Military Engineer Services-MES has published Repair Maintenance Of Lt Electric Distribution System In Domestic Area At Af Station Halwara. Submission Date for this Tender is 11-08-2020. Power Distribution Work Tenders in GE (AF) Halwara Punjab. Bidders can get complete Tender details and download the document.




Tender Notice

24876579
Corrigendum : Repair Maintenance Of Lt Electric Distribution System In Domestic Area At Af Station Halwara
Open Tender
Indian
Punjab
GE (AF) Halwara
11-08-2020

Tender Details

Repair Maintenance Of Lt Electric Distribution System In Domestic Area At Af Station Halwara

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 18-Jul-2020 amnd BOQ 04-08-2020
2 22-Jul-2020 Gobind Gopal AGE C Terms and Conditions 04-08-2020
3 04-Aug-2020 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 11-08-2020

Key Value

Document Fees
INR 500 /-
EMD
INR 50000.0 /-
Tender Value
INR 25 Lakhs /-

BOQ Items

Name of Work : REPAIR / MAINT OF LT ELECTRIC DISTRIBUTION SYSTEM IN DOMESTIC AREA AT AF STN HALWARA
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Taking up/down worn out/damaged/unserviceable PVC insulated underground cable armoured, heavy duty with aluminium conductors of any size, 1100V grade from trench/duct/pole/wall/pipes/roof tops etc. complete including taking out sand cushioning and brick protection etc all as specified and directed. Note:- Excavation and earth work shall be measured and paid separetely. 2600 RM
2 2 Supply, laying and connecting, LT UG cable XLPE insulated, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor laid in trenches/on poles/walls/in ducts/passing through pipes etc including jointing materials such as cable glands, lugs etc of size 240Sqmm 3.5 core complete all as specified and directed. Note : Epoxy cable Joints shall be measured and paid separately 200 RM
3 3 All as per Srl item No 2.00 above but of 185 sqmm 3.5 core. 200 RM
4 4 All as per Srl item No 2.00 above but of 150 sqmm 3.5 core. 200 RM
5 5 All as per Srl item No 2.00 above but of 120 sqmm 3.5 core. 200 RM
6 6 All as per Srl item No 2.00 above but of 95 sqmm 3.5 core. 300 RM
7 7 All as per Srl item No 2.00 above but of 70 sqmm 3.5 core. 200 RM
8 8 All as per Srl item No 2.00 above but of 50 sqmm 3.5 core. 300 RM
9 9 All as per Srl item No 2.00 above but of 35 sqmm 3.5 core. 400 RM
10 10 All as per Srl item No 2.00 above but of 25 sqmm 4.00 core. 200 RM
11 11 All as per Srl item No 2.00 above but of 10 sqmm 2 core. 200 RM
12 12 Supply, laying and connecting, LT UG cable XLPE insulated, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor laid in trenches/on poles/walls/in ducts/passing through pipes etc including jointing materials such as cable glands, lugs etc of size 300 Sqmm 3.5 core complete all as specified and directed. Note : Epoxy cable Joints shall be measured and paid separately 200 RM
13 13 Excavation in trenches in soft or loose soil, not exceeding 1.5 metre deep and not exceeding 1.5 metre wide and getting out complete all as specified and directed. \nNotes : (i) Payment for excavation shall be made for one time in case the new cable is laid in the same trenches . 405 Cum
14 14 Returning, filling in trenches including spreading, leveling, watering and well ramming in layers not exc 25 cm thick in soft/loose soil complete all as specified and as directed. 211 Cum
15 15 Removing surplus excavated soil to a distance not exceeding 50 Mtr and depositing where directed at a level not exceeding 1.5 Mtr above the starting point complete all as specified and as directed. 194 Cum
16 16 Brick protection with sub class "B" bricks (old size) laid dry, flat in trenches over cable with longest dimension perpendicular to the axis of the cable complete all as specified and directed specified . 16 Per 1000 Nos
17 17 Sand cushioning in trenches and well ramming in layers with 8 cm below and 15 cm above the cable with fine dry sand for cable protection and complete all as specified and directed.\nNote: 18 cm punned thickness shall be measured for payment purpose. 162 Cum
18 18 40mm bore GI tubing light grade as in cable protection pipe including all fittings as in replacement complete all as directed. 18 RM
