Military Engineer Services-MES has published Special Repair For Additional Alternation For Conversion Overhead Lines To Underground Cabling And Allied Works At Army Area Jodhpur. Submission Date for this Tender is 07-08-2020. Electrification Work Tenders in Army Area Jodhpur Rajasthan. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 30-Jul-2020 | Corrigendum | BOQ | 07-08-2020 |
Name of Work: SPECIAL REPAIR FOR ADDL/ALTN FOR CONVERSION OVERHEAD LINES TO UNDERGROUND CABLING AND ALLIED WORKS AT ARMY AREA JODHPUR | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Dismantling of insulators any type any size from existing poles all as directed. | 500 | Each | |
2 | 2 | Dismantling of unserviceable ACSR conductor of any type and size from existing broken poles at various location all as directed by Engr - in - charge at site. | 16 | Qtl | |
3 | 3 | Dismantling of cross arms (Clamp, nut bolts ),care fully from site complete all as specified and directed by Engr-in-charge. | 15 | Qtl | |
4 | 4 | Dismantling of existing any type and any size of broken poles including dismantling of cross arms (channel/ angles) insulators ,security lights ,fittings and earth work complete all as directed at site. NOTE- (i) Rates includes demolition of concrete and making good.(ii) Dismantling of cross arms (Channels/angles) and insulators will be measured and paid seperately under respective item of schedule. | 30 | Each | |
5 | 5 | Dismantling of broken U/S existing earthing with galvanised steel strip 32x6mm and 10/8 SWG wire complete including removing of PCC from site. | 16 | Each | |
6 | 6 | Dismantling of broken stay assembly from various location any size and stay rod complete all as specified and directed at site. | 10 | Each | |
7 | 7 | Dismantling of U/S LT Panel of any type and size complete all as specified and directed at site. | 3 | Each | |
8 | 8 | Taking out U/S LT cable of any type and size complete all as specified and directed at site. | 300 | RM | |
9 | 9 | Fixing only steel structure, cross arms bracing supports ,clamps, back plates of any type, section incl. nuts, bolts, washers, welding ,bending cold or hot in any size and shape all as directed Including two coats of aluminium paints over a coat of red oxide primer incl preparation of surface all as directed by Engr-in-charge. | 1 | Qtl | |
10 | 10 | Supply and fix steel tubular swaged poles type 410 SP-31 (9.0 mtrs long) swan Neck type/ detachable cantilever arm complete with CI base plate and finial and double swan neck/ detachable cantilever arm conforming to relavent latest IS complete all as specified and directed at site. Make: Bansal/Utkarsh/Jindal\n | 15 | Each | |
11 | 11 | Supply and fix steel tubular swaged poles type 410 SP-31 (9.0 mtrs long) swan Neck type/detachable cantilever arm complete with CI base plate and finial and single swan neck/detachable cantilever arm conforming to relavent latest IS complete all as specified and directed at site. Make: Bansal/Utkarsh/Jindal\n | 20 | Each | |
12 | 12 | Material and labour Cement concrete (1:3:6) type C -2 using 40 mm graded stone aggregate for foundation of pole /struts/stay assembly etc complete all as directed by Engineer-in-charge. | 21 | Cum | |
13 | 13 | Material and labour Cement concrete (1:3:6) type C -1 using 20 mm graded stone aggregate set in cement motor 1:6, for pedestal of poles/copping including necessary frame work ,fair finishing to exposed surfaces using extra cement complete form, all as directed by Engineer-in-charge. | 5 | Cum | |
14 | 14 | M&L for fixing of existing dismantled street light of any size complete with all as directed by Engr-in-Charge. | 50 | EACH | |
15 | 15 | Supply and fix cable path indicators made out of PCC (1:3:6) type C2 using 40mm graded stone aggregate size (30cm x 60cm) with applying two coats of paint, marking of voltage and size of cable, route including necessary earth work required complete all as specified and directed. | 100 | Each | |
16 | 16 | Supply and fix security light junction boxes of Diemension –[300X200X105]mm , shockproof, rustproof, termite resistant, weather proof, cable entry from bottom , pole mounting arrangement along with 3 phase 4 wire 100 amps almunium busbar with insulators and MCB SP - 6 amps rating with provision of Cable Glands incl three core copper cable with pvc conduit from junction box to existing LED fitting. Make :Sintex Code No GS-JB-3020 (I) (hight hinged) or equivalent.\n\n\n\n\n\n\n\n\n \n | 60 | Each | |
17 | 17 | Supply and fix security light junction boxes of Diemension –[540X310X200]mm , shockproof, rustproof, termite resistant, weather proof, cable entry from bottom , pole mounting arrangement along with 3 phase 4 wire 100 amps almunium busbar with insulators, Cable Glands. Make :Sintex Code No GSDB -5431or equivalent.\n\n\n\n\n\n\n\n\n \n | 5 | Each | |
18 | 18 | Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 5 connected to earthing test point all as specified or indicated including testing on completion and watering pipe shall be 20 mm bore medium grade including all excavation & earth work in any type of soil incl PCC pit (1:3:6) type C-1 with RCC cover including charcoal , salt, funnel, all as directed at site. NOTE:- Rate included for excavation & earth work in any type of strata as shown in electrical plate No 5. | 10 | Each | |
