Provision Of Package Type Air Conditioner In Ot And Icu At 4 Afh At Af Station Kalaikunda Under Ge ( Af ) Kalaikunda Provn Of Package Type Air Conditioner, AT AF STN KALAIKUNDA-West Bengal

Military Engineer Services-MES has published Provision Of Package Type Air Conditioner In Ot And Icu At 4 Afh At Af Station Kalaikunda Under Ge ( Af ) Kalaikunda Provn Of Package Type Air Conditioner. Submission Date for this Tender is 08-06-2020. Air Conditioner Tenders in AT AF STN KALAIKUNDA West Bengal. Bidders can get complete Tender details and download the document.




Tender Notice

24208344
Corrigendum : Provision Of Package Type Air Conditioner In Ot And Icu At 4 Afh At Af Station Kalaikunda Under Ge ( Af ) Kalaikunda Provn Of Package Type Air Conditioner
Open Tender
Indian
West Bengal
AT AF STN KALAIKUNDA
08-06-2020

Tender Details

Provision Of Package Type Air Conditioner In Ot And Icu At 4 Afh At Af Station Kalaikunda Under Ge ( Af ) Kalaikunda Provn Of Package Type Air Conditioner

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 14-May-2020 Ammendment in tender documents and revised BOQ for PROVN OF PACKAGE TYPE AIR CONDITIONER IN OT AND ICU AT 4 AFH AT AF STATION KALAIKUNDA UNDER GE (AF) KALAIKUNDA BOQ 25-05-2020
2 23-May-2020 Change in date for PROVN OF PACKAGE TYPE AIR CONDITIONER IN OT AND ICU AT 4 AFH AT AF STATION KALAIKUNDA UNDER GE (AF) Date 01-06-2020
3 01-Jun-2020 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 08-06-2020

Key Value

Document Fees
INR 1000 /-
EMD
INR 130000.0 /-
Tender Value
INR 70 Lakhs /-

BOQ Items

Name of Work: PROVISION OF PACKAGE TYPE AIR CONDITIONER IN OT AND ICU AT 4 AFH AT AIR FORCE STATION KALAIKUNDA
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Sch 'A' Sec -I (Building work)\nNote:- This schedule is not pre-priced by MES and the pre-priced rate as "Rs. 0.00" indicated under Col.5. signifies this fact only\n Construction of room for AHU of OT with permanent specification complete all as specified and shown in drawing. 1 Each
2 2 Sch 'A' Sec -I (Building work)\nNote:- This schedule is not pre-priced by MES and the pre-priced rate as "Rs. 0.00" indicated under Col.5. signifies this fact only\n Construction of room for AHU of ICU with permanent specification complete all as specified and shown in drawing. 1 Each
3 3 Total amount of Sch 'A' Part-II (Site clearance and earthwork)\nPrepriced amount B/F from Sl page No. 24 1 Lump sum
4 4 Total amount of Sch 'A' Part-III (Internal Electrification) \nPrepriced amount B/F from Sl page No. 26 1 Lump sum
5 5 Total amount of Sch 'A' Part-IV (Internal water supply) \nPrepriced amount B/F from Sl page No. 27 1 Lump sum
6 6 Total amount of Sch 'A' Part-V( External electric supply ) \n Prepriced amount B/F from Sl page No. 29 1 Lump sum
7 7 Total amount of Sch 'A' Part-VI( Sewage disposal) \nPrepriced amount B/F from Sl page No. 31 1 Lump sum
8 8 Total amount of Sch 'A' Part-VII (Road / Path)\nPrepriced amount B/F from Sl page No. 32 1 Lump sum
9 9 Total amount of Sch 'A' Part-VIII (Refrigeration/Air conditioning cooling appliances) \n Prepriced amount B/F from Sl page No. 33 1 Lump sum
10 10 Total amount of Sch 'A' Part-IX (False ceiling)\nPrepriced amount B/F from Sl page No. 34 1 Lump sum
11 11 Total amount of Sch 'A' Part-X (Misc work)\nPrepriced amount B/F from Sl page No. 36 1 Lump sum
12 12 Sch 'A' Part-XI (Misc Items)\nNote:- This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under Col.5 signifies this fact only.
