8256/E8 Repair Replacement Of Internal Wiring Including Fittings Fixtures Ceiling Fans And Exhaust Fans At Sahapore Military Camp Under Ge Central Kolkata, Kolkata-West Bengal

Military Engineer Services-MES has published 8256/E8 Repair Replacement Of Internal Wiring Including Fittings Fixtures Ceiling Fans And Exhaust Fans At Sahapore Military Camp Under Ge Central Kolkata. Submission Date for this Tender is 20-07-2020. Electrification Work Tenders in Kolkata West Bengal. Bidders can get complete Tender details and download the document.




Tender Notice

24449819
Corrigendum : 8256/E8 Repair Replacement Of Internal Wiring Including Fittings Fixtures Ceiling Fans And Exhaust Fans At Sahapore Military Camp Under Ge Central Kolkata
Open Tender
Indian
West Bengal
Kolkata
20-07-2020

Tender Details

8256/E8 Repair Replacement Of Internal Wiring Including Fittings Fixtures Ceiling Fans And Exhaust Fans At Sahapore Military Camp Under Ge Central Kolkata

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 12-Jun-2020 Date Corrigendum Date 25-06-2020
2 18-Jun-2020 Date Corrigendum2 Date 02-07-2020
3 26-Jun-2020 Date Corrigendum3 Date 09-07-2020
4 03-Jul-2020 Date Corrigendum4 Date 20-07-2020

