Military Engineer Services-MES has published Special Repair Replacement Of Dg Set , Ac Plant At Inhs Kasturi And Repair Replacement To Incinerator , Accessories And Lighting Protection System At Ins Shivaji Lonavla. Submission Date for this Tender is 16-06-2020. Lightening Protection Device Tenders in GE (I) (NAVY) LONAVLA Maharashtra. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 01-Jun-2020 | Amendment | Other | 09-06-2020 |
2 | 09-Jun-2020 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 16-06-2020 |
Name of Work: SPECIAL REPAIR/REPLACEMENT OF DG SET, AC PLANT AT INHS KASTURI AND REPAIR/REPLACEMENT TO INCINERATOR, ACCESSORIES AND LIGHTING PROTECTION SYSTEM AT INS SHIVAJI LONAVLA (8922/E8) | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Overhauling of DG Set of Cap 140 KVA at INHS Kasturi, reassembling with new spares, reinstalling, testing on load including Cleaning of Radiator and head Machining complete all as specified and as directed.\nNote :- Spares required will be measured and paid seperately under respective items | 1 | Job | |
2 | 2 | Supply only Piston Assembly suitable for 140 KVA DG Set all as specified and as directed\nLoc - INHS Kasturi | 6 | Each | |
3 | 3 | Supply only Liner Assembly suitable for 140 KVA DG Set all as specified and as directed\nLoc - INHS Kasturi | 6 | Each | |
4 | 4 | Supply only Valve Pair suitable for 140 KVA DG Set all as specified and as directed\nLoc - INHS Kasturi | 6 | Set | |
5 | 5 | Supply only ValveSeat suitable for 140 KVA DG Set all as specified and as directed\nLoc - INHS Kasturi | 6 | Set | |
6 | 6 | Supply only Valve Guide suitable for 140 KVA DG Set all as specified and as directed\nLoc - INHS Kasturi | 12 | Each | |
7 | 7 | Supply only Set of Joints suitable for 140 KVA DG Set all as specified and as directed\nLoc - INHS Kasturi | 1 | Set | |
8 | 8 | Supply only Radiator Hose suitable for 140 KVA DG Set all as specified and as directed\nLoc - INHS Kasturi | 1 | Set | |
9 | 9 | Supply only Engine Oil suitable for 140 KVA DG Set all as specified and as directed\nLoc - INHS Kasturi | 30 | Ltrs | |
10 | 10 | Supply only Oil Filter suitable for 140 KVA DG Set all as specified and as directed\nLoc - INHS Kasturi | 2 | Each | |
11 | 11 | Supply only Safety Unit suitable for 140 KVA DG Set all as specified and as directed\nLoc - INHS Kasturi | 1 | Set | |
12 | 12 | Supply only 24 V, D.C. Alternator suitable for 140 KVA DG Set all as specified and as directed\nLoc - INHS Kasturi | 1 | Each | |
13 | 13 | Supply only Fan Belt suitable for 140 KVA DG Set all as specified and as directed\nLoc - INHS Kasturi | 1 | Each | |
14 | 14 | Supply only CR Bearing (Std) suitable for 140 KVA DG Set all as specified and as directed\nLoc - INHS Kasturi | 1 | Each | |
15 | 15 | Supply only Piston Ring suitable for 140 KVA DG Set all as specified and as directed\nLoc - INHS Kasturi | 6 | Set | |
16 | 16 | Supply only Stop Solenoid 24V suitable for 140 KVA DG Set all as specified and as directed\nLoc - INHS Kasturi | 1 | Each | |
17 | 17 | Supply only Air Filter Assembly suitable for 140 KVA DG Set all as specified and as directed\nLoc - INHS Kasturi | 1 | Each | |
18 | 18 | Supply only OilSafety Switch suitable for 140 KVA DG Set all as specified and as directed\nLoc - INHS Kasturi | 1 | Each | |
19 | 19 | Supply only Air- intake Hose suitable for 140 KVA DG Set all as specified and as directed\nLoc - INHS Kasturi | 2 | Each | |
20 | 20 | Supply only Fuel Pump & Nozzle- Calibration suitable for 140 KVA DG Set all as specified and as directed\nLoc - INHS Kasturi | 1 | Each | |
