fan/fan point/call bell controlled by one way switch complete all as specified and as directed.\n | 300 | POINT | |
2 | 2 | All as per item No. 1.00 above but for One light point controlled by two way switch complete all as specified and as directed. | 30 | POINT | |
3 | 3 | All as per item No. 1.00 above but for One 3/5 pin socket outlet 6 amps on independent board complete all as specified and as directed. | 150 | POINT | |
4 | 4 | All as per item No. 1.00 here in before but for one 15 Amps power point on the independent board with two runs of PVC insulated and unsheathed copper conductor cable of size 2.5 sqmm multistranded FR (ISI marked) and 2.5 sqmm PVC insulated unsheathed solid copper conductor cable FR (ISI marked) as earth lead complete all as specified and as directed.\n | 200 | POINT | |
5 | 5 | All as per item No. 1.00 here in before but for one 15 Amps power point on the independent board with two runs of PVC insulated and unsheathed copper conductor cable of size 4 sqmm multistranded FR (ISI marked) and 4 sqmm PVC insulated unsheathed solid copper conductor cable FR (ISI marked) as earth lead complete all as specified and as directed.\n[i] Note for Item No. 1 to 5 : (i) The rate quoted is deemed to include making good the disturbed sufaces and to match the adjoining surface. \n(ii) The quoted rate is deemed to include cutting chases for concealed wiring including making good the same as per the existing one) | 180 | POINT | |
6 | 6 | M & L for Sub main wiring with 4 runs of Single core 10 sqmm [ for Phase & Neutral ] PVC insulated multi stranded FR (ISI marked) copper cable drawn through existing surface / ceiling / concealed steel / PVC conduit along with 1 run of single core 10 sqmm PVC insulated multi stranded FR (ISI marked) copper cable as earth continuity conductor including taking down the existing submain wiring and making good the disturbed surfaces to match with adjoining surface complete all as specified and as directed.\n(Note :- Four runs of 10 sqmm and one runs of 10 sqmm cable as earth will be measured as one length) | 120 | RM | |
7 | 7 | M & L for Sub main wiring with 4 runs of Single core 6 sqmm [ for Phase & Neutral ] PVC insulated multi stranded FR (ISI marked) copper cable drawn through existing surface / ceiling / concealed steel / PVC conduit along with 1 run of single core 6 sqmm PVC insulated multi stranded FR (ISI marked) copper cable as earth continuity conductor including taking down the existing submain wiring and making good the disturbed surfaces to match with adjoining surface complete all as specified and as directed.\n(Note :- Four runs of 10 sqmm and one runs of 10 sqmm cable as earth will be measured as one length) | 180 | RM | |
8 | 8 | M & L for Sub main wiring with 2 runs of Single core 6 sqmm [ for Phase & Neutral ] PVC insulated multi stranded FR (ISI Marked) copper cable drawn through existing surface / ceiling / concealed steel / PVC conduit along with 1 run of single core 6 sqmm PVC insulated multi stranded FR (ISI Marked) copper cable as earth continuity conductor including taking down the existing submain wiring and making good the disturbed surfaces to match with adjoining surface complete all as specified and as directed.\n(Note :- Two runs of 6 sqmm and one runs of 6 sqmm cable as earth will be measured as one length) | 250 | RM | |
9 | 9 | M & L for Sub main wiring with 2 runs of Single core 4 sqmm [ for Phase & Neutral ] PVC insulated multi stranded FR (ISI Marked) copper cable drawn through existing surface / ceiling / concealed steel / PVC conduit along with 1 run of single core 4 sqmm PVC insulated multi stranded FR (ISI Marked) copper cable as earth continuity conductor including taking down the existing submain wiring and making good the disturbed surfaces to match with adjoining surface complete all as specified and as directed.\n(Note :- Two runs of 4 sqmm and one runs of 4 sqmm cable as earth will be measured as one length.) | 320 | RM | |
