Construction Of District Headquarter Office Building For Excise And Taxation Department Sector 32 At Gurugram ( Detailed Estimate For Pdg . Fire Alarm System - Public Address System ) , XEN(E) Gurugram-Haryana

Public Works Department-PWD has published Construction Of District Headquarter Office Building For Excise And Taxation Department Sector 32 At Gurugram ( Detailed Estimate For Pdg . Fire Alarm System - Public Address System ) . Submission Date for this Tender is 09-06-2020. Building Work Tenders in XEN(E) Gurugram Haryana. Bidders can get complete Tender details and download the document.




Tender Notice

24314124
Corrigendum : Construction Of District Headquarter Office Building For Excise And Taxation Department Sector 32 At Gurugram ( Detailed Estimate For Pdg . Fire Alarm System - Public Address System )
Open Tender
Indian
Haryana
XEN(E) Gurugram
09-06-2020

Tender Details

Construction Of District Headquarter Office Building For Excise And Taxation Department Sector 32 At Gurugram ( Detailed Estimate For Pdg . Fire Alarm System - Public Address System )

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 21-May-2020 DateCorrigendum Date 08-06-2020
2 04-Jun-2020 Corrigendum Other 08-06-2020
3 08-Jun-2020 DateCorrigendum1 Date 09-06-2020