21 | 21 | S&F Heavy duty battery two Nos 24 plates 24 V 180 AH connected to the system with multistranded flexible copper lead 1.5 m long welded with battery terminals complete. Make - Exide Amaron, Standard | 2 | Each | |
22 | 22 | M&L for earthling complete with copper plate electrode of size 600x600x3.15 mm, buried directly in ground (earth pit not less than 2.25 mtr below normal ground level) with top edge of earth plate not less than 1.5 mtr below normal ground level connected to copper strip 20x3 mm as earthing lead means of volts, nuts, check nuts of galvanized iron or steel including earth work in any type of soil, charcoal, salt 15 cm around the earth plate as shown in electrical plate No 3 of SSR part1991,20 mm dia watering pipe medium grade 1.50 mtr long GI protection pipe light grade 25 mm dia from earth pit to main board. | 8 | Each Set | |
23 | 23 | S&F exhaust fan AC single phase 230/240 Volt of size 450 mm complete all as specified and as directed. | 2 | Each | |
24 | 24 | M &L for making hole in wall of suitable size for fixing of exhaust fan 450 mm sweep including suitable size of nut and bolt and making good to disturb surface complete all as specified and as directed. | 2 | Job | |
25 | 25 | Supply laying and testing cable XLPE insulated screened PVC beded,galvanized steel trip or wire armoured, electric power cables (heavy duty) 1100 Volt grade wiyh stranded aluminium conductor of size 150 sq mm 3,1/2 core. | 30 | RM | |
26 | 26 | Supply, fabricate, errect, connecting, testing & commisioning LT Panel, Indoor Type, weather and vermin proof made out of 2 mm thick CRCA sheet with front opening and locking arrangement, epoxy powder coated having colour siemens grey, 800 Amps capacity aluminium bus bar for phase, 3 No's and 1 No 400 Amp bus bar for neutral, mounted on epoxy insulator including neccessary copper control wiring, heat shrinkable, RYB coloured sleeves over bus bar for identification, earth shields, circular holes at bottom / top to receive incoming and outgoing cable, cable lugs, cable gland of sizes as required floor mounting angle iron frame made out mild steel angle iron of size 40 x 40 x 6 mm grouted on PCC (1:3:6) upto required height suitable for the following control/ fitments sensible for 3 phase, 50 Hz, 415 V system complete with and including following :-\nINCOMING- \n(a) Thermal magnetic adjustable FP ACB of capacity 800 A 50 kA- 1 No. \nOUT GOINGS- \n(b) Thermal magnetic adjustable FP MCCB of capacity 300 A 36 kA - 1 No.\n(c) Thermal magnetic adjustable FP MCCB of capacity 200 A 25 kA - 2 Nos.\n(d) Thermal magnetic adjustable FP MCCB of capacity 100 A 25 kA -2 Nos.\n(e) Thermal magnetic adjustable FP MCCB of capacity 63 A 25 kA - 2 Nos.\n(f) Change Over Switch Pannel Mounted, Front operated of size : 4 Pole 800 A - 1 No\n(g) Multidigital Meter :- 1 No's\n(h) Indicating lamp LED type :- 1 sets\n | 1 | Job | |
27 | 27 | S&F AMF control panel factory made cubicle type floor mounted totally enclosed fabricated out of CRCA sheet 14 SWG, over an angle iron frame made out of 50x50x6 mm angle with removable side cover hinged front panel and rear panel for easy accessibility epoxy powder coated complete with internal wiring with suitable size copper conductor cable and cable glands for external connection complete suitable for 140 KVA DG set with by pass arrangement including all necessary operating and controlled devices (to meet the requirement of above capacity plus 25% over load) such as connectors, MCCBs, CTs voltmeter, ammeter, indicating lamp, Frequency meter, energy meter with protection fuses for panel instrument battery charging system with indicator and cut off relay's low and high oil pressure, high speed, overload and earth fault protection, reverse current protection duly wired with flexible copper conductor cable and cable connection with lugs/thimble complete all as recommended by manufacturer and directed. | 1 | Job | |
