Military Engineer Services-MES has published Manning And Operation Including Periodical And Essential Repairs To Central Ac Plants At Nad Explosive Non Explosive Area Under Ge Nw Karanja. Submission Date for this Tender is 29-07-2020. HVAC Tenders in GE (NW) KARANJA Maharashtra. Bidders can get complete Tender details and download the document.




Tender Notice

24794582
Corrigendum : Manning And Operation Including Periodical And Essential Repairs To Central Ac Plants At Nad Explosive Non Explosive Area Under Ge Nw Karanja
Open Tender
Indian
Maharashtra
GE (NW) KARANJA
29-07-2020

Tender Details

Manning And Operation Including Periodical And Essential Repairs To Central Ac Plants At Nad Explosive Non Explosive Area Under Ge Nw Karanja

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 22-Jul-2020 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 29-07-2020

Key Value

Document Fees
INR 500 /-
EMD
INR 98000.0 /-
Tender Value
INR 49 Lakhs /-

BOQ Items

NAME OF WORK:Manning & Operation including periodical and essential repairs to central AC plants at NAD (Explosive /non explosivea area) under GE(NW) Karanja
Sl. No. Description of Item of Work Item Code / Make Quantity Unit
1 1 Manning and operation of under mentioned central AC plants comprising the various equipments as mentioned below in three shifts i.e. 0600 Hrs to 1400 Hrs, 1400 Hrs to 2200 Hrs, 2200 Hrs to 0600 Hrs including sunday & Holiday maintaining the documentation as directed for DX type central AC plant of capacity 70 TR installed at DBM 12/13 AC plant for maintaining Temp 74 + 4F and humidity 60 + 5% & for DX type central AC plant of capacity 30 TR installed at DBM 14 AC plant for maintaining Temp 74 + 4F and humidity 60 + 5% in AC spaces comprising of under mentioned plants equipments and accessaries. BI01010001010000000000000515BI0100001113 11 Per Month
2 1.01 For DBM 12/13 DX type Central AC Plant (70 TR) BI01010001010000000000000515BI0100001114
3 1.02 (i) Condensing units having reciprocating type Accel make compressors, 3 Ph electric motors control panles and other accessories -03 Nos BI01010001010000000000000515BI0100001115
4 1.03 (ii) Electrical systems comprising of main panles, AHU panel, control cables, earthing systems, interlocking panel wiring systems etc -01 Sets BI01010001010000000000000515BI0100001116
5 1.04 (iii) Cooling water circulating system comprising of 02 Nos water pumps, water piping system, control valves, FRP cooling tower, PVC water tank etc -01 Sets BI01010001010000000000000515BI0100001117
6 1.05 (iv) Supply air and return air ducts comprising of diffuser, grills, insulatios etc -01 Sets BI01010001010000000000000515BI0100001118
7 1.06 (v) AHU of 8500 CFM capacity , heating bands, control wiring system, fresh air grills etc complete -01 Sets BI01010001010000000000000515BI0100001119
8 1.07 (vi) Sensing devices such as RH sensor, temp gauges control circuits etc -01 Sets BI01010001010000000000000515BI0100001120
9 1.08 For DBM 14 DX type Central AC Plant (30 TR) BI01010001010000000000000515BI0100001121
10 1.09 (i) Condensing units having reciprocating type Accel make compressors, 3 Ph electric motors control panles and other accessories -03 Nos BI01010001010000000000000515BI0100001122
11 1.1 (ii) Electrical systems comprising of main panles, AHU panel, control cables, earthing systems, interlocking panel wiring systems etc -01 Sets BI01010001010000000000000515BI0100001123
12 1.11 (iii) Cooling water circulating system comprising of 02 Nos water pumps, water piping system, control valves, FRP capacity cooling tower, PVC water tank etc -01 Sets BI01010001010000000000000515BI0100001124
13 1.12 (iv) Supply air and return air ducts comprising of diffuser, grills, insulatios etc -01 Sets BI01010001010000000000000515BI0100001125
14 1.13 (v) AHU of 6500 CFM capacity , heating bands, control wiring system, fresh air grills etc complete -01 Sets BI01010001010000000000000515BI0100001126
15 1.14 (vi) Sensing devices such as RH sensor, temp gauges control circuits etc -01 Sets BI01010001010000000000000515BI0100001127