13 13 S&F LED 18 Watt tube light fitting (T8 type) ,single end connection type LED retrofit tube lamp 18 W , 240 Volt, PF > 0.90, colour Temp 6500 K, System Luminious efficacy > 100Lm/W, complete with powder coated CRCA decorative box type batten suitable for surface mounting on wall, complete fitting including connecting with PVC insulated multistranded copper flexible cable 0.5 sqmm three core, and PVC round/ square box white colour x 2 Nos for mounting of fitting complete all as specified & directed. Make :- Bajaj (Batten BLRB-DB-118 box type batten suitable for 18 watt retofit LED tube single side connection type). LED lamp 18 Watt complete all as specified and as directed \nNOTE:-Box type batten and LED tube shall be of same make 12 Each
14 14 S&F LED bulkhead light of 10W with polycarbonate body and diffuser , IP-65, PF>0.95 complete all as specified and directed by Engineer in charge. 4 Each
15 15 Supply and fixing lamp holder , PVC/Poly carbonate type with back plate suitable for batten fittings to be fixed on PVC box including supply and fixing 11 watt LED lamp. Make For holder complete all as specified and directed by Engineer in charge. 5 Each
16 16 S&F LED building security light fittings of 60 Watts LED made up of die cast housing with toughed glass and individual LEDs with secondary optics and IP 66 protection , including mounting bracket of 40 mm light gradge GI pipe of suitable length fixed on wall complete all as specified and as directed by Engineer-in-Charge.\nNote:- All LED street light shall be properly connected with earth dolly provided with fittings 4 Each
17 17 S&F MCB SP 240 volts 10 Amps, 10 KA breaking capacity, 'C' Curve including connection with suitable size aluminium / copper lugs complete all as specified and directed by Engr-In-Charge 6 Each
18 18 S&F MCB DP 20 Amps 10 KA , 'C' Curve including connection with suitable size aluminium / copper lugs including taking down u/s complete all as specified and directed by Engr-In-Charge 3 Each
19 19 Supply and fixing Exhaust fan 300 mm sweep, metal body, with bird screen & double ball bearing powerful and energy efficient motor , single phase , 240 volt ,50 Hz , AC complete all as specifiedand as directed. 1 Each
20 20 Supply , installation , testing and commissioning of Automatic Servo controlled voltage stabilizer(Confirming to BIS 9815:Part1-1994) Three phase , 50 Hz , Naturally oil cooled , copper wound , indoor type , metallic body duly powder coated with lifting hooks two nos ,digital display type , relay free smooth and silent operation , efficiency more than 95% with over load/short circuit protection , high/low voltage cut off , by pass arrangement in case of emergency & designed for input variation between 300V to 480V with output voltage stabilizer at 415V with accuracy± 2.5% and speed of correction 8 Volts per second and of capacity 50 kVA. complete all as specifiedand as directed. \nNOTE:-Contractor has to be submit general arrangement drawing of stabilizer and take approval of GE before placing the order for procurement 3 Each
21 21 M & L for Fly ash bricks of size 250 mm X 120 mm X 70 mm laid in trenches as in protection of under ground cables all as specified and directed. 3200 Each
22 22 Supply,installation,testing and commissioning LT panel board suitable for working on 3 phase,4 wire, 415 volts, AC, 50Hz, Outdoor type, cubicle, floor mounted,dust and vermin proof, with IP-64 protection fabricated out 3.15mm thick CRCA sheet duly powder coated painting,CPRI approved,front and rear opening with locking arrangement, cable alleys, bus bar (400 Amp capacity) chamber and switch gear compartments,copper bus bar duly covered with heat shrinkable sleeves color coaded fixed on DMC/SMC insulators bottom cable entry hole for incoming and outgoing cables and connecting MCCBs/switch gears with main bus bar by using copper bus links or copper conductor flexible wires of suitable rating and connecting with terminal blocks of approprite rating by cable lugs,thmbles etc.Earthing terminals,affixing danger notice plate, 1 Each