28 | 28 | Supply, fabricate, errect, connecting, testing & commisioning LT Panel, Indoor Type, weather and vermin proof made out of 3.15 mm thick CRCA sheet with front opening and locking arrangement, epoxy powder coated having colour siemens grey, 300 Amps capacity aluminium bus bar for phase, 3 No's and 1 No 150 Amp bus bar for neutral, mounted on epoxy insulator including neccessary copper control wiring, heat shrinkable, RYB coloured sleeves over bus bar for identification, earth shields, circular holes at bottom / top to receive incoming and outgoing cable, cable lugs, cable gland of sizes as required floor mounting angle iron frame made out mild steel angle iron of size 40 x 40 x 6 mm grouted on PCC (1:3:6) upto required height suitable for the following control/ fitments sensible for 3 phase, 50 Hz, 415 V system complete with and including following :- | 1 | Job | |
29 | 29 | INCOMING- \n(a) Thermal magnetic adjustable FP ACB of capacity 300 A 36 kA- 1 No. \nOUT GOINGS- \n(b) Thermal magnetic adjustable FP MCCB of capacity 63 A 25 kA - 5 Nos (03 for Compressor, 02 No AHU).\n(c) Thermal magnetic adjustable FP MCCB of capacity 40 A 16 kA - 3 Nos. (02 for Condensor Pump, 01 No Spares)\n(d) Thermal magnetic adjustable FP MCCB of capacity 20 A 16 kA -2 Nos. (01 Lighting, 01 - Security Lighting)\n(e) Thermal magnetic adjustable FP MCCB of capacity 16 A 10 kA - 1 No. (Cooling Tower Fan)\n(f) Multidigital Meter :- 8 No's (03 Compressor, 02 AHU, 02 Pump, 01 Panel)\n(g) Indicating lamp LED type :- 8 sets (03 Compressor, 02 AHU, 02 Pump, 01 Panel)\n(h) Star Delta Starter for Compressor of Central AC Plant of Cap 28 TR Each - 03 Nos\n(j) Star Delta Starter for AHU Motor of Central AC Plant of Cap 56 TR Cap - 02 Nos\n(k) DOL Starter for Condensor Motor of 05 HP Cap - 02 Nos\n(l) Indicating lamp LED type :- 8 sets (03 Compressor, 02 AHU, 02 Pump, 01 Panel)\n | |||
30 | 30 | Overhauling of compressor Model No SMC 465, including evacuation of refrigerant from complete system of central A/c plant with pump and filling refrigerant in gas cylinder. Isolating the reciprocating comp-ressor by loosing/ cutting nuts and bolts at suction and discharge valve opening of compressor, removing the unservicable/ damaged internal parts, cleaning, overhauling complete, replacement of wornout parts such as suction reeds, discharge reeds, safety valve, loading/ unloading mechanism, piston, rings, springs, washers, nuts and blots, gasket set, shaft seal, 'O' ring set, recharging compressor oil and refrigerant after pressure test and vaccum test. Testing and commissioning complete all as directed by Eng-in-charge for compressor (14 TR Each) model SMC - 465. Loc- INHS Kasturi\nNote : All spare parts and refrigerant will be measured and paid seperately under respective items of sch.'A'. | 2 | Job | |
31 | 31 | M&L for dismantling carefully the squirrel cage induction motor from position. Taking out old wornout winding and rewinding the same with copper winding wire with suitable gaugeand providing insulating paper in the slots and applying varnish and packings and reassembling after repair. Testing and commisssioning after repair including to and fro transportation from site to workshop all as directed for the 30 HP capacity. Loc- INHS Kasturi | 2 | Job | |