19 19 50mm bore GI tubing light grade as in cable protection pipe including all fittings as in replacement complete all as directed. 18 RM
20 20 80mm bore GI tubing light grade as in cable protection pipe including all fittings as in replacement complete all as directed. 18 RM
21 21 Boring under road/path/hard standing to pass the HT / LT UG cables upto 80mm dia pipe using mechanical arrangements complete all as specified and directed. 54 RM
22 22 Heat shrinkable straight through joint for LT XLPE UG cables suitable for cable of size 300 Sqmm 3.5 core aluminium complete all as specified and directed. 2 Each
23 23 Heat shrinkable straight through joint for LT XLPE UG cables suitable for cable of size 185 to 240 Sqmm 3.5 core aluminium complete all as specified and directed. 2 Each
24 24 Heat shrinkable straight through joint for LT XLPE UG cables suitable for cable of size 70 to 150 Sqmm 3.5 core aluminium complete all as specified and directed. 2 Each
25 25 M&L in replacement for feeder pillars box factory made-out door type made out of MS sheet (CRCA) of thickness not less than 3mm of size 75x75x45cm with aluminium bus bar strip 4 Nos of 600 Amps rated suitable for 1100 volt (LT) mounted of LT porcelain insulator front opening door two leaf braced with hinged,mounted on 4 Nos of angle iron 50x50mm duly welded with box and grouted in PCC block of size 30cmx30cmx15cm in concrete 1:3:6 Top of box MS sheet duly bent in/slope,tapper with projection of 30mm on all side,weather/vermin proof with high quality of rubber beeding on panel door,cable entry arrangements at bottom includes earthing terminals 2 Nos at both side and painted with two coats of ssmoke grey stove enameled paint over a primer coat including providing MCCB, 4 pole,fixed type 400Amps, 36 KA rating-01 No complete all as directed by Engr-In-Charge. 4 Each
26 26 Supply,install,testing and commissioning of LT panel board as per IS-8632, made out of 3.15mm CRCA sheet, outdoor cubical type totally enclosed weather dust and vermin prrof with front and rear opening of 415 Volts 3 phase 4 wire 50Hz including internal wiring with copper conductor including two coats of synthetic enamel paint over one coat of red oxide primer including connecting all in coming and out going cable feeders with necessaary cable glands, thimbles etc. The panel should have angle iron base frame made of 40x40x6mm fixed/grouted, including suitable size PCC blocks with PCC 1:2:4 type B-1 using 20mm graded mechanically crshed stone aggregate foundation support, well finishing with cement mortar and comprising of the following switchgear and accessories and including taking down existing LT panel any type.\n(a) 04 Strips of aluminium bus bar with insulation colour sleeves of capacity 1000Amp fixed on PVC heat shrinkable.\n(b) Volt meter 0-500 volts digital type, panel mounted,flush type, three phase of size 96x96mm complete with built in selector switch-01 No.\n(c) Amp meter 0-300 Amps,digital type panel mounted,flush type,three phase of size 96x96mm complete with built in selector switch with suitable size of CTs-01 No.\n(d) Indicator lamp LED type on all phases (R,Y,B)-03 Nos.\n(e) MCCB 630Amps,3phase,415 volt,4 pole,breaking capacity 36KA rating with adjustable thermal & Adjustablemagnetic type-01 Nos (Incoming).\n(f) MCCB 315Amps,3 phase,415 volt 4 pole, breaking capacity 36KA rating with adjustable thermal & Adjustable magnetic type-02 Nos (Outgoing)\n(g) MCCB 250Amps,3 phase,415 volt, 4 pole,breaking capacity 25KA rating with adjustable thermal & Adjustable magnetic type-02 Nos (Outgoing).\n(h) MCCB 200Amps,3 phase,415 volt, 4 pole,breaking capacity 25KA rating with adjustable thermal & Adjustable magnetic type-01 Nos (Outgoing).\n(j) MCCB 160Amps,3 phase,415 volt, 4 pole,breaking capacity 25KA rating with adjustable thermal & Adjustable magnetic type-03 Nos (Outgoing). 1 Each Job