23 22.1 Item no 22 Cont….\neach compartment shall be numbered/lettered for indication and control wiring with flexible copper conductor cables of suitable size and adequate length,control fuses/MCBs and PCC foundation(1:3:6) as per site requirement and a clear space to be kept from bottom of panel for proper termination of cable and including cable connection to MCCBs,switch gear with necessary cable glands,lugs,nut,bolts and washer etc, complete all as specified and directed including comprising of following.(Proposed Main AC Panel-P1)\n(a) MCCB 160Amp,Thermal magnetic release, 4 Pole, 35 kA, 415 volts, AC, 50Hz - 01 No ( I/C)\n(b) MCCB 63 Amp,Thermal magnetic release, 4 Pole, 25 kA, 415 volts, AC, 50Hz - 03 No ( O/G 2W+1S)\n\n
24 22.2 Item no 22 Cont…\n.(c) MCB 40Amp, 4 Pole, 18 kA, 415 volts, AC, 50Hz - 01 No (O/G)\n(d) MCB 10Amp, 2 Pole, 10 kA, 220 volts, AC, 50Hz - 01 No (O/G)\n(e) Indicating Lamp - 01 set (03Nos)\n(f) Ammeter 0-300 volts with CTs and slector switch - 01 No\n(g) On load Changeover Switch 250Amp, 4P,Conforms IS/IEC 60947-3 - 01No\nNOTE:- (i) Contractor has to submit the drawing of LT panel and take approval of GE before placing the order for fabrication of panel.\n(ii) All MCCB’s in above item shall be characteristics of thermal magnetic release type, Ics = 100% Icu, with adjustable overload and short circuit setting including providing spreader terminals and phase barriers.\n
25 23 Supply,installation,testing and commissioning LT panel board suitable for working on 3 phase,4 wire, 415 volts, AC, 50Hz, Indoor type, cubicle, floor mounted,dust and vermin proof, with IP-54 protection fabricated out 2 mm thick CRCA sheet duly powder coated painting,CPRI approved,Front and rear opening type with provision of cable alley on both (incoming and outgoing) side. with locking arrangement, cable alleys, bus bar (200 Amp capacity) chamber and switch gear compartments,copper bus bar duly covered with heat shrinkable sleeves color coaded fixed on DMC/SMC insulators bottom cable entry hole for incoming and outgoing cables and connecting MCCBs/switch gears with main bus bar by using copper bus links or copper conductor flexible wires of suitable rating and connecting with terminal blocks of approprite rating by cable lugs,thmbles etc.Earthing terminals,affixing danger notice plate,each 1 Each
26 23.1 Item no 23 cont...\ncompartmentshall be numbered/lettered for indication and control wiring with flexible copper conductor cables of suitable size and adequate length,control fuses/MCBs and PCC foundation(1:3:6) as per site requirement and a clear space to be kept from bottom of panel for proper termination of cable and including cable connection to MCCBs,switch gear with necessary cable glands,lugs,nut,bolts and washer etc, complete all as specified and directed including comprising of following.(Proposed ICU Panel P-2)\n(a) MCCB 100 Amp,Thermal magnetic release, 4 Pole, 35 kA, 415 volts, AC, 50Hz - 01 No ( I/C)\n(b) MCCB 63 Amp,Thermal magnetic release, 4 Pole, 25 kA, 415 volts, AC, 50Hz - 02 No ( O/G 1W+1S)\n
27 23.2 Item no 23 cont…\n(c) MCB 40Amp, 2 Pole, 10 kA, 415 volts, AC, 50Hz - 01 No ( O/G)\n(d) MCB 10Amp, 2 Pole, 10 kA, 220 volts, AC, 50Hz - 01 No ( O/G)\n(e) Indicating Lamp - 01 set (03Nos)\n(f) Voltmeter 0-500 volts with selector switch - 01 No\n(g) Ammeter 0-300 volts with CTs and slector switch - 01 No\nNOTE:- (i) Contractor has to submit the drawing of LT panel and take approval of GE before placing the order for fabrication of panel.\n(ii) All MCCB’s in above item shall be characteristics of thermal magnetic release type, Ics = 100% Icu, with adjustable overload and short circuit setting including providing spreader terminals and phase barriers.