Key Value

Document Fees
INR 5000 /-
EMD
INR 75500.0 /-
Tender Value
INR 37.71 Lakhs /-

BOQ Items

Name of Work : Construction of District Headquarter office building for Excise & Taxation Department Sector 32 at Gurugram (detailed estimate for pdg. fire alarm system & public address system)
Sl. No. Item Description Item Code / Make Quantity Units
1 1 SITC of Micro processor based 2 wire fault tolerant, networkable type fire alarm / detection control panel ( having nos. of 2 loops to suit minimum 20% extra over the nos. of fire detectors. The panel shall be able to give location of all fire / fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON/OFF respective control module when ever any alarm is triggered. The panel shall have rectifier, loop cards, minimum 160 character L C D unit/ 5.7’’TFT to indicate Fire / Fault Signal with address and analog output, external/inbuilt printer to log all fire or fault events complete in all respects. The Panel Shall be sheet Steel power coated, sealed to IP30. The Panel shall have 20 Zones with individual LED Indicators, expandable to 80LED Indicators. The Panel shall have 3 Serial Ports. The panel shall have a built in power supply and battery charger along with maintenance free 24 AH,2 x 12 volt SMF lead acid batteries capable of running for a minimum of 24 hours with battery charger complete as required. And conforming to BS5839 standards and Duly Approved by EN 54/UL/VDS/ as per specifications complete in all respect up to the entire satisfaction of Engineer-in – charge of work Makes : Bosch FPA 5000 Series, Notifier NFS 3030 / Cerberus PRO by Siemens / Edward EST-3. 1 Each
2 2 SITC of addressable multisensor detector with a combination of Optical and Thermal including mounting base, auto addressing feauture as required. Detetctor should have 2 as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements. High resistance to electromagnetic effects in accordance with EFSG agreement EFSG/F/97/005 .Detector should monitor Electromagnetic interference and report to the panel - current and average values. EMC safety for detector shall be 50 V/m. Shall be EN54/ VDs/UL certification. (Detectors without Inbuilt Isolators may be considered with an additional Isolator Module after 20 devices) Makes: Bosch / Siemens Cerberus / Notifier/ Edwards 461 Each
3 3 SITC ofaddressable Heat detector with fixed and rate of raise feature including mounting base with LED… etc. complete as required. Each Detector should have 2 as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements. High resistance to electromagnetic effects in accordance with EFSG agreement EFSG/F/97/005 .Detector should monitor Electromagnetic interference and report to the panel - current and average values. EMC safety for detector shall be 50 V/m. Shall be EN54/ VDs/UL certification. (Detectors without Inbuilt Isolators may be considered with an additional Isolator Module per detector) Makes: Bosch / Siemens Cerberus / Notifier/ Edwards 175 Each
4 4 SITC of intelligent Analog Addressable type Manual Call Point having Surface or flush mounting option fully compliat to EN 54 having Rotary Decade switches for addressing with back box for mounting as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required to complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work. Makes: Bosch / Siemens Cerberus / Notifier/ Edwards 34 Each
5 5 SITC of Addressable Loop powered sounder with strobe / flasher complete with mounting base as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required to complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work. Makes: Bosch / Siemens Cerberus / Notifier/ Edwards 34 Each
6 6 SITC of Glow Type EXIT Sign Board photo luminescent of size 300 mm x 250 mm x 1.5 mm rigid sheet signage containing Zink Sulphate as bare chemical class – 1 material PSPA fixed on 3 mm acrylic sheet on both side showing marking (running man, Arrow and Exit) and hanged with the ceiling with chain and fastener including cost of labour & material required to complete the job in all respect up to the entire satisfaction of Engineer-in-Charge of work Make PES/Giolite/OMEX 34 Each
7 7 SITC of Addressable Control Relay Module with flexible network structures with a maximun switching current of 1A @ 30V DC. Shall be EN54/UL/VDS Certification Makes: Bosch / Siemens Cerberus / Notifier/ Edwards 15 Each
8 8 SITC of Addressable Monitor Module for monitoring of a line with EOL resistor/ Potential free contact/ voltage monitoring shall be EN54/UL/VDS approved. (In case of 2 monitoring features in one module (points) each point shall be consider separately for payment). Makes: Bosch / Siemens Cerberus / Notifier/ Edwards 15 Each
9 9 SITC of Analog Addressable type Active Repeater fire alarm panel with Backlit LCD Display, having controls for reset, mute, Accept, Silence alarms and self test conforming to BS5839 standards and Duly approved by EN54/UN54/VDS with all labour and material required to complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work. Makes: Bosch / Siemens Cerberus / Notifier/ Edwards 3 Each
10 10 SITC of UL/EN54/LPCB listed and FM Approved Line Isolator for Isolating the section of circuit in case of short in the addressable Loop wiring Makes: Bosch / Siemens Cerberus / Notifier/ Edwards 50 Each
11 11 SITC of minimum 1000 Mtr. Range Siren generatorprovided at the roof of the building with separate power suppl, relay etc. with all accessories required to complete the job in all respect up to the entire satisfaction of engineer incharge. Make: National/Kheraj 1 Each
12 12 SITC of controller unit 6-zone system pre-amplifier, with single or dual channel operation. Two input channels for call stations , Universal input for microphone/line, with speech optimized tone control , Three inputs for BGM selection and music optimized tone control , Front panel zone selection for BGM and call station zone selection for calls, S/N (flat at max volume) >63 dB (mic); >70 dB (line), S/N (flat at min volme/muted) >75 dB, CMRR >40 dB (50 Hz – 20 kHz), Line input 3 x, Master output 1 x, Frequency response 50 Hz to 20 kHz (+1 / -3 dB) complete in all respect Make Honeywell/BOSCH/Henrich 1 Each
13 13 SITC of Booster amplifier 480 watts Frequency response: 60 Hz to 15 khz (+1/3db), Inputs :XLR & phone jack , Input 1, Input 2-4, Impendence :20kO, Sensitivity : 1 V balanced , S/N >: >85 dB complete in all respect Make Honeywell/BOSCH/Henrich 1 Each
14 14 SITC of Stylish 6-zone call station, Six zone selection keys, all-call key and momentary PTT-key for calls Selectable gain, speech filter and limiter for improved intelligibility LED indications for zone selection, fault and emergency state Voltage range 18 – 24V Nominal sensitivity 85 dB SPL (gain preset 0dB) Gain preset +6 / 0 / -15 dB Equivalent input noise level 25 dBSPLA Frequency response 100Hz – 16kHz complete in all respect Make Honeywell/BOSCH/Henrich 1 Each
15 15 Supply, Installation, Testing & commissioning of Horn Loudspeaker made with ABS, waterand dust protected to IP 65,Sound pressure level at 15W/1W - 115/103 dB (SPL), Effective frequency range 500 Hz to 5 kHz, Rated power 15W Make Honeywell/BOSCH/Henrich 2 Each
16 16 Supply, Installation, Testing & commissioning of Celling Mount Speaker with Plastic Mount or without mount as per site requirement for operation 6 Watts Make Honeywell/BOSCH/Henrich 105 Each
17 17 SITC of PVC unsheathed s/c stranded ( ISI marked ) copper contuvtor cable 1100v grade in existing pipe excluding cost and erection of pipe but including connection etc. with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer – in charge of work MAKE FINOLEX/POLYCAB/HAVELLS PVC unsheathed copper size 1.5 sq mm single core 4000 Mtr
18 18 2 core PVC unsheathed copper size 1.5 sq mm 1000 Mtr
19 19 SITC of CAT 6 UTP Cable Make: Schenider/Molex/AMP 305 Mtr
20 20 SITC of PVC Conduit Pipe, 25mm medium, ISI Mark with complete accessories. Make: Diplast/AKG/BEC 2000 Mtr
21 21 SITC of 22 U Standard rack to place all Av equipment Make Valrack, Comrack,Hive Networks 1 Each
22 22 SITC of battery backup for controllers ( 3 KVA UPS on line with 1 hours backup ) Make APC/ LIEBERT EMERSON/Microtek 1 Each
23 23 Supply & erection of FIRE EXTINGUISHERS duly hang on wall with necessary hook complete in all respect (Make: Safex/Minimax/ Ceasefire) ABC Dry power type fire Extinguishers of 5 kg. capacity 54 Each
24 24 Co2 type fire extinguishers of 4 Kg capacity 12 Each