16 2 Manning and operation of under mentioned central AC plants comprising the various equipments as mentioned below in three shifts i.e. 0600 Hrs to 1400 Hrs, 1400 Hrs to 2200 Hrs, 2200 Hrs to 0600 Hrs including sunday & Holiday maintaining the documentation as directed for DX typechilled water type AC plant of capacity 50 TR installed at DBM 17/SBM 3 AC plant for maintaining Temp 22 C + 3 C and humidity 55 + 5% & for DX type Chilled water type AC plant of capacity 46 TR installed at SBM 4 AC plant for maintaining Temp 74 + 4F and humidity 60 + 5% in AC spaces comprising of under mentioned plants equipments and accessaries. BI01010001010000000000000515BI0100001128 11 Per Month
17 2.01 For DBM 17/SBM-3 DX type Chilled water type AC Plant (50 TR) BI01010001010000000000000515BI0100001129
18 2.02 (i) Condensing units having reciprocating type Accel make compressors, 3 Ph electric motors control panles and other accessories -03 Nos BI01010001010000000000000515BI0100001130
19 2.03 (ii) Electrical systems comprising of main panles, AHU panel, control cables, earthing systems, interlocking panel wiring systems etc -01 Sets BI01010001010000000000000515BI0100001131
20 2.04 (iii) Cooling water circulating system comprising of 02 Nos water pumps, water piping system, control valves, FRPcapacity cooling tower, PVC water tank etc -01 Sets BI01010001010000000000000515BI0100001132
21 2.05 (iv) Supply air and return air ducts comprising of diffuser, grills, insulatios etc -01 Sets BI01010001010000000000000515BI0100001133
22 2.06 (v) AHU of 15250 CFM capacity, heating bands, control wiring system, fresh air grills etc complete -01 Sets BI01010001010000000000000515BI0100001134
23 2.07 (vi) Sensing devices such as RH sensor, temp gauges control circuits etc -01 Sets BI01010001010000000000000515BI0100001135
24 2.08 For SBM-4 DX type Chilled water type AC Plant (46 TR) BI01010001010000000000000515BI0100001136
25 2.09 (i) Condensing units having reciprocating type Accel make compressors, 3 Ph electric motors control panles and other accessories -03 Nos BI01010001010000000000000515BI0100001137
26 2.1 (ii) Electrical systems comprising of main panles, AHU panel, control cables, earthing systems, interlocking panel wiring systems etc -01 Sets BI01010001010000000000000515BI0100001138
27 2.11 (iii) Cooling water circulating system comprising of 02 Nos water pumps, water piping system, control valves, FRP capacity cooling tower, PVC water tank etc -01 Sets BI01010001010000000000000515BI0100001139
28 2.12 (iv) Supply air and return air ducts comprising of diffuser, grills, insulatios etc -01 Sets BI01010001010000000000000515BI0100001140
29 2.13 (v) AHU of 15000 CFM capacity, heating bands, control wiring system, fresh air grills etc complete -01 Sets BI01010001010000000000000515BI0100001141
30 2.14 (vi) Sensing devices such as RH sensor, temp gauges control circuits etc -01 Sets BI01010001010000000000000515BI0100001142
31 3 Manning and operation of under mentioned central AC plants comprising the various equipments as mentioned below in three shifts i.e. 0600 Hrs to 1400 Hrs, 1400 Hrs to 2200 Hrs, 2200 Hrs to 0600 Hrs including sunday & Holiday maintaining the documentation as directed for DX type central AC plant of capacity 29 TR installed at DBM 11 AC plant for maintaining Temp 74 + 5F and humidity 60 + 5% & for DX type central AC plant of capacity 37 TR installed at DBM 15 AC plant for maintaining Temp 23 C + 2 C and humidity 60 + 5% in AC spaces comprising of under mentioned plants equipments and accessaries. BI01010001010000000000000515BI0100001143 11 Per Month
32 3.01 For DBM 11 DX type Central AC Plant (29 TR) BI01010001010000000000000515BI0100001144
33 3.02 (i) Condensing units having reciprocating type Accel make compressors, 3 Ph electric motors control panles and other accessories -03 Sets BI01010001010000000000000515BI0100001145
34 3.03 (ii) Electrical systems comprising of main panles, AHU panel, control cables, earthing systems, interlocking panel wiring systems etc -01 Sets BI01010001010000000000000515BI0100001146
35 3.04 (iii) Cooling water circulating system comprising of 02 Nos water pumps, water piping system, control valves,FRP cooling tower, PVC water tank etc -01 Set BI01010001010000000000000515BI0100001147