10 | 10 | M & L for Sub main wiring with 2 runs of Single core 2.5 sqmm [ for Phase & Neutral ] PVC insulated multi stranded FR (ISI Marked) copper cable drawn through existing surface / ceiling / concealed steel / PVC conduit along with 1 run of single core 2.5 sqmm PVC insulated multi stranded FR (ISI Marked) copper cable as earth continuity conductor including taking down the existing submain wiring and making good the disturbed surfaces to match with adjoining surface complete all as specified and as directed.\n(Note :- Two runs of 2.5 sqmm and one runs of 2.5 sqmm cable as earth will be measured as one length.) | 250 | RM | |
11 | 11 | S & F in repairs Concealed sheet metal enclosure with socket plug top and MCBs having single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB of capacity 20Amp 240V complete all as specified and as directed.\n | 60 | EACH SET | |
12 | 12 | S & F in repairs Concealed sheet metal enclosure with socket plug top and MCBs having triple pole and nutral enclosure with a three pin and earth plug and socket complete with one triple pole MCB of capacity 32Amp 240V complete all as specified and as directed. | 30 | EACH SET | |
13 | 13 | S & F in repairs AC Plug for two pin and earth plug and socket enclosure complete all as specified and as directed. | 50 | EACH | |
14 | 14 | S & F in repairs AC Socket for two pin and earth plug and socket enclosure complete all as specified and as directed. | 50 | EACH | |
15 | 15 | S & F in replacement Distribution Board, TPN, 4 way, Double door with IP 54 protection including taking down existing fittings and fixtures and making good the disturbed surfaces to match with adjoining surface complete all as specified and as diretced complete all as specified and directed.\n(Make: Indo Asian Indo Asian cat part No. 811857 or equivalent make as per List of Manufacturer's) | 18 | EACH | |
16 | 16 | S & F in replacement Distribution Board, TPN, 6 Way, Double door with IP 54 protection including taking down existing fittings and fixtures and making good the disturbed surfaces to match with adjoining surface complete all as specified and as diretced complete all as specified and directed.\n(Make: Indo Asian Indo Asian cat part No. 811859 or equivalent make as per List of Manufacturer's) | 12 | EACH | |
17 | 17 | S & F in repairs Distribution Board, SPN 12 Way, Double door with IP 54 protection including taking down existing fittings and fixtures and making good the disturbed surfaces to match with adjoining surface complete all as specified and as directed. \n(Make : Indo Asian cat part No. 811828 [Optipro] or equivelant of make as per List of manufacturer's) | 18 | EACH | |
18 | 18 | S & F in repairs Distribution Board, SPN 8 Way ,Double door with IP 54 protection including taking down existing fittings and fixtures and making good the disturbed surfaces to match with adjoining surface complete all as specified and as directed. \n(Make : Indo Asian cat part No. 811826 [Optipro] or equivelant of make as perList of manufacturer's) | 12 | EACH | |
19 | 19 | S & F in repairs Vertical DB double door for provision for four pole MCCB upto 125 A incommer 4 way 12 outgoing with IP 54 protection including taking down existing fittings and fixtures and making good the disturbed surfaces to match with adjoining surface complete all as specified and as directed. \n(Make : Indo Asian cat part No. 812045 or equivelant of make as per List of manufacturer's) | 9 | EACH | |
20 | 20 | S & F in repairs Vertical DB double door for provision for four pole MCCB upto 250A incommer 8 way 24 outgoing with IP 54 protection including taking down existing fittings and fixtures and making good the disturbed surfaces to match with adjoining surface complete all as specified and as directed. \n(Make : Indo Asian cat part No. 812047 or equivelant of make as per List of manufacturer's) | 7 | EACH | |
21 | 21 | S & F MCB SP 6 to 32 Amps, 240 Volts, C Curve, complete all as specified and as directed \n(Make : Indo Asian Cat part No. 811122 to 811129 [ Optipro] or equivelant of make as perList of manufacturer's) | 200 | EACH | |