Key Value

Document Fees
INR 500 /-
EMD
INR 50000.0 /-
Tender Value
INR 25 Lakhs /-

BOQ Items

Name of Work: REPAIR/ REPLACEMENT OF INTERNAL WIRING INCLUDING FITTINGS, FIXTURES, CEILING FANS AND EXHAUST FANS AT SAHAPORE MILITARY CAMP UNDER GE (CENTRAL) KOLKATA.
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Taking down carefully any type of point wiring (light, fan, bell, socket or power) complete including fixture and fitting such as switches, ceiling roses, pendents, regulators, sockets ( excluding light fittings) etc stacking at site for reuse of serviceable items and removal of unserviceable items from site and making good disturbed faces of walls, ceiling, floor etc to match with the existing surface complete all as specified and directed by the Engineer-in-charge. 1 543 Per Point
2 2 Material and labour Point wiring with PVC insulated and unsheathed FR cable single core multistranded copper conductor 1.5 Sqmm size, 1100 volts grade cable confroming to IS - 694 1990 drawn through and including PVC casing and caping of suitable size with all accessories including fabricated MS terminal boxes fixed flush with wall surface with 3 mm thick plastic masonite laminated sheet top cover fixed with cadmium screw for mounting switches, sockets, regulator etc including 1.5 Sqmm multistranded PVC insulated and unsheathed copper conductor earth continuity conductor to common earth and connecting to earth dolly all as specified for One light / ceiling fan / bell point / 3 pin 5 Amps Socket outlet point on independent board controlled by one switch single pole one way complete all as specified and as directed. 2 498 Per Point
3 3 All as per item No. 2.00 here in-before but for one 3 pin 5 amps socket outlet on the same board with other switch for surface / conduit wiring with casing caping / PVC conduit complete all as specified and directed by Engineer in-charge. 3 20 Per Point
4 4 All as per item No. 2.00 here-in-before but using 2.5 Sq mm size FR type stranded copper conductor cable for one 16 amp switch socket outlet on independent board complete all as specified and directed by Engineer-in-Charge. 4 25 Per Point
5 5 Supply & fix Switch piano, flush type, SP, one way, 5/6 Amps 230 Volts complete all as specified and as directed.\nMake:- Make:- Cona cat Part No.1121 or equivalent model of make:- Havells/ Plaza.\n\n 5 503 Each
6 6 Supply & fix Bell/buzzer push 5/6 Amps, flush type, white/ivory finish complete all as specified and as directed. \nMake:- Cona cat Part No. 1131 or equivalent model of make:- Havells/ plaza. 6 25 Each
7 7 Supply and fix Switch socket combination multipurpose 2 in 1, 3 pin 6 Amps 240 volt flush type complete all as specified and as directed.\nMake:- Havells Reo cat part No.AHETOXW202 or Make:- Cona cat Part No.2246. 7 30 Each
8 8 Supply and fix Socket outlet , 2 in 1, 3 pin, 6 Amps, 240 volt flush type complete all as specified and as directed.\nMake:- Cona Cat Part No.1646 or equivalent model of make:- Havells/ Plaza. 8 20 Each
9 9 Supply and fix Switch socket combination multipurpose 2 in 1, 3 pin 5 & 15 Amps 240 volt flush type complete all as specified and as directed.\nMake:- Cona Cat part No. 2251 or equivalent model from make:-Havells / Plaza. 9 25 Each
10 10 Supply and fixing Lamp holder suitable for batten fittings complete all as specified and directed by the Engr-in-Charge.\nMake:- Cona Cat Part No.2166 or equivalent model from make:- Plaza/ Havells. 10 60 Each
11 11 Supply and fix Ceiling rose surface Bakelite three terminals 230 volts complete all as specified and as directed.\nMake:- Cona Cat Part No.2186 or Havells cat part No.AHEEIXW000.\n 11 415 Each
12 12 Supply and fix Call bell ding dong AC 230 volts, single pole complete all as specified and as directed.\nMake:- Cona cat Part No. 3351 or equivalent model of make:- Havells/ plaza. 12 25 Each
13 13 Supply & fix Electronics fan regulator, step type, AC 120/280 volt, white/ivory finish complete all as specified and as directed.\nMake:- Cona Cat part No. 3061 or equivalent model from make:-Havells / Plaza. 13 170 Each
14 14 Supply & fix LED lamp of 14/15 watts for energy conversion upto 50% and for efficianteco friendly coollighting and for 30000 maintenance free burning hours including necessary connection including taking down old unserviceable tube light fittings complete all as specified and as directed by Engr-in-Charge.\nMake:- Havells Cat part No. LHLDDEEEML8R015 or Make:- Surya Cat Part No.14W NEO LED LAMP 6500K, 14 60 Each
15 15 Supply & fix LED tube light fittings suitable for 1x20 watt Surface and wall mounted LED batten, extruded aluminium housing provided for efficient heat dissipation with polycarbonate diffuser & integrated electronic driver with tube rod including necessary connection including taking down old unserviceable LED tube light fittings complete all as specified and as directed by Engr-in-Charge.\nMake:- Havells Cat No. LUMLINEPLUSBS20WLED865PCSS or make:- Cromton Cat part No. LDL 20 NW or Philips Cat Part No. BN021 LED 20S PSU CW GR S2. 15 220 Each