36 3.05 (iv) Supply air and return air ducts comprising of diffuser, grills, insulatios etc -01 Set BI01010001010000000000000515BI0100001148
37 3.06 (v) AHU of 6500 CFM capacity , heating bands, control wiring system, fresh air grills etc complete -01 Set BI01010001010000000000000515BI0100001149
38 3.07 (vi) Sensing devices such as RH sensor, temp gauges control circuits etc -01 Set BI01010001010000000000000515BI0100001150
39 3.08 For DBM 15 DX type Chilled Water type AC Plant (37 TR) BI01010001010000000000000515BI0100001151
40 3.09 (i) Condensing units having reciprocating type Accel make compressors, 3 Ph electric motors control panles and other accessories -03 Sets BI01010001010000000000000515BI0100001152
41 3.1 (ii) Electrical systems comprising of main panles, AHU panel, control cables, earthing systems, interlocking panel wiring systems etc -01 Sets BI01010001010000000000000515BI0100001153
42 3.11 (iii) Cooling water circulating system comprising of 02 Nos water pumps, water piping system, control valves,45 TR cooling tower, PVC water tank etc -01 Set BI01010001010000000000000515BI0100001154
43 3.12 (iv) Supply air and return air ducts comprising of diffuser, grills, insulatios etc -01 Set BI01010001010000000000000515BI0100001155
44 3.13 (v) AHU of 11200 CFM capacity , heating bands, control wiring system, fresh air grills etc complete -01 Set BI01010001010000000000000515BI0100001156
45 3.14 (vi) Sensing devices such as RH sensor, temp gauges control circuits etc -01 Set BI01010001010000000000000515BI0100001157
46 4 Manning and operation of under mentioned central AC plants comprising the various equipments as mentioned below in three shifts i.e. 0600 Hrs to 1400 Hrs, 1400 Hrs to 2200 Hrs, 2200 Hrs to 0600 Hrs including sunday & Holiday maintaining the documentation as directed for DX type Chilled water type AC plant of capacity 50TR installed at SM-39 AC plant for maintaining Temp 23 C + 2 C and humidity 60 + 5% & for DX type central AC plant of capacity 104 TR installed at TAL (Works Shop) AC plant for maintaining Temp 23 C + 2 C and humidity 60 + 5% in AC spaces comprising of under mentioned plants equipments and accessaries. BI01010001010000000000000515BI0100001158 11 Per Month
47 4.01 For SBM-39 DX type Chilled Water type AC Plant (50 TR) BI01010001010000000000000515BI0100001159
48 4.02 (i) Condensing units having reciprocating type voltas make compressors, 3 Ph electric motors control panles and other accessories -03 Sets BI01010001010000000000000515BI0100001160
49 4.03 (ii) Electrical systems comprising of main panles, AHU panel, control cables, earthing systems, interlocking panel wiring systems etc -01 Set BI01010001010000000000000515BI0100001161
50 4.04 (iii) Cooling water circulating system comprising of 02 Nos 20 HP capacity water pumps, water piping system, control valves, FRP cooling tower, PVC water tank etc -01 Set BI01010001010000000000000515BI0100001162
51 4.05 (iv) Supply air and return air ducts comprising of diffuser, grills, insulatios etc -01 Set BI01010001010000000000000515BI0100001163
52 4.06 (v) AHU of 12600 CFM capacity , heating bands, control wiring system, fresh air grills etc complete -01 Set BI01010001010000000000000515BI0100001164
53 4.07 (vi) Sensing devices such as RH sensor, temp gauges control circuits etc -01 Set BI01010001010000000000000515BI0100001165
54 4.08 For TAL (Works Shop) DX type Chilled Water type AC Plant (104 TR) BI01010001010000000000000515BI0100001166
55 4.09 (i) Condensing units having reciprocating type Kirloskar make compressors, 3 Ph electric motors control panles and other accessories -03 Sets BI01010001010000000000000515BI0100001167
56 4.1 (ii) Electrical systems comprising of main panles, AHU panel, control cables, earthing systems, interlocking panel wiring systems etc -01 Set BI01010001010000000000000515BI0100001168
57 4.11 (iii) Cooling water circulating system comprising of 02 Nos 20 HP capacity water pumps, water piping system, control valves,FRP cooling tower, PVC water tank etc -01 Set BI01010001010000000000000515BI0100001169
58 4.12 (iv) Supply air and return air ducts comprising of diffuser, grills, insulatios etc -01 Set BI01010001010000000000000515BI0100001170