22 | 22 | S & F in repairs MCB SP 6 to 32 Amps, 240 Volts, C Curve, complete all as specified and as directed \n(Make : Indo Asian Cat part No. 811122 to 811129 [ Optipro] or equivelant of make as perList of manufacturer's) | 200 | EACH | |
23 | 23 | S & F MCB SPN 6-32A Amps 240 Volts MCB C Curve , complete all as specified and as directed \n(Make : Indo Asian Cat part No. 811144 to 811151[ Optipro] or equivelant of make as perList of manufacturer's)\n | 90 | EACH | |
24 | 24 | S & F in repairs MCB SPN 6-32A Amps 240 Volts MCB C Curve , complete all as specified and as directed \n(Make : Indo Asian Cat part No. 811144 to 811151[ Optipro] or equivelant of make as perList of manufacturer's)\n | 90 | EACH | |
25 | 25 | S & F MCB, four pole 63 Amps, C Curve , complete all as specified and as directed \n(Make : Indo Asian Cat part No. 811242 [ Optipro] or equivelant of make as perList of manufacturer's)\n | 30 | EACH | |
26 | 26 | S & F in repairs MCB, four pole 63 Amps C Curve , complete all as specified and as directed \n(Make : Indo Asian Cat part No. 811242 [ Optipro] or equivelant of make as perList of manufacturer's)\n | 30 | EACH | |
27 | 27 | S & F MCB, TP 63 Amps C Curve complete all as specified and as directed \n(Make : Indo Asian Cat part No. 811198 [ Optipro] or equivelant of make as perList of manufacturer's)\n | 30 | EACH | |
28 | 28 | S & F in repairs MCB, TP 63 Amps C Curve complete all as specified and as directed \n(Make : Indo Asian Cat part No. 811198 [ Optipro] or equivelant of make as perList of manufacturer's)\n | 30 | EACH | |
29 | 29 | S & Fix repairs of single core 2.5 Sqmm size cable (nominal area) PVC insulated unsheathed multistranded FR copper conductor cable 1100 Volts [ISI marked ] drawn through existing point wiring complete all as specified and as directed.\n | 600 | RM | |
30 | 30 | All as per item No. 29 above but of cable size 4 Sqmm size cable complete ditto. \n\n | 600 | RM | |
31 | 31 | All as per item No. 29 above but of cable size 6 Sqmm complete ditto.\n\n | 600 | RM | |
32 | 32 | S & F in repair Spreaders, 3/4 pole Breakers complete all as specified and as directed. \n(Make: Indo Asia/ Legrand/Havell's)\n | 30 | Each | |
33 | 33 | S & F in repair Street light bracket arm of length not less than 1.5 m made out of GI tubing, 40 mm bore, light grade fixed to pole, etc with suitable size flat iron clamp, nuts, bolts including painting with two coats of aluminium paint over a coat of red oxide, zinc chrome primer complete all as specified and directed. | 25 | Each | |
34 | 34 | S & F Stepped type electonic fan regulator flush type on the existing phenolic laminated sheet complete all as specified and as directed. \n | 175 | Each | |
35 | 35 | S & F in repairs Stepped type electonic fan regulator flush type on the existing phenolic laminated sheet complete all as specified and as directed. \n | 175 | Each | |
36 | 36 | S & F ceiling rose, 65 X 50mm two to three terminals, PVC/polycarbonate, insolated body complete all as specified and directed. \n | 90 | Each | |
37 | 37 | S & F in repairs ceiling rose, 65 X 50mm two to three terminals, PVC/ polycarbonate, insolated body complete all as specified and directed. \n\n | 90 | Each | |
38 | 38 | S & F in repairs 3mm thick backelite sheet (hylam) as sheet cover of size 10"x8" for fixing switches, sockets & regulator etc complete all as specified and as directed. \n\n | 30 | Each | |
39 | 39 | S & F in repairs 3mm thick backelite sheet (hylam) as sheet cover of size 6"x4" for fixing switches, sockets & regulator etc complete all as specified and as directed. \n\n | 30 | Each | |
40 | 40 | Supply and laying cable XLPE insulated screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 35 Sqmm 3.5 core including taking out old one complete all as specified and directed. (Note: Excvation and earth work shall be measured and paid seperately)\n\n | 150 | RM | |