16 16 Supply & fix LED tube light fittings suitable for 1x10 watt Surface and wall mounted LED batten, extruded aluminium housing provided for efficient heat dissipation with polycarbonate diffuser & integrated electronic driver with tube rod including necessary connection including taking down old unserviceable LED tube light fittings complete all as specified and as directed by Engr-in-Charge.\nMake:- Phillips Cat Part No. BN021C LED10S PSW CW GR S2 or Havells Cat No. LUMLINEPLUSBS10WLED865PCSS or make:- Cromton Cat part No. LDL 10 NW 16 110 Each
17 17 Supply and fixing in repairs highly robust industrial box type luminaire suitable for twin led tube after taking down old underviceable one complete all as specified and as directed. \nMake :-Crompton Cat NoIGP162LT8-16 or Bajaj cat part no-BLRB-DB 218. 17 90 Each
18 18 Supply & fix LED Building security light 30 watt in aluminium PDC housing, toughened glass cover with IP66 protection with 0.5 mtr GI pipe of suitable size making connection with PVC cable of 0.50 sq mm three core sheatered not more than 0.5 meter in lenght including taking down old unserviceable recess light fittings complete all as specified and as directed.\nMake:- HAVELLS Cat part No. ENDURACITYLITEPLATINUMPLUSSL30WLED757SASYBOPC or Make Crompton Cat Part No. LSTS-30-CDL-M or SURYA Cat Part No. SLE UL30W IP66 LXN. 18 65 Each
19 19 Supply & fix LED tube light suitable for 20 watt Ultra bright LED polycarbonate Tubelight with very high efficacy suited for installation in existing T8 fitting including necessary connection including taking down old unserviceable one complete all as specified and as directed by Engr-in-Charge.\nMake:- Havells Cat Part No.CRYSTAL1213T8DSTL20WLED865SGLASS or Make:-Crompton cat Part No. LGT8-20-865-2. 19 300 Each
20 20 Supply and fixing Surface Recess mounted LED luminaries 36/34 watt , 2'x2', White powder coated luminaries with screw less design and bottom opening to give high aesthetic and ease of servicing making connection with PVC cable of 0.50 sq mm three core sheatered not more than 0.5 meter in lenght including taking down old unserviceable recess light fittings complete all as specified and as directed.\nMake:- Havells Catb Part No. DROPDOWNFLAT2X2PLR36WLED857S or Make:- Philips RC 380B LED 36S-4000 G4 L60W60 PSD OD WH OC 20 18 Each
21 21 Supply and fix Sheet metal enclosure Metal Door for DB's where MCBs to be used 4 way single pole and neutral with 200 amps rated bus bar including taking down old unserviceable DB complete all as specified and as directed. \nMake:- ABB Cat part No.1SYI011604C0001 or Make:-Havells Cat Part No.DHDNSHODAW04\nNote:- (1) Quoted rates are inclusive of taking down DB including MCBs.\n(2) Found Unserviceable MCBs will be contractor property and will be measured under Schedule of Credit.\n(3) Found Serviceable MCBs will be taken into safe custody for reuse under relevent item of this Schedule.\n 21 25 Each
22 22 Supply and fix Sheet metal enclosure Metal Door for DB's where MCBs to be used 8 way single pole and neutral with 200 amps rated bus bar including taking down old unserviceable DB complete all as specified and as directed. \nMake:- ABB Cat Part No.1SYI011608C0001 or Make:-Havells Cat Part No.DHDNSHODAW04\nNote:- (1) Quoted rates are inclusive of taking down DB including MCBs.\n(2) Found Unserviceable MCBs will be contractor property and will be measured under Schedule of Credit.\n(3) Found Serviceable MCBs will be taken into safe custody for reuse under relevent item of this Schedule. 22 40 Each
23 23 Supply and fix Sheet metal enclosure Metal Door for DB's where MCBs to be used 12 way single pole and neutral with 200 amps rated bus bar including taking down old unserviceable DB complete all as specified and as directed. \nMake:-ABB Cat Part No.1SYI011612C0001 or Make:-Havells Cat Part No.DHDNSHODAW12\nNote:- (1) Quoted rates are inclusive of taking down DB including MCBs.\n(2) Found Unserviceable MCBs will be contractor property and will be measured under Schedule of Credit.\n(3) Found Serviceable MCBs will be taken into safe custody for reuse under relevent item of this Schedule.\n 23 10 Each
24 24 Supply and fixing MCB DB Metal Door TPN 4 way including bus bar neutral link, earth bar and din rail, recessed with wall surfaces and making good surfaces of wall including taking down old unserviceable DB all as specified and directed by the Engr-in-Charge. \nMake:- -ABB Cat Part No 1SYI0216004C0001 or Make:-Havells Cat Part No.DHDNTHODAWO4\nNote:- (1) Quoted rates are inclusive of taking down DB including MCBs.\n(2) Found Unserviceable MCBs will be contractor property and will be measured under Schedule of Credit.\n(3) Found Serviceable MCBs will be taken into safe custody for reuse under relevent item of this Schedule. 24 20 Each