27 27 Supply,install,testing and commissioning of LT panel board as per IS-8632, made out of 3.15mm CRCA sheet, outdoor cubical type totally enclosed weather dust and vermin prrof with front and rear opening of 415 Volts 3 phase 4 wire 50Hz including internal wiring with copper conductor including two coats of synthetic enamel paint over one coat of red oxide primer including connecting all in coming and out going cable feeders with necessaary cable glands, thimbles etc. The panel should have angle iron base frame made of 40x40x6mm fixed/grouted, including suitable size PCC blocks with PCC 1:2:4 type B-1 using 20mm graded mechanically crshed stone aggregate foundation support, well finishing with cement mortar and comprising of the following switchgear and accessories and including taking down existing LT panel any type.\n(a) 04 Strips of aluminium bus bar with insulation colour sleeves of capacity 630Amp fixed on PVC heat shrinkable.\n(b) Volt meter 0-500 volts digital type, panel mounted,flush type, three phase of size 96x96mm complete with built in selector switch-01 No.\n(c) Amp meter 0-300 Amps,digital type panel mounted,flush type,three phase of size 96x96mm complete with built in selector switch with suitable size of CTs-01 No.\n(d) Indicator lamp LED type on all phases (R,Y,B)-03 Nos.\n(e) MCCB 400Amps,3phase,415 volt,4 pole,breaking capacity 36KA rating with adjustable thermal & Adjustablemagnetic type-01 Nos (Incoming).\n(f) MCCB 315/320Amps,3 phase,415 volt 4 pole, breaking capacity 36KA rating with adjustable thermal & Adjustable magnetic type-02 Nos (Incoming)\n(g) MCCB 200Amps,3 phase,415 volt, 4 pole,breaking capacity 25KA rating with adjustable thermal & Adjustable magnetic type-01 Nos (Outgoing).\n(h) MCCB 63Amps,3 phase,415 volt, 4 pole,breaking capacity 25KA rating with adjustable thermal & Adjustable magnetic type-02 Nos (Outgoing).\n 1 Each Job
28 28 Supply,install,testing and commissioning of LT panel board as per IS-8632, made out of 3.15mm CRCA sheet, outdoor cubical type totally enclosed weather dust and vermin prrof with front and rear opening of 415 Volts 3 phase 4 wire 50Hz including internal wiring with copper conductor including two coats of synthetic enamel paint over one coat of red oxide primer including connecting all in coming and out going cable feeders with necessaary cable glands, thimbles etc. The panel should have angle iron base frame made of 40x40x6mm fixed/grouted, including suitable size PCC blocks with PCC 1:2:4 type B-1 using 20mm graded mechanically crshed stone aggregate foundation support, well finishing with cement mortar and comprising of the following switchgear and accessories and including taking down existing LT panel any type.\n(a) 04 Strips of aluminium bus bar with insulation colour sleeves of capacity 400Amp fixed on PVC heat shrinkable.\n(b) Volt meter 0-500 volts digital type, panel mounted,flush type, three phase of size 96x96mm complete with built in selector switch-01 No.\n(c) Amp meter 0-300 Amps,digital type panel mounted,flush type,three phase of size 96x96mm complete with built in selector switch with suitable size of CTs-01 No.\n(d) Indicator lamp LED type on all phases (R,Y,B)-03 Nos.\n(e) MCCB 250Amps,3phase,415 volt,4 pole,breaking capacity 36KA rating with adjustable thermal & Adjustablemagnetic type-01 Nos (Incoming).\n(f) MCCB 160Amps,3 phase,415 volt 4 pole, breaking capacity 25KA rating with adjustable thermal & Adjustable magnetic type-02 Nos (Outgoing)\n(g) MCCB 63Amps,3 phase,415 volt, 4 pole,breaking capacity 25KA rating with adjustable thermal & Adjustable magnetic type-01 Nos (Outgoing).\n 2 Each Job
29 29 Supply,install,testing and commissioning of LT panel board as per IS-8632, made out of 3.15mm CRCA sheet, outdoor cubical type totally enclosed weather dust and vermin prrof with front and rear opening of 415 Volts 3 phase 4 wire 50Hz including internal wiring with copper conductor including two coats of synthetic enamel paint over one coat of red oxide primer including connecting all in coming and out going cable feeders with necessaary cable glands, thimbles etc. The panel should have angle iron base frame made of 40x40x6mm fixed/grouted, including suitable size PCC blocks with PCC 1:2:4 type B-1 using 20mm graded mechanically crshed stone aggregate foundation support, well finishing with cement mortar and comprising of the following switchgear and accessories and including taking down existing LT panel any type.