28 24 Supply,installation,testing and commissioning LT panel board suitable for working on 3 phase,4 wire, 415 volts, AC, 50Hz, indoor type, cubicle, floor mounted,dust and vermin proof, with IP-63 protection fabricated out 2 mm thick CRCA sheet duly powder coated painting,CPRI approved,Front and rear opening type with provision of cable alley on both (incoming and outgoing) side with locking arrangement, cable alleys, bus bar (300 Amp capacity) chamber and switch gear compartments,copper bus bar duly covered with heat shrinkable sleeves color coaded fixed on DMC/SMC insulators bottom cable entry hole for incoming and outgoing cables and connecting MCCBs/switch gears with main bus bar by using copper bus links or copper conductor flexible wires of suitable rating and connecting with terminal blocks of approprite rating by cable lugs,thmbles etc.Earthing terminals,affixing danger notice plate,each 1 Nos
29 24.1 Item no 24 cont... \ncompartment shall be numbered/lettered for indication and control wiring with flexible copper conductor cables of suitable size and adequate length,control fuses/MCBs and PCC foundation(1:3:6) as per site requirement and a clear space to be kept from bottom of panel for proper termination of cable and including cable connection to MCCBs,switch gear with necessary cable glands,lugs,nut,bolts and washer etc, complete all as specified and directed including comprising of following.(Proposed OTs Panel- P3)\n(a) MCCB 160Amp,Thermal magnetic release, 4 Pole, 35 kA, 415 volts, AC, 50Hz - 01 No ( I/C)\n(b) MCCB 63 Amp,Thermal magnetic release, 4 Pole, 25 kA, 415 volts, AC, 50Hz - 03 No ( O/G 2W+1S)
30 24.2 Item no 24 cont…\n(c) MCB 40Amp, 4 Pole, 18 kA, 415 volts, AC, 50Hz - 01 No (O/G)\n(d) MCB 10Amp, 2 Pole, 10 kA, 220 volts, AC, 50Hz - 01 No (O/G)\n(e) Indicating Lamp - 01 set (03Nos)\n(f) Voltmeter 0-500 volts with selector switch - 01 No\n(g) Ammeter 0-300 volts with CTs and slector switch - 01 No
31 25 Supply and fixing of MCCB 250 Amp 4 pole 415 V, 35KA, 50HZ, thermal magnetic release type, Ics = 100% Icu with adjustable overload and short circuit setting including providing spreader terminals and phase barriers. MCCB to be installed in existing panel including making all connections complete all as specified and directed by Eng-in-charge. 1 Each
32 26 M & L for Earthing complete with copper earth plate 60 cm X 60 cm X 3.15 mm thick, buried directly in ground (earth pit not less than 3.25 metres deep below ground level) with top edge of the plate not less than 2.5 metres below normal ground level, connected to copper strip 20 X 3 mm as earth lead by means of bolts, nuts, check nuts and washers of brass and as shown in electrical plate No. 3 connected to earthing test point including necesary excavation any type of soil , RCC chamber cover plate , wire mesh , funnel ,test point , 50 mm dia GI pipe light grade for protection pipe and watering etc complete and testing on completion. \nNote:- Copper strip upto 7.5 RM will be included in the item rate and copper strip beyound 7.5 RM will be measured seperately. 12 Each
33 27 M & L for manual boring of hole under road,pavement,hard standing by required T & P without disturbing the top surface of existing area for throughing the cable in GI pipe of 80-100 mm dia complete all as specified and directed. 25 Rm
34 28 Design,Supply, Installation, testing & commissioning of Dx Out door AC plant, condensing unit fitted with scroll compressor, Copper condensor coil, condensor fan with motor of following tonnages for OTs & ICU capacities including pressure testing, nitrogen gas flushing, vaccumisiing etc complete all as specified and direted by Engr-in-Charge.\n(a) Outdoor Unit Nominal Capacity - 5.5 TR (capable to run with R410a Refrigerant) 4 Each
35 29 Design,Supply, Installation, testing & commissioning of Dx Out door AC plant, condensing unit fitted with scroll compressor, Copper condensor coil, condensor fan with motor of following tonnages for OTs & ICU capacities including pressure testing, nitrogen gas flushing, vaccumisiing etc complete all as specified and direted by Engr-in-Charge.\n(a) Outdoor Unit Nominal Capacity - 8.5 TR (capable to run with R410a Refrigerant) 4 Each
36 30 Design,Supply , Installation, testing & commissioning , Double skin construction Air Handling Unit with variable speed induction fan motor, humidification and dehumidification arrangement,Mixing Chamber, Combination Filter at Suction ( Pre filter with 20µ Filter & Fine Filter with 5µ Filter, Cooling Coil Section with 6RD DX Cooling Coil and SS304 Drain Tray, Fan Section with DIDW Centrifugal Blower with Backward Curved Impeller, Fan-Motor Mounting Base, Suitable capacity drive Motor with V-Belt Drive Package, Vibration Isolators and Fire Retardant Flexible Canvas Connector. Air Handling Unit shall have 46 mm thick Sandwich Insulated Panels with Thermal Break Profile with Pre-Coated GSS Outer Skin and 0.6 MM Thick Plain GSS Inner Skin and with Extruded Aluminium Frame Structure. VCD in Aluminium aerofoil construction to be provided in SA, FA, RA Openings, etc complete all as specified and directed by Engr-in-Charge.\n(a) AHU for OT-1 - 4500 cfm @ 140mm TSP with Dual Dx Coil (one operating one stand by) 1 Each