32 | 32 | Supply only Crankshaft suitable for SMC 465 Compressor of cap 14 TR all as specified and as directed\nLoc - INHS Kasturi | 2 | Each | |
33 | 33 | Supply only Crankshaft Bearing suitable for SMC 465 Compressor of cap 14 TR all as specified and as directed\nLoc - INHS Kasturi | 4 | Each | |
34 | 34 | Supply only Connecting Rod suitable for SMC 465 Compressor of cap 14 TR all as specified and as directed\nLoc - INHS Kasturi | 8 | Each | |
35 | 35 | Supply only Piston for SMC 465 Compressor of cap 14 TR all as specified and as directed\nLoc - INHS Kasturi | 8 | Each | |
36 | 36 | Supply only Piston Ring suitable for SMC 465 Compressor of cap 14 TR all as specified and as directed\nLoc - INHS Kasturi | 8 | Set of 4 | |
37 | 37 | Supply only Piston Pin suitable for SMC 465 Compressor of cap 14 TR all as specified and as directed\nLoc - INHS Kasturi | 1 | Each | |
38 | 38 | Supply only Suction Reed suitable for SMC 465 Compressor of cap 14 TR all as specified and as directed\nLoc - INHS Kasturi | 8 | Each | |
39 | 39 | Supply only Disharge Reeds suitable for SMC 465 Compressor of cap 14 TR all as specified and as directed\nLoc - INHS Kasturi | 8 | Each | |
40 | 40 | Supply only suction valve spring suitable for SMC 465 Compressor of cap 14 TR all as specified and as directed\nLoc - INHS Kasturi | 8 | Each | |
41 | 41 | Supply only discharge valve spring suitable for SMC 465 Compressor of cap 14 TR all as specified and as directed\nLoc - INHS Kasturi | 8 | Each | |
42 | 42 | Supply only solenoid valve assembly suitable for SMC 465 Compressor of cap 14 TR all as specified and as directed\nLoc - INHS Kasturi | 2 | Each | |
43 | 43 | Supply only Safety Valve Assembly suitable for SMC 465 Compressor of cap 14 TR all as specified and as directed\nLoc - INHS Kasturi | 2 | Set | |
44 | 44 | Supply only Oil Pump suitable for SMC 465 Compressor of cap 14 TR all as specified and as directed\nLoc - INHS Kasturi | 2 | Each | |
45 | 45 | Supply only Head Gasket suitable for SMC 465 Compressor of cap 14 TR all as specified and as directed\nLoc - INHS Kasturi | 2 | Set of 2 | |
46 | 46 | Supply only Crankcase Gasket suitable for SMC 465 Compressor of cap 14 TR all as specified and as directed\nLoc - INHS Kasturi | 2 | Set of 2 | |
47 | 47 | Supply only Cylinder Liner suitable for SMC 465 Compressor of cap 14 TR all as specified and as directed\nLoc - INHS Kasturi | 8 | Each | |
48 | 48 | Supply only Main Bearing Bush suitable for SMC 465 Compressor of cap 14 TR all as specified and as directed\nLoc - INHS Kasturi | 4 | Each | |
49 | 49 | Supply only main seal end rod bearing with washer suitable for SMC 465 Compressor of cap 14 TR all as specified and as directed Loc - INHS Kasturi | 4 | Each | |
50 | 50 | Supply only main pump end rod bearing with washer suitable for SMC 465 Compressor of cap 14 TR all as specified and as directed Loc - INHS Kasturi | 4 | Each | |
51 | 51 | Supply only compressor oil etc complete all as specified and as directed.\nMake - Power Oil/ Indian Oil | 50 | Ltr | |
52 | 52 | Supply only Refrigerent Gas for Central AC Plant of Cap 14TR x 3of Model No SMC 465 complete all as specified and as directed. Loc - INHS Kasturi | 63 | kg | |