41 | 41 | S & F in repairs Rigid non-metalic PVC conduit (20mmdia) exclusive of boxes (junction/ treminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hook etc. complete all as specified and directed. \n\n | 300 | RM | |
42 | 42 | Supply and fix in repair fan capacitors of 2.5 Mfd complete all as specified and as directed. \n(Make : Havells/USHA/TIBCON) | 300 | EACH | |
43 | 43 | S & F steped type modular fan regulator ,100/120 W 1/ 2 module complete all as specified and as directed. \n | 125 | Each | |
44 | 44 | S & F in repairs steped type modular fan regulator ,100/120 W 1/ 2 module complete all as specified and as directed. \n | 125 | Each | |
45 | 45 | S & F Switch socket combination 2 in1, 3 pin, 6 Amps flush type, universal complete all as specified and as directed. \n | 75 | Each | |
46 | 46 | S & F in repairs Switch socket combination 2 in1, 3 pin, 6 Amps flush type, universal complete all as specified and as directed. \n | 175 | Each | |
47 | 47 | S & F Switch socket combination 2 in1, 3 pin, 6 and 16Amp, flush type, universal complete all as specified and as directed. \n | 170 | Each | |
48 | 48 | S & F in repairs Switch socket combination 2 in1, 3 pin, 6 and 16Amp, flush type, universal complete all as specified and as directed. \n | 10 | Each | |
49 | 49 | S & F switch piano Flush type, single pole one way 6 Amp 240 volts, complete all as specified and as directed. \n | 255 | Each | |
50 | 50 | S & F in repairs switch piano Flush type, single pole one way 6 Amp 240 volts, complete all as specified and as directed. \n | 145 | Each | |
51 | 51 | S & F Switch flame proof rotary type with termination box in LM6, 16A, single pole 250V complete all as specified and as directed. \n \n | 10 | Each | |
52 | 52 | S & F in repairs Switch flame proof rotary type with termination box in LM6, 16A, single pole 250V complete all as specified and as directed. \n | 5 | Each | |
53 | 53 | S & F Modular socket outlet 6A, 2/3 pin combined, 2 module,AC 230V, 50HZ,conforming to IS 1293 :2005 (incl all revisons and amendments). complete all as specified and as directed. \n | 75 | Each | |
54 | 54 | S & F in repairs Modular socket outlet 6A, 2/3 pin combined, 2 module,AC 230V, 50HZ,conforming to IS 1293 :2005 (incl all revisons and amendments). complete all as specified and as directed. \n | 175 | Each | |
55 | 55 | S & F Modular socket outlet 6A/16A, 2/3 pin combined, 2 module,AC 230V, 50HZ,conforming to IS 1293 :2005 (incl all revisons and amendments) complete all as specified and as directed. \n | 200 | Each | |
56 | 56 | S & F in repairs Modular socket outlet 6A/16A, 2/3 pin combined, 2 module,AC 230V, 50HZ,conforming to IS 1293 :2005 (incl all revisons and amendments) complete all as specified and as directed. \n | 10 | Each | |
57 | 57 | S & F switch modular single pole one way 6 amp 240 volts,1 Module complete all as specified and as directed. \n | 75 | Each | |
58 | 58 | S & F in repairs switch modular single pole one way 6 amp 240 volts,1 Module complete all as specified and as directed. \n | 105 | Each | |
59 | 59 | S & F switch modular single pole one way 16 amp 240 volts,1 Module complete all as specified and as directed. \n | 200 | Each | |
60 | 60 | S & F in repairs switch modular single pole one way 16 amp 240 volts,1 Module complete all as specified and as directed. \n | 10 | Each | |
61 | 61 | S & F switch modular single pole Two way 6 amp 240 volts,1 module complete all as specified and as directed. \n | 60 | Each | |
62 | 62 | S & F in repairs switch modular single pole Two way 6 amp 240 volts,1 module complete all as specified and as directed. \n | 1 | Each | |
63 | 63 | S & F bell push flush type, 6 amp 240 volts, complete all as specified and as directed. \n | 20 | Each | |
64 | 64 | S & F in repairs bell push flush type, 6 amp 240 volts, complete all as specified and as directed. \n | 10 | Each | |
65 | 65 | S & F Bell electric, Ding Dong AC 230 Volts, single pole complete all as specified and as directed. \n | 35 | Each | |
66 | 66 | S & F in repairs Bell electric, Ding Dong AC 230 Volts, single pole complete all as specified and as directed. \n | 15 | Each | |