37 31 Design,Supply , Installation, testing & commissioning , Double skin construction Air Handling Unit with variable speed induction fan motor, humidification and dehumidification arrangement,Mixing Chamber, Combination Filter at Suction ( Pre filter with 20µ Filter & Fine Filter with 5µ Filter, Cooling Coil Section with 6RD DX Cooling Coil and SS304 Drain Tray, Fan Section with DIDW Centrifugal Blower with Backward Curved Impeller, Fan-Motor Mounting Base, Suitable capacity drive Motor with V-Belt Drive Package, Vibration Isolators and Fire Retardant Flexible Canvas Connector. Air Handling Unit shall have 46 mm thick Sandwich Insulated Panels with Thermal Break Profile with Pre-Coated GSS Outer Skin and 0.6 MM Thick Plain GSS Inner Skin and with Extruded Aluminium Frame Structure. VCD in Aluminium aerofoil construction to be provided in SA, FA, RA Openings, etc complete all as specified and directed by Engr-in-Charge.\n(b) AHU for OT-2 - 4500 cfm @ 140mm TSP (with single Dx Coil) 1 Each
38 32 Design,Supply , Installation, testing & commissioning , Double skin construction Air Handling Unit with variable speed induction fan motor, humidification and dehumidification arrangement, Mixing Chamber, Combination Filter at Suction ( Pre filter with 20µ Filter & Fine Filter with 5µ Filter, Cooling Coil Section with 6RD DX Cooling Coil and SS304 Drain Tray, Fan Section with DIDW Centrifugal Blower with Backward Curved Impeller, Fan-Motor Mounting Base, Suitable capacity drive Motor with V-Belt Drive Package, Vibration Isolators and Fire Retardant Flexible Canvas Connector. Air Handling Unit shall have 46 mm thick Sandwich Insulated Panels with Thermal Break Profile with Pre-Coated GSS Outer Skin and 0.6 MM Thick Plain GSS Inner Skin and with Extruded Aluminium Frame Structure. VCD in Aluminium aerofoil construction to be provided in SA, FA, RA Openings, etc complete all as specified and directed by Engr-in-Charge.\n(c)AHU for ICU - 3500 cfm @ 125 mm TSP (with Single Dx Coil) 1 Each
39 33 Supply , Installation, testing & commissioning Refrigeration Valves & Controls - Ball Valve, Expansion Valve, Dryer, Sightglass, Angle Valve & Cooling Thermostat For Major OT & ICU including all items as per site requirement for commissioning of plant as specified and directed by Engr-in-Charge. 3 Set
40 34 Supply Installation, testing & commissioning of Copper piping with19 mm/13 mm nitrile insulation from plant to AHU, including brassing, purging and leakge testing , installation of pipe line in neat manner on tray complete all as specified and directed.\n(a)1-1/8" with 19 mm thick Insulation 30 Rmt
41 35 Supply Installation, testing & commissioning of Copper piping with19 mm/13 mm nitrile insulation from plant to AHU, including brassing, purging and leakge testing , installation of pipe line in neat manner on tray complete all as specified and directed.\n(b) 7/8" with 19 mm thick Insulation\n 30 Rmt
42 36 Supply Installation, testing & commissioning of Copper piping with19 mm/13 mm nitrile insulation from plant to AHU, including brassing, purging and leakge testing , installation of pipe line in neat manner on tray complete all as specified and directed.\n(c) 5/8" with 13 mm thick Insulation\n 30 Rmt
43 37 Supply Installation, testing & commissioning of Copper piping with19 mm/13 mm nitrile insulation from plant to AHU, including brassing, purging and leakge testing , installation of pipe line in neat manner on tray complete all as specified and directed.\n(d) 1/2" with 13 mm thick Insulation 30 Rmt
44 38 Supply Installation, testing & commissioning of site fabricated Duct of 24 gauge made out of GSS sheet complete angle Flange etc fabricated and erected as per IS 655/ Smacna standard with support rods, fasteners, gasket nut bolts , canvas including all mounting arrangement for installation of duct as per site requrement complete all as specified and directed 100 Sqm
45 39 Supply Installation, testing & commissioning of site fabricated Duct of 22 gauge made out of GSS sheet complete angle Flange etc fabricated and erected as per IS 655/ Smacna standard with support rods, fasteners, gasket nut bolts , canvas including all mounting arrangement for installation of duct as per site requrement complete all as specified and directed 160 Sqm
46 40 Supply Installation, testing & commissioning of site fabricated Duct 24 gauge made out of Aluminium duct complete angle Flange etc fabricated and erected as per IS 655/ Smacna standard with support rods, fasteners, gasket nut bolts , canvas including all mounting arrangement for installation of duct as per site requrement complete all as specified and directed 150 Sqm