53 | 53 | Supply, install, testing and commissioning of double skin, floor mounted, Air handling unit 6 rows deep cooling coil of nominal capacity 5000 CFM, 50 SP including Masonary work for foundation of AHU and comprising of the following :\n(i) 6 Row Cooling coils of copper tube with aluminium fins. \n(ii) Prefilter - 10 Micron\n(iii) Blower for AHU with suitable motor, TEFC squirrel cage induction motor for operation on 415 volts, 3 phase, AC supply with suitable starters with overload protection and single phase preventors with V belt and guard.\n(iv) Insulation of AHU and AHU room as specified.\n(v) Hepa Filter in addition to AHU model\nMake : Zeco or equivalant Voltas/Blue star\nLoc - INHS Kasturi | 2 | Job | |
54 | 54 | Supply, install, testing and commissioning of Monoblock centrifugal pump set 05 HP capacity, LPS11 to 24, HEAD 06 to 24 MTR including Masonary work for foundation of Pump, Make :- Kirloskar KDI 520+ or equivalent | 2 | Job | |
55 | 55 | S&F in replacement of existing M.S PIPE medium grade 65 mm all as specified and directed | 15 | RM | |
56 | 56 | S&F in replacement of existing M.S PIPE medium grade 50 mm all as specified and directed | 12 | RM | |
57 | 57 | S&F in replacement of existing M.S PIPE medium grade 40 mm all as specified and directed | 10 | RM | |
58 | 58 | S&F in replacement of existing Butter fly valve 65mm all as specified and directed | 1 | Each | |
59 | 59 | S&F in replacement of existing Butter fly valve 50mm all as specified and directed | 4 | Each | |
60 | 60 | S&F in replacement of existing NRV 65 mm all as specified and directed | 4 | Each | |
61 | 61 | S&F in replacement of existing Pot strainer 65 mm all as specified and directed | 1 | Each | |
62 | 62 | S&F Fabricated rectangular square duct made out of 24 gauge GI sheet in L shaped hollow profit including all accessories such as corner, carriage bolt hangers, gasket and seal the longitudinal joints with and including approved sealant complete | 60 | Sqm | |
63 | 63 | S&F Fabricated rectangular square duct made out 22 gauge GI sheet in L shaped hollow profit including all accessories such as corner, carriage bolt hangers, gasket and seal the longitudinal joints with and including approved sealant complete | 10 | Sqm | |
64 | 64 | M & L for duct insulations with resin bonded fiber glass wool ensity 24kg/cum with laminated aluminium barriers thick 40 mm and including following :\na) Cleaning the duct surface\nb) Applying rubber based adhesive CPRXA compound.\nC) Sealing all the joints and circular cover laps including alumium foil tape 50 mm\nd) Securing the insulation including mechanically fastened, nylons/ sheets straps size 12/50mm, maximum intervals 1.2 mtrs. | 70 | Sqm | |
65 | 65 | M & L for Acoustic lining of duct work with 25mmthick resin bonded fibre glass of 32 kg/m3 covered with RP tissue of thickness 0.3mm covered with 24G perforated. | 10 | Sqm | |
66 | 66 | M & L for Fire Damper with fusible link made out of 18 gauge GI sheet with overlap to avoid leakage | 1 | Sqm | |
67 | 67 | M & L for Manual Volume control damper made out of 18 GI sheet with over lap to avoid leakage | 1 | Sqm | |
68 | 68 | S& F SITC of duct mounted strip Heater Plenum of 04 KW rating | 1 | Each | |
69 | 69 | Supply and fixing expansion valve suitable for 28 TR compelte. | 2 | Each | |
70 | 70 | S&F in replacement of existing LT XLPE 1100 V armured cable copper conductor 3 core 2.5 Sqmm all as specified and directed | 15 | RM | |
71 | 71 | S&F in replacement of existing LT XLPE 1100 V armured cable copper conductor 3 core 4 Sqmm all as specified and directed | 20 | RM | |