25 25 Supply and fixing MCB DB Metal Door TPN 8 way including bus bar neutral link, earth bar and din rail, recessed with wall surfaces and making good surfaces of wall including taking down old unserviceable DB all as specified and directed by the Engr-in-Charge. \nMake:- ABB Cat Part No 1SYI0216008C0001 or Make:-Havells Cat Part No.DHDNTHODAWO8\nNote:- (1) Quoted rates are inclusive of taking down DB including MCBs.\n(2) Found Unserviceable MCBs will be contractor property and will be measured under Schedule of Credit.\n(3) Found Serviceable MCBs will be taken into safe custody for reuse under relevent item of this Schedule. 25 18 Each
26 26 Supply and fix MCB 6 to 32 Amps, SP, 240 Volts , 'C' curve braking capacity 10 kA as directed by the Engr-in-Charge.\nMake:-ABB Cat part No. SH201M-C6 to SH201M-C32 or Make:-Havells Cat Part No.DHMGCSPF006-032. 26 918 Each
27 27 Supply and fix in repair MCB 6 to 32 Amps, SP, 240 Volts , 'C' curve braking capacity 10 kA as directed by the Engr-in-Charge.\nMake:ABB Cat part No. SH201M-C6 to SH201M-C32 or Make:-Havells Cat Part No.DHMGCSPF006-032. 27 100 Each
28 28 Supply and fix MCB 6 to 32 Amps, DP, 240 Volts , 'C' curve breaking capacity 10 KA as directed by the Engr-in-Charge.\nMake:-ABB Cat Part No.SH202M-C6 to SH201M-C32 or Make:-Havells Cat Part No.DHMGCDPF006-032 28 147 Each
29 29 Supply and fix MCB 6 to 32 Amps, DP, 240 Volts , 'C' curve breaking capacity 10 KA as directed by the Engr-in-Charge.\nMake:-ABB Cat Part No.SH202M-C6 to SH201M-C32 or Make:-Havells Cat Part No.DHMGCDPF006-032 29 40 Each
30 30 Supply and fix MCB 63 Amps, FP, 240 Volts , 'C' curve breaking capacity 10 KA as directed by the Engr-in-Charge.\nMake:-ABB Cat part No.S204M-C63 or Make:-Havells Cat Part No.DHMGCFPF063 30 56 Each
31 31 Supply and fix in repair MCB 63 Amps, FP, 240 Volts , 'C' curve breaking capacity 10 KA as directed by the Engr-in-Charge.\nMake:-ABB Cat part No.S204M-C63 or Make:-Havells Cat Part No.DHMGCFPF063 31 10 Each
32 32 Materials and labour Sub main wiring with 2 runs of single core PVC insulated FR type, unsheathed stranded copper conductor of size 4 Sqmm and one run of PVC insulated unsheathed multistrand copper conductor of size 2.5 Sqmm FR type as earth lead drawn in and including PVC casing caping of suitable size including all fittings and taking out old unserviceable sub main wring including PVC casing caping complete all as specified and as directed.\nNote:- One run of 4 Sqmm cable and one run of 2.5 Sqmm cable with one run of PVC casing caping shall be measured as one unit. 32 200 RM
33 33 Materials and labour Sub main wiring with 2 runs of single core PVC insulated unsheathed stranded copper conductor FR type of size 6 Sqmm and one run of PVC insulated unsheathed multistrand copper conductor of size 4 Sqmm FR type as earth lead drawn in and including PVC casing caping of suitable size after taking out old un serviceable wring including PVC casing caping complete all as directed.\nNote:- One run of 6 Sqmm cable and one run of 4 Sqmm cable with one run of PVC casng caping shall be measured as one unit. \n 33 150 RM
34 34 Removing unserviceable ceiling fan upto 1400 mm sweep from its original position for inspection removing bush / bearing, cleaning of bush / bearing, replacement of unserviceable / worn out bearing / bush, and capacitor removing burnt out coils from the slots, cleaning and repairing of slots, including materials like split pin, nut bolts, rubber reel etc reassembling and refixing of fan complete including 'S' hook for fixing of fan and including 1.5 Mtr length connecting rod and fixing back in position after servicing all as specified and as directed. \nNote:- (i) Spares will be measured and paid separately as "Supply only" under relevant items of this Schedule. 34 170 Each Job
35 35 Material and Labour Rewinding of fan motor with super enamelled copper winding wire of suitable size and varnishing including testing of ceiling fan after rewinding complete all as specified and as directed. 35 100 Each Job
36 36 Supply only Ball bearing suitable for ceiling fan upto 1400mm sweep. 36 120 Each
37 37 Supply only Capacitor of 2.5 mfd for ceiling fan upto 1400mm sweep. 37 150 Each
38 38 Supply only Gun metal bush of suitable for ceiling fan upto 1400mm sweep. 38 110 Each
39 39 Supply only Shaft suitable for ceiling fan upto 1400mm sweep. 39 110 Each
40 40 Supply only nuts, bolts, for Ceiling fan 40 170 Each
41 41 SSupply only PVC connector for Ceiling fan, 41 170 Each
42 42 Supply only rubber reel insulator for Ceiling fan 42 170 Each
43 43 Material and Labour Painting of ceiling fan of any size and sweep complete with synthetic enamel paint by spraying including filling with cavities with filler, after cleaning all dust etc including taking out of ceiling fan and refixing in same position complete all as specified and as directed by Engineer-in-Charge. 43 170 Each Job