47 41 Suppy and fixing Nitrile rubber (class - O) thickness 19mm (plain sheet) for Duct thermal insulation of supply air & Return air duct (inside the building)Thermal and accoutic insulation of Duct complete all as specified and directed 350 Sqm
48 42 Suppy and fixing 10 mm thick, class - O open cell, Nitrile rubber insulation for duct accoustic insulation complete all as specified and directed 30 Sqm
49 43 Supply, laying and fixing of insulation to exposed ducting with Thermocole covered by 300G Polythin sheet (vapour barrier) & finished with Sand cement plaster with AI net, with water proof & weather proof treatment. to provided weather proof cover to duct all as specified and directed by EIC. 250 Rm
50 44 Supply, laying and fixing of under deck insulation of OT & ICU ceiling with 19 mm thick (Class O Nitrile rubber (plain sheet) including providing wire mesh cover protection. all as specified and directed by EIC. 150 Sqm
51 45 Supply , fixing and installation of Aluminium Powder Coated Supply Air Diffusers with Damper of suitable size all as specified and directed by EIC . 2 Sqm
52 46 Supply, fixing & installation of Aluminium Powder Coated Return air Diffusers without Damper of suitable size all as specified and directed by EIC . 2 Sqm
53 47 Supply , fixing and installation of Collar damper for Supply air Grills of of suitable size all as specified and directed by EIC . 1 Sqm
54 48 Supply and installation of SA/RA liner discrete Grills all as specified and directed by EIC . 2 Sqm
55 49 Supply, fixing and installation of Aluminium volume control dampers all as specified and directed by EIC 2 Sqm
56 50 Supply, fixing and installation of Fresh Air damper all as specified and directed by EIC 1 Sqm
57 51 Supply, fixing and installation of Motorised fire damper all as specified and directed by EIC 3 Sqm
58 52 Supply, fixing and installaiton of Actuator for motorised Fire Damper all as specified and directed by EIC 6 Nos
59 53 Supply Installation and testing Aluminium Extruded bottom loading HEPA Box plenum with bottom operated arrangement , differential pressure measuring points along with Gel Seal Minipleate HEPA filter EU- 13 having Efficiency of 99.97% down to particle size of 0.3 Microns. SS-304, capsule perforation of 20 x 8mm ,16 SWG should be provided with the box. Hepa Filters are bottom loading type and can be replaced from room side. (Size 2400 mm x 1800 mm x 450 mm (L x B x H) including supply and installation of HEPA Filter of size suitable to fix in Plenum) all as specified and directed by EIC\nNote:- If size of Plenum required to be changed or increased as per design condition, contractor has to provide that size of Plenum along with HEPA Filters without any price adjustment. Dimensions like Length and width may vary as per site condition by total Sq mtr area of Plenum with HEPA Filters should not be less than 4.32 SQ Mtrs 2 Nos
60 54 Supply and errrection of Magnahelic Gauge complete all as specified and directed by EIC 2 Nos
61 55 Supply, installaion testing and commisioning of indoor electrical AHU control panel of 2.0 mm thick CRCA sheet, with copper bus bar of 200 Amp with incoming MCCB, Control circuit, all protection like single phase preventer, OLR, AHU ON / OFF status indicator etc.\nBy Pass starter with suitable size VFD for OT 1 to supply Power & control AHU & all Outdoor units. \nNote: (i) Contractor to take approval of drawing of control panel from GE before placing order.\n(ii) All cables from Main panel to control panel and control panel to AHU unit and Out door unit to be laid in neat in dressed form on cable tray. 1 Nos
62 56 Supply, installaion testing and commisioning of indoor electrical AHU control panel of 2.0 mm thick CRCA sheet, with copper bus bar of 200 Amp with incoming MCCB, Control circuit, all protection like single phase preventer, OLR, AHU ON / OFF status indicator etc.\nBy Pass starter with suitable size VFD for OT 2 to supply Power & control AHU & all Outdoor units. \nNote: (i) Contractor to take approval of drawing of control panel from GE before placing order.\n(ii) All cables from Main panel to control panel and control panel to AHU unit and Out door unit to be laid in neat in dressed form on cable tray. 1 Nos
63 57 Supply, installaion testing and commisioning of indoor electrical AHU control panel of 2.0 mm thick CRCA sheet, with copper bus bar of 200 Amp with incoming MCCB, Control circuit, all protection like single phase preventer, OLR, AHU ON / OFF status indicator etc.\nBy Pass starter with suitable size VFD for ICU to supply Power & control AHU & all Outdoor units. \nNote: (i) Contractor to take approval of drawing of control panel from GE before placing order.\n(ii) All cables from Main panel to control panel and control panel to AHU unit and Out door unit to be laid in neat in dressed form on cable tray. 1 Nos