67 | 67 | S & F modular bell push 6 amp 240 volts1 module,complete all as specified and as directed. \n | 15 | Each | |
68 | 68 | S & F in repairs modular bell push 6 amp 240 volts1 module,complete all as specified and as directed. \n | 5 | Each | |
69 | 69 | S & F Lamp Holder, PVC/ Polycarbonate type with backplate suitable for batten fitting complete all as specified and as directed. \n | 50 | Each | |
70 | 70 | S & F in repairs Lamp Holder, PVC/ Polycarbonate type with backplate suitable for batten fitting complete all as specified and as directed. \n | 50 | Each | |
71 | 71 | S & F in repairs MCCB enclosure suitable for MCCB as per site requirement complete all as specified and as directed. \n | 20 | Each | |
72 | 72 | S & F in repairs MCCB 415 Volt 16 KA, 4 Pole, 100 Amps Capacity complete all as specified and as directed . \n(Make: /Indo Asian. Cat Part No. 830022 or equivelant of make as per List of Manufacturer's) | 15 | Each | |
73 | 73 | S & F in repairs MCCB 415 Volt 16 KA, 4 Pole, 160 Amps Capacity complete all as specified and as directed . \n(Make: /Indo Asian. Cat Part No. 830095 or equivelant of make as per List of Manufacturer's) | 12 | Each | |
74 | 74 | S & F in repairs MCCB 415 Volt 50 KA 4 Pole 400 Amps Capacity complete all as specified and as directed. \n(Make: /Indo Asian. Cat Part No. 830196 or equivelant of make as per List of Manufacturer's) | 3 | Each | |
75 | 75 | S & F in repairs MCCB 415 Volt 25 KA 4 Pole 250 Amps Capacity complete all as specified and as directed. \n(Make: /Indo Asian. Cat Part No. 830107 or equivelant of make as per List of Manufacturer's) | 6 | Each | |
76 | 76 | S & F in repairs 70 W, HPSV ballast complete all as specified and as directed.\n(Make : Bajaj/ Philips / CG/ Havell's)\n | 50 | Each | |
77 | 77 | S & F in repairs 150 W, HPSV ballast complete all as specified and as directed.\n(Make : Bajaj/ Philips / CG/ Havell's)\n | 20 | Each | |
78 | 78 | S & F in repairs 250 W, HPSV/MH ballast complete all as specified and as directed.\n(Make : Bajaj/ Philips / CG/ Havell's)\n | 50 | Each | |
79 | 79 | S & F in repairs 70 W, HPSV Lamp complete all as specified and as directed.\n(Make : Bajaj/ Philips / CG/ Havell's)\n | 30 | Each | |
80 | 80 | S & F in repairs 150 W, HPSV Lamp complete all as specified and as directed.\n(Make : Bajaj/ Philips / CG/ Havell's)\n | 30 | Each | |
81 | 81 | S & F in repairs 250 W, HPSV Lamp complete all as specified and as directed.\n(Make : Bajaj/ Philips / CG/ Havell's)\n | 60 | Each | |
82 | 82 | S & F in repairs LED Drive 36/40 watts as per site requirement complete all as specified and as directed. \n(Make : Bajaj/ Philips / CG/ Havell's) | 120 | Each | |
83 | 83 | S & F in repairs LED Drive 10/14 watts as per site requirement complete all as specified and as directed \n(Make : Bajaj/ Philips / CG/ Havell's) | 120 | Each | |
84 | 84 | S & F in repairs LED Drive 100 watts flood lights as per site requirement complete all as specified and as directed \n(Make : Bajaj/ Philips / CG/ Havell's) | 30 | Each | |
85 | 85 | S & F in repairs 20W, LED Flame proof lights with IP 65 protection complete with all accessories all as specified and as directed.\n(Make : Model no EXTN1LT8-16/20 of Crompton or equivalent of make as per List of Manufacturer's)\n | 30 | Each | |
86 | 86 | S & F in repairs Ignitor for HPSV/MH luminaires complete all as specified and as directed.\n(Make : Havells /Bajaj/ Philips / CG) \n | 50 | Each | |
87 | 87 | S & F in repairs capacitors of 25/36 Mfd suitable for 70/150 / 250watts HPSV/ MH luminaires complete all as specified and as directed.\n(Make : Bajaj / Phillips / CG)\n | 30 | Each | |
88 | 88 | S & F in repairs Aluminium thimbles/ lugs for suitable size Cable complete all as specified and as directed. \n | 50 | Each | |
89 | 89 | S & F in repairs HRC Fuse links and bases, 35 to 63A bolted type of suitable size as per site requirement complete all as specified and as directed.\n | 20 | Each | |