\n(a) 04 Strips of aluminium bus bar with insulation colour sleeves of capacity 400Amp fixed on PVC heat shrinkable.\n(b) Volt meter 0-500 volts digital type, panel mounted,flush type, three phase of size 96x96mm complete with built in selector switch-01 No.\n(c) Amp meter 0-300 Amps,digital type panel mounted,flush type,three phase of size 96x96mm complete with built in selector switch with suitable size of CTs-01 No.\n(d) Indicator lamp LED type on all phases (R,Y,B)-03 Nos.\n(e) MCCB 315/320Amps,3 phase,415 volt 4 pole, breaking capacity 36KA rating with adjustable thermal & Adjustable magnetic type-01 No (Incoming)\n(f) MCCB 200Amps,3 phase,415 volt, 4 pole,breaking capacity 25KA rating with adjustable thermal & Adjustable magnetic type-02 Nos (Outgoing).\n(g) MCCB 160Amps,3 phase,415 volt, 4 pole,breaking capacity 25KA rating with adjustable thermal & Adjustable magnetic type-01 Nos (Outgoing).\n 2 Each Job
30 30 Cleaning,scrapping,preparing the old painted steel surface of any description and applying two coats of synthetic enamel paint over one coat of red oxide primer to HT/LT panel complete all as specified. 30 Job
31 31 M&L in replacement for earthing complete with GI earth plate electrode of size 60cmx60cmx6mm thick buried directly in ground vertically at a depth not less than 2.25 mtr below normal ground level with top edge of earth plate at depth not less than 1.5 mtr below normal ground level surrounded from all sides by 15cm thick and packed layer of charcol dust and common salt filling in alternate layers and electrode connected by galvanised iron strip 32mmx6mm by means of bolts,nuts,check nut and washers connected to test termination point protected by 40mm bore GI pipe light grade and GI pipe light grade 20mm bore for watering and including funnel,wire mesh, RCC pit cover and PCC chamber pit with PCC 1:2:4 type B1 including exluvation and earth work,disposal of surplus soil to a distance not exceeding 50 mtr all as specified and shown in electrical plate No.3 of SSR Part-I complete all as specified and directed \nNote :- (i) The unit rate shall include for GI water pipe,protection pipe wire mesh,funnel,excavation, RCC pit cover, PCC test point, GI strip 32x6mm from top of earth plate upto 5 mtr.\n(ii) PCC pit shall be providded at least 1.5m away from the earth pit and extra cost of additional length of water pipes and fixing junction,Elbows etc. Shall be deemed to be included in the unit rate.\n(iii) RCC pit cover shall be percast of RCC 1:2:4, type B-1,80mm thickreinforced with XPM weighing not less than 4kg/Sqm in liue of cast iron cover. 12 Each Job
32 32 S&F in replacement MCB 63A TPN complete all as specified and directed. 6 Each
33 33 S&F in replacement MCCB 63A 4 pole 25KA with adjustable Thermal & fixed magnetic setting lcs =100% of icu complete all as specified and directed. 4 Each
34 34 S&F in replacement MCCB 100Amp 4 pole 25KA with adjustable Thermal & fixed magnetic setting lcs =100% of icu complete all as specified and directed. 3 Each
35 35 S&F in replacement MCCB 160A 4 pole 25KA with adjustable Thermal & fixed magnetic setting lcs =100% of icu complete all as specified and directed. 2 Each
36 36 S&F in replacement MCCB 200 A 4 pole 25KA with adjustable Thermal & fixed magnetic setting lcs =100% of icu complete all as specified and directed. 3 Each
37 37 S&F in replacement MCCB 250 A 4 pole 36KA with adjustable Thermal & fixed magnetic setting lcs =100% of icu complete all as specified and directed. 3 Each
38 38 S&F in replacement MCCB 315A/320A 4 pole 36KA with adjustable Thermal & fixed magnetic setting lcs =100% of icu complete all as specified and directed. 3 Each
39 39 S&F in replacement MCCB 400-A 4 pole 36KA with adjustable Thermal & fixed magnetic setting lcs =100% of icu complete all as specified and directed. 2 Each
40 40 S&F in replacement MCCB 630-A 4 pole 36KA with adjustable Thermal & fixed magnetic setting lcs =100% of icu complete all as specified and directed. 3 Each