59 4.13 (v) AHU of 29000 CFM capacity , heating bands, control wiring system, fresh air grills etc complete -01 Set BI01010001010000000000000515BI0100001171
60 4.14 (vi) Sensing devices such as RH sensor, temp gauges control circuits etc -01 Set BI01010001010000000000000515BI0100001172
61 4.15 Note for Sl item No 1 TO 4.14 : \n(a) The contractor will employ suitable staff having qualification ITI / sufficient experience in Refrigeration/ Air conditioning field. Staffs police verification and other authenticated documantations are mandatory for security will be responsiblity of contractor.\n(b) Contractor will provide the uniform as reccommended by Engr -In - Charge. The safty of equipment neccessary T & P shall be maintained at all the installations. The contractor shall be fully responsible for safety of staff employed. Department will not be held responsible for any eventualty occured to staff employed. The contractor will be responsible / liabile to pay all type compensation etc to employed staff in accordance with prevailing labour laws in country/ staff.\n (c) Charges of documantation statainerys including maintaining documantations such as attendance register, Log sheets, complaint registers etc as per sample provided by Engr -In - charge will be responsibility of contractor. BI01010001010000000000000515BI0100001173
62 4.16 Note for Sl. Item No. 1 to 4.14 : Carrying out operation of equipments, as a part of day to day operation and in accordance with relevant PM checklists and as per schedules that will be prepared upon activation of contract. The salient features in these checklists are as follows :(i) Starting and stopping of the equipment as per requirement of the user. (ii) Checkingh the water level in the colling tower (applicable for water cooled units), (iii) Recording the equipment operational parameter including pump pressure and motor amps in the logsheet. (iv) Checking the central AC or Refrigeration system and equipment such as compressors,motors,pumps, cooling towers and their electrical controls on the respective equipment. (v) Checking the refrigeration system for any leaks. (vi) Checking the electrical and refrigeration control system for operation and adjustments of set values as necessary. (vii) Lubrication of all necessary points in the system & its components in line with the checklist. BI01010001010000000000000515BI0100001174
63 5 PERIODICAL MAINTENANCE BI01010001010000000000000515BI0100001175
64 5.01 Periodical and maintenance of under mentioned central AC plants comprising the various equipments as mentioned below including maintaining the documentation as directed for DX type central AC plant of capacity 70 TR installed at DBM 12/13 AC plant for maintaining Temp 74 + 4F and humidity 60 + 5% & AC plant of capacity 30 TR installed at DBM 14 AC plant for maintaining Temp 74 + 4F and humidity 60 + 5% in AC spaces comprising of under mentioned plants equipments and accessaries as mentioned in Sch "Manning and operation" Sl item No 01. BI01010001010000000000000515BI0100001176 11 Per Month
65 5.02 Periodical and maintenance of under mentioned central AC plants comprising the various equipments as mentioned below including maintaining the documentation as directed for DX type central AC plant of capacity 50 TR installed at DBM 17/SBM 3 AC plant for maintaining Temp 22 C + 3 C and humidity 55 + 5% & AC plant of capacity 46 TR installed at SBM 4 AC plant for maintaining Temp 74 + 4F and humidity 60 + 5% in AC spaces comprising of under mentioned plants equipments and accessaries as mentioned in Sch "Manning and operation" Sl item No 02. BI01010001010000000000000515BI0100001177 11 Per Month
66 5.03 Periodical and maintenance of under mentioned central AC plants comprising the various equipments as mentioned below including maintaining the documentation as directed for DX type central AC plant of capacity 29 TR installed at DBM 11 AC plant for maintaining Temp 74 + 5F and humidity 60 + 5%& AC plant of capacity 37 TR installed at DBM 15 AC plant for maintaining Temp 23 C + 3 C and humidity 60 + 5% in AC spaces comprising of under mentioned plants equipments and accessaries as mentioned in Sch "Manning and operation" Sl item No 03 BI01010001010000000000000515BI0100001178 11 Per Month