90 | 90 | Taking down ceiling fan / EXHAUST FAN any sweep from the site and replacing the defective parts such as shakle & clamps including, rubber bush, bolts, nuts & split pin (Chera Pin), washer etc. for ceiling fan and ensure proper inserting the quarter/ Split pin to hold the nut and bolt on fan downrod at fix position including servicing, oiling and greasing and re-fixing the ceiling fan / exhaust fan of any sweep again at existing site all as specified and as directed . | 400 | Each Job | |
91 | 91 | Material and Labour for preparation of old metal surfaces of Panel Boards after complete removal of existing painting over 10cm width or girth not otherwise described and applying two coats of enamel paint (1st quality) of simens grey colour over a coat red oxide zinc chrome primer and marking the Qtr No, Panel Board No in front side complete all as specified and directed by engineer in Charge.\n(Note: Adjoing aresa there to properly covered befor painting.Adjoing areas, floor, walls are to cleaned free of paint spillage after painting work. If Paint spill is not cleaned to match with exsting surface a panel recovery @ Rs.200/- per location will be made from payments due to the contractor). | 400 | Sqm | |
92 | 92 | M & L for Repairs to Panel board indoor type sheet metal approximate szie (5 x5 x 1.5 Feet's) parts tinkering the parts and replacing fully corroded sheet metal parts like base plate, top plate, front cover etc with appropriate gauges MS sheet including bending to match with the existing size, welding brazing and assembling including replacing all nuts & bolts in MCBs and proper legging in cable and control wire sheet metal screws metal screws and painting the complete body with two coat of synthetic enamel paint over a coat of Zinc chrome primer and marking the Qtr No, Panel Board No in front side and all as specified and as directed | 20 | Each Job | |
93 | 93 | M & L Earthing complete with GI earth plate electrode 600 mm x 600mm x 6 mm thick burried directly in ground vertically to a depth not less than 2.25 m below ground level with the top edge of earth plate at depth not less than 1.5 m below ground level connected with galvanised earth strip of size 32x6mm dia by means of bolts, nuts, check nuts and washers protected by 40mm bore light grade GI pipe, funnel with 20mm bore GI medium grade pipe for watering, wire mesh, including concrete pit in PCC (1:3:6) type C-1, with 50 mm thick Pre-cast R.C.C. (1:2:4) type B-I cover slab (reinforced with 8 mm dia deformed bar @ 15 cm C/C both ways and suitable handle of 10 mm dia round bar), including providing charcoal or coke and common salt in alternate layers of 15 cm compacted thickness all around the earth electrode, with funnel, wire mesh, aluminium lugs, complete in all respect and other end connected with main switch board or Earthing test point as directed, including necessary earth work and disposal of spoil to a distance not exceeding 50 metre and necessary testing on completion inclduing taking down old one complete all as specified and as directed by the Engineer-in-Charge. | 5 | Each Set | |
94 | 94 | S & F in repairs Aluminium strip of size 25x3.15 mm for lightning conductor (roof conductors)/down conductors) laid in trench/floor including necessery clamps, nuts, bolts and hylem sheet block complete all as specified and as directed. | 120 | RM | |
95 | 95 | S & F in repairs GI strip of size 25x4mm for lightning conductor laid in trench / floor including necessery clamps, nuts, bolts and hylem sheet block complete all as specified and as directed. | 80 | RM | |
96 | 96 | S & F in repairs Air termination, single pointed aluminium rod 12mm dia and 300mm long and fixed complete all as specified and as directed. | 30 | Each | |
97 | 97 | S & F in repairs Test terminal box of size 175x150x100mm made out of 2mm thick hot dip galvanised sheet drilled and screwed including 4 nos 125mm long hexogonal head screwed with test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw complete all as specified and as directed. | 30 | Each |