72 | 72 | S&F in replacement of existing LT XLPE 1100 V armured cable copper conductor 4 core 10 Sqmm all as specified and directed | 15 | RM | |
73 | 73 | S&F in replacement of existing V belt for SMC 465 Compressor of cap 14 TR all as specified and as directed\nLoc - INHS Kasturi | 3 | Set of 3 | |
74 | 74 | S&F in replacement of existing Suction Valve Seat for SMC 465 Compressor of cap 14 TR all as specified and as directed Loc - INHS Kasturi | 3 | Each | |
75 | 75 | S&F in replacement of existing Discharge valve Seat for SMC 465 Compressor of cap 14 TR all as specified and as directed Loc - INHS Kasturi | 3 | Each | |
76 | 76 | S&F in replacement of existing Loading-Unloading Valve for SMC 465 Compressor of cap 14 TR all as specified and as directed Loc - INHS Kasturi | 3 | Each | |
77 | 77 | S&F in replacement of existing LP Hp Cut out for SMC 465 Compressor of cap 14 TR all as specified and as directed\nLoc - INHS Kasturi | 3 | Each | |
78 | 78 | S&F in replacement of existing Oil Pressure Switch for SMC 465 Compressor of cap 14 TR all as specified and as directed Loc - INHS Kasturi | 3 | Each | |
79 | 79 | S&F in replacement of existing LP, HP & OP Gauge for SMC 465 Compressor of cap 14 TR all as specified and as directed Loc - INHS Kasturi | 3 | Set of 3 | |
80 | 80 | S&F in replacement of unservicable water pressure gauge 4" dia suitable to size at site for Range 0 to 150PSI all as specified and as directed Loc - INHS Kasturi | 4 | Each | |
81 | 81 | M & L for preparation of old painted surfaces of central AC installation equipment synthetic enamel paint by spray painting including filling cavities with filler for air conditioning plant of capacity 14 TR X 3 No's comprising compressor motors, condenser AHU, refrigerant piping control water pipe lines, pump, cooling tower, panel board incl DG set, alternator, LT panel board etc complete all as specified and as directed. Location- Kasturi AC Plant | 1 | Job | |
82 | 82 | S&F in replacement of existing Temperature Thermometer all as specified and as directed\nLoc - INHS Kasturi | 6 | Each | |
83 | 83 | M&L for De-scaling of condensor of 14 TR Cap by using pumpset complete all as directed by Engineer-in-Charge | 3 | Job | |
84 | 84 | Dismantling of Existing Old Chimney of Incinerator of Top Dia 250 mm, Height is 28 mtr, Approx weight 6000 kg and cutting of 3 m pieces and loading in truck by \ncrane complete all as specified and as directed | 1 | Each Job | |
85 | 85 | Supply and Erection of Incinerator Chimney (M.S) wall supported of Following specification - \nOuter Dia: 250 mm\n(Considering Heat utilization 4 lakh kilo calories) \nHeight: 12 m straight with Guy rope support\nMS 7 mm Thick Monkey ladder\nSupoort Temperature - HT ( 400 deg c )\nPainting - Silver Painting\nincluding Civil foundation work for these incinerator chimney also Supply & erection of ducting material, cutting and reconnection of new chimney to existing system complete all as specified and as directed\n | 1 | Each Job | |
86 | 86 | Supply & Erection of refractory material, lining of refractory material including replacement of Furnace bed of incinerator of Following specification:-\nBurning capacity - 100 kg/hr\nFuel - High Speed Diesel\nPower consumption - 7.5 to 10 KW\nincluding taking down of existing Refractory material, lining of Refractory material and Furnace Bed complete all as specified and as directed\n | 1 | Job | |
87 | 87 | Supplying, Installing, Testing & commissioning of the Hot Water Control Panel (Electric) in Replacement of existing Control panel of HOT Water Generation Plant (Aquamatic Type, cap- 2.00 Lakhs Kcal, Model -AMW -02, HSD Fired, Make - Thermax): | 4 | Each | |