67 5.04 Periodical and maintenance of under mentioned central AC plants comprising the various equipments as mentioned below including maintaining the documentation as directed for DX type central AC plant of capacity 50 TR installed at SM-39 AC plant for maintaining Temp 23 C + 3 C and humidity 60 + 5% AC plant of capacity 104TR installed at TAL (Works Shop) AC plant for maintaining Temp 23 C + 3 C and humidity 60 + 5% in AC spaces comprising of under mentioned plants equipments and accessaries as mentioned in Sch "Manning and operation" Sl item No 04 BI01010001010000000000000515BI0100001179 11 Per Month
68 5.05 Inspection services for Sl. Item No. 5.01 to 5.04 : (a) Inspecting the plant/system and carry out preventive maintenance as per the standard practice four times in a year. (b) Checking the refrigeration system, motor and starters and ensuring healthy condition of the plant. (c) Checking the system for any leaks and rectificationm of leaks if found. (d) Tracking set of reading and reporting the healthiness of the plant and suggesting improvements if any. (e) Checking the refrigeration control system for operation and adjusting the settings. (f) Descaling the condensers for water cooled units if found necessary.(Once a year) however descaling compound will be provided on chargible basis. (g) Checking the fuinctioning of compressor and its accssories. (h) Cleaning the evaporator once a year if fiound necessary (j) Lubricating the bearings of motors, and fans when found necessary. (k) Quarterly inspection of belts adjusting the tension. (l) Checking of the microprocessor controller for its proper functioning. (m) Attending to break calls. (n) Labour involving evecuation of refrigerant during replacement of controls and replacement of compressor. (o) Carrying out-once in a year, testing of lubricant and water (chilled water system and water cooled condensing system only) samples. BI01010001010000000000000515BI0100001180
69 5.06 Note for Sl. Item No. 5.1 to 5.04 :- The quoted rate for above plants shall be deemed to be included following:- BI01010001010000000000000515BI0100001181
70 5.07 (a) To carry out routine, periodical, preventive (weekly, monthly, quarterly, half yearly, yearly) breakdown maintenance as per attached formats and as directed by GE & Engr-in-Charge. BI01010001010000000000000515BI0100001182
71 5.08 (b) To attend the breakdown during day & night including holidays and putting the plant in operational condition with in the shortest period. The contractor shall keep all fast consuming spares in store to be made available by GE/Engr-in-Charge at any one of the above installation. BI01010001010000000000000515BI0100001183
72 5.09 (c) Maintaining all the accessories such as electric panel. Interlocking wiring cables, pumps etc and all assemblies such as chillers etc and sub assemblies such as AHU, tower etc functional in any situation round the clock for the period including holidays etc. BI01010001010000000000000515BI0100001184
73 5.1 (d) Maintaining the surrounding area of central AC plant building, cooling tower, etc neat & clean at all time. No wild vegitaion to be seen with in the surrounding of building upto 5 mtr all around BI01010001010000000000000515BI0100001185
74 6 ESSENTIAL REPAIRS BI01010001010000000000000515BI0100001186
75 6.01 Supply and fix in repairs Thermostatic expansion valve of model No HVE 11 of Make : Sporlan, Avcon or equivalent suitable for DX and chilled water type AC plant including cutting, welding, brazing, replacement of new gasket, nut bolt, washer etc all as specified and directed by Engineer-in-Charge.Make Sporlan, Danfoss, Lanco BI01010001010000000000000515BI0100001187 4 Each
76 6.02 Ditto- all as per item No 6.01 above but model No HVE 16 BI01010001010000000000000515BI0100001188 4 Each
77 6.03 Ditto- all as per item No 6.01 above but model No MVE 20 BI01010001010000000000000515BI0100001189 4 Each
78 6.04 Ditto- all as per item No 6.01 above but model No MVE 34 BI01010001010000000000000515BI0100001190 4 Each
79 6.05 Note for sl Item No 6.01 to 6.04 :- BI01010001010000000000000515BI0100001191