44 44 Removing unserviceable exhaust fan upto 300 mm sweep from position replacement of unserviceable bush and bearing, open the covers for repairs removing burnt out coils from the slots, cleaning and repairing of slots , and painting of fan with one coat of synthetic enamil paint by spraying and fixing back in position after servicing all as specified and as directed. \nNote:- (i) Spares such as bearing and bushes etc will be paid separately as Supply only under relevent items here-in-after. 44 40 Each Job
45 45 Material and Labour Rewinding of fan motor with super enamelled copper winding wire of suitable size and varnishing including testing of Exhaust fan after rewinding complete all as specified and as directed. 45 20 Each Job
46 46 Supply only Bush suitable for exhaust fan of suitable sweep. 46 12 Each
47 47 Supply only Ball bearing suitable for exhaust fan of suitable sweep. 47 15 Each
48 48 Supply only capacitor 3.15 mfd for exhaust fan of suitable sweep. 48 18 Each
49 49 Taking down exhaust fans of any size/ sweep complete from any height and painting the same with one coat of synthetic enamel paint of approved colour including refixing the fan at its existing position complete all as specified and as directed. 49 40 Each Job
50 50 Taking down carefully storage type water heater (Geyser ) of any make of capacity 25 Ltrs after removing all electrical and water connection from installed position at different locations,dismantling the geyser into parts for inspection.Checking /testing of all parts/accessories like appratus plate,heating element,thermostat switch,neon lamp, water tank,safety valve, spacer ring, rubber gasket,nut-bolts,inspection plate, bottom& top cover etc. complete,de-scaling of water tank and brazing the same to make it leak proof complete inclduing replacement of unserviceable spare parts and re-installation, making electric and water connectionsincluding painting with one coat of synthetic enamel paint with necessary preparation of surfaces and testing all as specified. \nNote :- Spare parts shall be measured & paid seperately as "Supply only" Items . 50 15 Each
51 51 Supply only Heating element 1 KW including rubber washer suitable for existing geyser of capacity 25 Ltrs. 51 6 Each
52 52 Supply only Heating element 1.5 KW including rubber washer suitable for existing geyser of capacity 25 Ltrs. 52 5 Each
53 53 Supply only Heating element 2 KW including rubber washer suitable for existing geyser of capacity 25 Ltrs. 53 3 Each
54 54 Supply only Chromium plated copper pipe of length not less than 60 Cm suitable for incoming and out going 54 8 Each
55 55 Supply only Apparatus plate (head assembly) complete all as per existing suitable for 25 Ltrs geysers of any make complete including rubber packing. 55 4 Each
56 56 Supply only Thermostat switch suitable for geyser of capacity 25 Ltrs. 56 8 Each
57 57 Supply only Outer casing made out of 22 gauge MS sheet white painted (in two parts) suitable for geyser of capacity 25 Ltr. 57 6 Each
58 58 Supply only Split plate (top cover ) made out of 22 gauge MS sheet,white painted suitable for geyser of capacity 25 Ltrs. 58 5 Each
59 59 Supply only Split plate (bottom cover ) made out of 22 gauge MS sheet,white painted suitable for geyser of capacity 25 Ltrs. 59 5 Each
60 60 Supply only Storage tank stanless steel, 60 4 Each
61 61 Supply only Fusible metal plug. 61 8 Each
62 62 Supply only Insulating materials (Glass wool) suitable for 25 Ltrs geyser. 62 4 Kg
63 63 Supply only non returning valve for geyser inlet. 63 4 Each
64 64 Supply only Neon Lamp round or square in shape as per existing. 64 6 Each
65 65 Supply only Element holding clamp as per existing. 65 8 Each
66 66 Supply only Element holding brass stud as per existing. 66 8 Each
67 67 Supply and fix Power supply unit consisting of starter with 11-18 Amp over load protection, MCB of 25 Amp with socket complete for AC 240 Volt single phase including taking down old unserviceable one complete all as specified and directedby Engr-in-Charge. \nMake:Havells Cat Part No DHDUCDP0253016-25 or equivalent model of Northwest . 67 6 Each
68 68 Materials and labour Earthing complete with galvanised steel earth plate electrode 60 Cm x 60 Cm x 6.00 mm thick buried in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level, connected to GI wire 4 mm as earthing lead by means of bolts, nuts, check nuts and washers of GI or steel, GI strip projected by 40 mm bore light grade GI pipe and other end connected to earth test point as directed including funnel with watering pipe 20 mm bore light grade galvanised iron, wire mesh, charcoal or coke common salt laid in alternative layer of 15 cm (complete thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1, 50 mm thick pre-cast RCC (1:2:4) type B-1 normal mix cover slab reinforced with 8 mm dia TMT bar 10 Cm c/c both ways and single handle of 10 mm dia round bar including necessary excavation, earth work etc. in soft / loose soil and disposal pf soil to a distance n. exc. 50 m and necessary testing on completion all as shown in electrical plate No. 3 MES Schedule Part-I including taking out of old unserviceable earth pit with all accessories complete all as specified and as directed. 68 14 Each Set
Disclaimer :