88 | 88 | Supplying, Installing, Testing & commissioning of the Copper Coils of calorifier in Replacement of existing Calorifier Coil of HOT Water Generation Plant (Aquamatic Type, cap- 2.00 Lakhs Kcal, Model -AMW -02, Make - Thermax) complete all as specified and as directed\nNote :- i. Rate is Inclusive for Gas Cutting of Upper Dome (of Calorifier) for Removing Purpose\nii. Rate is Inclusive for Welding of Upper Dome after proper fixing of Coils of calorifier\niii. Job Includes the No Leak Test of calorifier from Upper Dome Area \niv . Job Includes the Taking out the Coils\nv. Job Includes Nut, Bolts, Packing, Boring & drilling holes in existing body if Required) | 1 | Job | |
89 | 89 | Taking down Aluminium/GI strip of any size complete all as specified and as directed. | 50 | RM | |
90 | 90 | Fixing only old Aluminium/GI strip of any size on Insulator/roof/wooden Block/Pcc block complete all as specified and directed.(Note:-Qoted rates are inclusive of drilling and new GI screws/nut bolts). | 50 | RM | |
91 | 91 | Supply and Fix in replacement single pointed air termination aluminium rod, 12mm dia 300 mm long complete all as specified and as directed. | 30 | Each | |
92 | 92 | Supply and Fix in replacement Aluminium strip 25mmx3.15mm complete with saddles and fixing screw for fitting the strip complete all as specified and as directed. (Note:-Qoted rates are inclusive of drilling and new GI screws/nut bolts). | 920 | RM | |
93 | 93 | Supply and Fix in replacement GI strip 32 mm x 6 mm complete with saddles and fixing screw for fitting the strip complete all as specified and as directed. (Note:-Qoted rates are inclusive of drilling and new GI screws/nut bolts). | 645 | RM | |
94 | 94 | M&L for Test point terminal block made of gun metal or phosphorus bronze size 75x75x25 mm drilled and screwed including 3 Nos 8mm dia 25mm long hex head screw complete all as specified and as directed | 35 | Each | |
95 | 95 | M&L for fixing of insulator BMD 40 for mounting of earth continuity conductor complete all as specified and as directed. | 1000 | Each | |
96 | 96 | M & L earthing complete with galvanized steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.’25 mtr below normal ground level) with top edge of the plate not less 1.5 mtr below normal ground level connected to galvanized earth plate with 32x6 mm thick GI strip by means of suitable size of GI nuts, bolts, check nuts and washers all as specified in electrical plate SSR Part I including necessary .Exc & earth work, providing charcoal and salt dust layers and construction of PCC pit in 1:3:6 using 20 mm size graded stone aggregate, precast RCC 40 mm thick cover in 1:2:4 type B 1 with 12 mm dia steel MS plain bar, lifting handle GI pipe of 50 mm bore for earth lead protection andGI pipe 15 mm dia for watering, with funnel and wire mesh including testing on completion. All as specified and as directed incl dismentling existing unsv earthing of panel. | 35 | Each | |
97 | 97 | M&L for cement concrete Type B1 (1:2:4) 20 mm graded stone aggregate as in coping/ support blocks including demolation of existing concrete complete all as specified and as directed by EIC at site. | 3 | Cum | |
98 | 98 | M&L for 40mm dia MS pipe bracket 450mm long with flange welded at the one end and arrangement for mounting of air termination rod at the other end complete all as specified and as directed. | 30 | Each |