80 6.06 Before disconnecting the existing expansion valve from the system the Refrigerant has to be pumped down or taken in empty cylinder by the help of Ice or as directed by Engineer-in-Charge. BI01010001010000000000000515BI0100001192
81 7 Supply and fix in repairs Differential Preassure control cut out MP-15 (Low Pressure and High Pressure common cut out) Make: Indofoss, Danfoss, Accel including interlock wiring, Brass flare nut, Brass tee, Brass union etc all as specified and directed by Engineer in charge. BI01010001010000000000000515BI0100001193 5 Each
82 7.01 Ditto- all as per item No 7.00 above, but MP-55 (Oil Pressure cut out) BI01010001010000000000000515BI0100001194 5 Each
83 7.02 Ditto- all as per item No 7.00 above, but MP-1 (Low Pressure cut out) BI01010001010000000000000515BI0100001195 5 Each
84 7.03 Ditto- all as per item No 7.00 above, but MP-5 (High Pressure cutout) BI01010001010000000000000515BI0100001196 5 Each
85 8 S&F in replacement V Belt of Make : Nirlong, Pix, Fenner, Ecodrive following sizes :- BI01010001010000000000000515BI0100001197
86 8.01 (a) V Belt B-96 BI01010001010000000000000515BI0100001198 20 Each
87 8.02 (b) V Belt B-104 BI01010001010000000000000515BI0100001199 12 Each
88 8.03 (c) V-Belt B-110 BI01010001010000000000000515BI0100001200 10 Each
89 8.04 (d) V-Belt B-112 BI01010001010000000000000515BI0100001201 10 Each
90 8.05 (e) V Belt C-128 BI01010001010000000000000515BI0100001202 12 Each
91 8.06 (f) V Belt C-124 BI01010001010000000000000515BI0100001203 18 Each
92 9 Descaling of condenser by recommended chemical of make scal gun WS or equivalent cleaning agent ( Chemical should be used as per manufacturer's instructions) by soaking method, disconnecting condenser from the system by taking out nuts, bolts, studs, valves and MS/GI pipe line from both side cover, cleaning each tube with nylon brush, flushing with alkaline solution, connecting back both side cover including replacing rubber gasket 3 mm thick for the following capacities of condenser ,suitable for AC plant of capacity as indicated below complete all as specified and as directed including required quantity of chemical, all as per manufacturer's instructions and to the entire satisfaction of Engineer-in-charge. (Notes:- 1.Descaling should be done once in every three months.Each descaling will be measured seperately. 2. New nuts, bolts, washer and studs shall be measured and paid for seperately.) BI01010001010000000000000515BI0100001204
93 9.01 (a) Up to 15 TR capacity BI01010001010000000000000515BI0100001205 68 Job
94 9.02 (b) 16 to 25 TR capacity BI01010001010000000000000515BI0100001206 96 Job
95 9.03 (c ) 26 to 50 TR capacity BI01010001010000000000000515BI0100001207 100 Job
96 9.04 (d) 51 to 90 TR capacity BI01010001010000000000000515BI0100001208 32 Job
97 10 Supply and replacement in repairs Strip heater finned 2 inch wide allumised steel fines of 415 volt 1.5 to 3 KW capacity as per existing BI01010001010000000000000515BI0100001209 4 Nos
98 11 Supply and fix in repair PVC fills (full) suitable for Mihir make cooling tower BI01010001010000000000000515BI0100001210 50 Each
99 12 Supply and fix in repair PVC fills (half) suitable for Mihir make cooling tower BI01010001010000000000000515BI0100001211 50 Each
100 13 Supply and fix in repair PVC fills (Eliminator) suitable for Mihir make cooling tower BI01010001010000000000000515BI0100001212 20 Each
101 14 M & L for CI Strainer 'Y' type with SS 304 (perforated screen) flanged end of 100mm dia including nuts, bolts and rubber gasket for fixing of the strainer all as specified and directed by Engineer-in-charge Make:- Zoloto/ Kirloskar/ Leader. BI01010001010000000000000515BI0100001213 2 Each
102 15 S & F in repair Thermostat of make Ranco/ Honeywells as per existing range including control wiring to the necessary machineries etc all as specified and directed BI01010001010000000000000515BI0100001214 2 Nos
103 16 S & F in repair Humiditistat of make Ranco/ Honeywells as per existing range including control wiring to the necessary machineries etc all as specified and directed BI01010001010000000000000515BI0100001215 3 Nos
104 17 Supply and Fix in repairs GI tubing (ISI marked) , medium grade, 80mm bore with necessary GI pipe fittings for condenser water circulation pipes all as specified and directed (Make: Jindal/Tata/ Zenith/Swastik) BI01010001010000000000000515BI0100001216 25 RM