64 58 Supply, laying and of suitable size armoured Cu cable for Starter Panel to AHU & Outdoor units with necessary cable tray for OT 1 all as specified and directed by EIC 1 Lot
65 59 Supply, laying and of suitable size armoured Cu cable for Starter Panel to AHU & Outdoor units with necessary cable tray for OT 2 all as specified and directed by EIC 1 Lot
66 60 Supply, laying and of suitable size armoured Cu cable for Starter Panel to AHU & Outdoor units with necessary cable tray for ICU all as specified and directed by EIC 1 Lot
67 61 Supply, installation, testing and commisssioning of RH sensor and heater controller for OT and ICU all as specified and directed by EIC 3 Nos
68 62 Supply and fixing PVC drain piping of 40 mm dia upto neraest drain trap all as specified and directed by EIC. 30 Rm
69 63 Supply and charging of Refrigeration Gas after pressure testing, nitrogen gas flushing, vaccumisiing etc all as specified and directed by EIC. 100 Kg
70 64 Supply, fixing, installation and testing of 3 KW Duct mounted Electrical Heater with required thermostatic control for OT (2 nos) and ICU including all control and power cables as required completeall as specified and directed by EIC. 3 Nos
71 65 Supply and fixing Control Cable for IDU to ODU communication 6C x 2.5 Sqmm as required complete all as specified and directed by EIC. 35 Rm
72 66 Supply and Installation of MS supports for out door unit, as required. complete all as specified and directed by EIC. 8 Nos
73 67 M & L for shifting of existing split type AC capacity 1.5/2 TR from Major OT 1 & 2 and ICU to new location in Hospital building including removing and refixing of mounting bracket gas pipe line etc complete as specified. and directed by EIC. 12 Each job
74 68 M & L for taking down existing ceiling fan of any size- 04 Nos and round curtain with clip and rod in ICU and refixing the same at existing or new place after completion of ducting work complete as specified. The cost item includes the extension of down rod of ceiling fan to fix it below false ceiling at suitable height. complete as specified. and directed by EIC. 1 Each job
75 69 M & L for taking down existing light fitting any type surface/ recess mounting from existing position and fixing the same at existing or at new place after completion of ducting work complete as specified. The cost item includes the extension of wires with casing capiing for providing supply to light fittings. complete as specified. and directed by EIC. 25 Each
76 70 M & L for taking down existing Shadowless light fitting safely from existing position for fixing plenum for providing laminare air flow in OT and fixing the same at existing or at new place after completion of AC work complete as specified. The cost item includes the extension of wires with casing capiing for providing supply to light fittings complete as specified. and directed by EIC. 2 Each job
77 71 M & L for taking down existing pendent assly safely from existing position for fixing plenum for providing laminare air flow in OT and false celing and fixing the same at existing or at new place after completion of AC work including extension / incresing the down height of pandent for its free movement of arm by providing extra long GI studs of existing dia/ size of heavy duty, extension of medical gas flexible pipe and probes, power supply cable as per existing complete all as specified and directed by EIC. Note: Work to be done by specilized agency doing the work of modular OT and medical gas system. complete as specified. and directed by EIC. 2 Each job
78 72 S&F 4mm thick ACP panels fixed to walls including aluminium frame work complete all as specified and directed. 35.5 Sqm
79 73 Removing of tree roots for preventing the regrowthing and making good the disturbed earth complete all as specified & directed by Engr- in -Charge. 1 Each
80 74 GENERAL POINTS FOR ALL AHU ( BOQ ITEM NOS 30,31,32)\n(i) The velocity across the AHU is 500 FPM\n(ii) In AHU one Fresh air opening with adjustable grill is to be provided at no extra cost to the Department.\n(iii) All necessary cabling work for providing electric supply from control panel to VFD, AHU and DX unit with suitable size of cable to be provided by the contractor at no extra cost to the department.\n(iv) Cooling coil with copper tubes diameter should be as per OEM design, 12 aluminum fins per inch.\n(v) Humidification section as per stranded practice\n(vi) Suitable canvas connection shall be provided at the outlet of blower.\n(vii) Electrically controlled / operated control such as humidistat and thermostat along with all equipment and accessories.\n(viii)Contractor shall submit ADP of coil, total dehumidified quantity of air and duct design within 30 days of acceptance of tender.\n(ix) All necessary civil work and including making holes wherever required for installation of the above said equipment’s, laying and passing of cables, ducts shall be done by the contractor without any extra cost to the department.