19 | 19 | Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 32x6mm galvanised iron strip | 20 | RM | |
20 | 20 | Supply and fix Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4 mm dia galvanised iron or steel wire complete all as directed by Engr-in-Charge. | 30 | RM | |
21 | 21 | Supply and fix LT XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 120 sq. mm x 3.5 Core. Make: Havells/Polycab/KEI | 600 | RM | |
22 | 22 | M&L cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volt grade with stranded aluminium conductor of size 70 Sq mm 3.5 Core. | 200 | RM | |
23 | 23 | Supply and fix LT XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 16 sq. mm x 4 Core. | 3200 | RM | |
24 | 24 | M&L cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volt grade with stranded aluminium conductor of size 10 Sq mm 2 Core. | 1000 | RM | |
25 | 25 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying of cables, erection of poles, struts/stays, leveling of yard etc not exceeding 10 M² on plan and not exceeding 1.5 m in depth and getting out in soft/loose soil. | 810 | Cum | |
26 | 26 | Material and labour for sand for cushioning to underground cable screened un-washed river sand and punning for cushioning to cable all as directed. | 324 | Cum | |
27 | 27 | Material and labour for stone slab(patti), roughly hammer dressed stone, 40 to 50 mm thick, 25 to 30 cm wide and not less than 60 cm long laid dry and abutting each other with gap between adjacent slab not exceeding 10 mm over underground cables for protection. | 1200 | Cum | |
28 | 28 | Returning, filling in, including spreading, leveling watering and well ramming in layers n.exc 25 cm in soil. | 426 | Cum | |
29 | 29 | Removing of excavated soil not exc. 50 M from starting points all as directed by EIC. | 384 | Cum | |
30 | 30 | M&L for GI tubing medium grade (ISI marked) with all fitting/accessories for protection of cable on pole/wall and under road crossing including clamps, nuts bolts etc all as specified and directed of following sizes:- (a) 40mm dia | 150 | RM | |
31 | 31 | Motorized Auguring/drilling in road at 90cm depth of dia suitable for laying of 50mm dia GI tubing pipe. | 70 | RM | |
32 | 32 | Supply and fixing Feeder pillar box or Junction box of size 350mm x 350mm x 200mm with proper cover/door hinged to one end and locking arrangement at other end dust proof duly painted by a single coat of synthetic enamel paint over a coat of red oxide incl fixing up on angle iron frame of size 40mm x 40mm x 5mm and provn for fixing of Isolators/MCB-TPN/DP/SP on insulator and connecting incoming and out going cables all as directed at site. NOTE: Items like MCB, Isolators will be measured and paid separately in respective schedule A items. | 3 | Each Job | |
33 | 33 | Supply, install, testing and commissioning of LT Panel board, outdoor type, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with copper bus bars duly insulated by insulation of RYB colour 100 Amps rating mounted on porcelain insulators. The panels shall be factory made, double door, made out of 3.15 mm thick MS sheet totally enclosed dust, vermin and rust proof front operated, front and rear opening with locking arrangement fixed with MS angle iron frame of size 40X40X6 mm duly embedded in PCC platform and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 hinges to panel doors and locking arrangement as desired complete all as directed by Engr-in-charge and comprising of the following:- (A) IN COMING (a) Onload change over switch 200 Amps 4 pole - 01 No (b) MCCB 4 Pole 415 Volts 36 KA 200 Amp rating micro processor release type (Icu=Ics=100%) -01 No Make : Legrand DPX/L&T d sine/ equivalent of ABB (c) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (d) Panel mounted multi function energy meter of accuracy CL-1.0 rating - 01 No L&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 25 KA 100 Amp rating thermal magnetic release type -02 Nos (b) MCCB 4 Pole 415 Volts 25 KA 63 Amp rating thermal magnetic release type -01 Nos | 1 | Each Job | |
34 | 34 | Supply, install, testing and commissioning of LT Panel board, outdoor type, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with copper bus bars duly insulated by insulation of RYB colour 300 Amps rating mounted on porcelain insulators. The panels shall be factory made, double door, made out of 3.15 mm thick MS sheet totally enclosed dust, vermin and rust proof front operated, front and rear opening with locking arrangement fixed with MS angle iron frame of size 40X40X6 mm duly embedded in PCC platform and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 hinges to panel doors and locking arrangement as desired complete all as directed by Engr-in-charge and comprising of the following:- (A) IN COMING (a) Onload change over switch 250 Amps 4 pole - 01 No (b) MCCB 4 Pole 415 Volts 36 KA 250 Amp rating micro processor release type (Icu=Ics=100%) -01 No (c) Panel mounted multi function energy meter of accuracy CL-1.0 rating - 01 No Make :- L&T/Siemens/Legrand. (d) RYB LED indicating lamp panel mounting type (Set of three) - 01 No. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 25 KA 125 Amp rating thermal magnetic release type -01 Nos (b) MCCB 4 Pole 415 Volts 25 KA 100 Amp rating thermal magnetic release type -01 Nos | 3 | Each Job |