105 18 Supply and Fix in repairs GI tubing (ISI marked) , medium grade, 100mm bore with necessary GI pipe fittings for condenser water circulation pipes all as specified and directed (Make: Jindal/Tata/ Zenith/Swastik) BI01010001010000000000000515BI0100001217 25 RM
106 19 S&F in repairs Shaft seal including 10 AG cat part No 10 of Make : Accel suitable for SMC - 65 compressors. BI01010001010000000000000515BI0100001218 6 Each
107 20 Ditto- all as per item No19.00 here-in-before but suitable for SMC - 100 compressors. BI01010001010000000000000515BI0100001219 6 Each
108 21 Ditto- all as per item No 19.00 here-inbefore but suitable for AC 4-70 cat part No 3510102050 Kirloskar make compressor. BI01010001010000000000000515BI0100001220 4 Each
109 22 M&L for rewinding of induction motor 2900RPM, 3 phase, 50 Hz, 415 volt of Compressor motor and AHU Blower motor comprising of following activities for motor of following capacities complete all as directed and specified and as per manufacturer's instructions. BI01010001010000000000000515BI0100001221
110 22.01 i) Disconnecting and removing the electric motor from installed position and loading, unloading, transporting to authorised/approved work shop. BI01010001010000000000000515BI0100001222
111 22.02 ii) Dismantling existing burnt winding from the motor and rewinding complete with super enamelled copper winding wire of existing guage including all material such as insulated paper sleeves tape varnish etc complete for class F insulation and including shaft metalising, Bearing cover slieving, necessary replacement of cooling fan, nut-bolt etc. BI01010001010000000000000515BI0100001223
112 22.03 iii) Loading, unloading and transporting motor & reinstalling in position and in alignment including electric connection commissioning and testing in actual working condition for 8 hours continuosly to check the performance on full load and designed RPM to the complete satisfaction of Engr-In-Charge all as specified and directed. BI01010001010000000000000515BI0100001224
113 22.04 (a) Ditto all as per item No. 22.0 to 22.03 but, capacity 50 HP BI01010001010000000000000515BI0100001225 2 Job
114 22.05 (b) Ditto all as per item No. 22.0 to 22.03 but capacity 40 HP BI01010001010000000000000515BI0100001226 2 Job
115 22.06 (c) Ditto all as per item No. 22.0 to 22.03 but capacity 30 HP BI01010001010000000000000515BI0100001227 2 Job
116 22.07 (d) Ditto all as per item No. 22.0 to 22.03 but capacity 15 HP BI01010001010000000000000515BI0100001228 3 Job
117 22.08 (e) Ditto all as per item No. 22.0 to 22.03 but capcity 10 HP BI01010001010000000000000515BI0100001229 3 Job
118 22.09 (f) Ditto all as per item No. 22.0 to 22.03 but capcity 7.5 HP BI01010001010000000000000515BI0100001230 4 Job
119 22.1 (g) Ditto all as per item No. 22.0 to 22.03 but capcity 5 HP BI01010001010000000000000515BI0100001231 4 Job
120 22.11 (h) Ditto all as per item No. 22.0 to 22.03 but capcity 3 HP BI01010001010000000000000515BI0100001232 4 Job
121 23 S & F Ball bearing of bearing No - 6206 of Make : SKF or Equivalent BI01010001010000000000000515BI0100001233 2 Nos
122 24 S & F Ball bearing of bearing No - 6208 of Make : SKF or Equivalent BI01010001010000000000000515BI0100001234 2 Nos
123 25 S & F Ball bearing of bearing No - 6305 of Make : SKF or Equivalent BI01010001010000000000000515BI0100001235 2 Nos
124 26 S & F Ball bearing of bearing No - 6306 of Make : SKF or Equivalent BI01010001010000000000000515BI0100001236 3 Nos
125 27 S & F Ball bearing of bearing No - 6307 of Make : SKF or Equivalent BI01010001010000000000000515BI0100001237 2 Nos
126 28 S & F Ball bearing of bearing No - 6308 of Make : SKF or Equivalent BI01010001010000000000000515BI0100001238 2 Nos
127 29 Supply only Freon gas F-22 in returnable cylinder of capacity 61 Kgs of Make : Refron/Mafron/Floron. BI01010001010000000000000515BI0100001239 200 Kgs
128 30 Supply only compressor oil in sealed container manufactured by Hindustan Petroleum limited (Sheetal N - 68) or Bharat Petroleum (Freezol 201.68) or Indian Oil (Servo Freez F-57) BI01010001010000000000000515BI0100001240 200 Ltr