81 74.1 ITEM 74 CONTD\n(x) Foundation bolts, fashner and any other hardware required for installation of above equipment’s to be provided by the contractor without any extra cost.\n(xi) All refrigerant piping and cable arrangement from Dx unit to AHU shall be done in proper dressed way, in alignment and piping to be laid on tray to be provided by the contractor without any extra cost.\n(xii) Pressure gauges, thermometers, flow switches, HP/LP cut outs, humidistat’s, electronic thermostatic expansion valve, solenoid valve, humidity transmitter and any other controls, safety devices and advanced / latest technology considered necessary for achieving the specified inside conditions shall be inclusive of the rate quoted in the above respective items.\n
82 75 GENERAL POINTS\n(i) Installation and commissioning of DX unit and AHU shall be carried out in presence of OEM rep.\n(ii) Contractor has to be submitted original paid voucher and test certificate of DX unit AC plant, AHU, \n LT panel, cable, stabilizer, Duct sheet to the department.\n(iii) Digital thermometer and Humidistat are to be provided in 3 Rooms as directed by Engr-in-Charge – 3 Sets (Each set consists of digital thermometer and digital humidistat)\n(iv) Normal Twin sets of Dry/Wet Bulb thermometers in other rooms – 21 sets\n(v) One sling psychrometer and Anemo meter shall also be provided at no extra cost to the department. \n(vi) All drawings for lay out of equipment, foundation details, wiring layout for equipment, controls, Duct design shall be got approved by CE’s office before taking up for execution. \n(vii) Schematic diagram of plant details on a luminous Fluorescent sheet and first aid box as directed by Engr-in-Charge shall be provided in each Plant room at no extra cost to the department.\n
83 75.1 ITEM 75 CONTD\n(viii) Provision of fire stand of suitable size made out of MS angle iron / channel and painted with 2 coats of synthetic enamel paint over a coat of red oxide primer and lettering with white paint including and providing following:-\n(a) Galvanized MS fire bucket 14 liters capacity –\n 2 Nos\n(b) Portable fire extinguisher CO2 type 3 kg capacity – 2 Nos \n\n(viii) Operation manuals (03 copies) shall be given. \n\n(ix) Even though the item of AC Plant, AHU, Duct work, control cable, electrical cable, LT panel, Control panel, microprocessor controller, VFD have been catered in BOQ, however any other item left out and required to achieve air conditioning parameter as specified in PS and for functioning of equipment to be provided by contractor without any extra cost to department.\n\n
84 75.2 ITEM 75 CONTD\n(x) Phase – I test for 24 hrs will be carried out after completion and after successful completion of test, Provisional completion certificate will be given. Phase – II test for 72 hours will be carried out in summer, monsoon and winter. After successful completion of these tests, Final completion certificate will be issued.\n \n(xi) Contractor shall be provided his staff for manning and maintenance of all three plants till completion of Phase – II test without any extra cost.\n(xii) All ducts, piping work, fitting etc shall be of specified type, quality design and workmanship and are neatly laid, fixed and painted to match the surrounding work. \n(xiii) Design of duct dimensions / sizes of supply air and return air duct for OTs and ICU as per CFM of AHU to be submitted by the contractor duly vetted by the specialized agency within 30 days of acceptance of tender without any extra cost.\n\n(xiv) Though brick work platform for mounting AHU and DX plant is shown in lump sum as a part of AC Plant bldg, However if any additional requirement arises on site for completion of Job, contractor shall provide platform for AC equipment and weather protection over Dx out door unit without extra cost to department. \n