Certain Misc Repairs Maint Of Dg Set And Pumping Installation At Various Location At Outram Line Under Ge ( Army ) Baroda As Per Boq, GE Army Baroda-Gujarat

Military Engineer Services-MES has published Certain Misc Repairs Maint Of Dg Set And Pumping Installation At Various Location At Outram Line Under Ge ( Army ) Baroda As Per Boq. Submission Date for this Tender is 28-05-2020. Diesel Generators Tenders in GE Army Baroda Gujarat. Bidders can get complete Tender details and download the document.




Tender Notice

24114342
Corrigendum : Certain Misc Repairs Maint Of Dg Set And Pumping Installation At Various Location At Outram Line Under Ge ( Army ) Baroda As Per Boq
Open Tender
Indian
Gujarat
GE Army Baroda
28-05-2020

Tender Details

Certain Misc Repairs Maint Of Dg Set And Pumping Installation At Various Location At Outram Line Under Ge ( Army ) Baroda As Per Boq

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 03-Apr-2020 CHANGE IN DATES Date 24-04-2020
2 24-Apr-2020 CRITICAL DATE CHANGE Date 08-05-2020
3 07-May-2020 CHANGE IN CRITICAL DATE Date 21-05-2020
4 21-May-2020 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 28-05-2020

Key Value

Document Fees
INR 500 /-
EMD
INR 24000.0 /-
Tender Value
INR 12 Lakhs /-

BOQ Items

Name of Work: CERTAIN MISC REPAIRS/ MAINT OF DG SET AND PUMPING INSTALLATION AT VARIOUS LOCATION AT OUTRAM LINE UNDER GE (ARMY) BARODA
Sl. No. Item Description Item Code / Make Quantity Units
1 1 General servicing of existing make of capacity of 30/35/63/100 KVA DG set including tappet cover adjustment & gasket replacement including replacement of following spares complete all as specified and directed by EIC. All spares shall be of existing make . 4 Each Job
2 1.01 Diesel fitter 4 Each
3 1.02 Lub oil filter 4 Each
4 1.03 Carbon bush 4 Each
5 1.04 Coupling 4 Each
6 1.05 Fan belt 4 Each
7 1.06 Radiator hose pipe set. 4 Each
8 2 M & L for dismantling the FIP assembly for overhauling and caliberation in authorised workshop including replacement of worn out rings, plungers , damper plates , gasket etc .including refitting , refixing , & testing complete .
9 2.01 Ditto but for 63 KVA 2 Each
10 3 M & L for replacement of old engine oil from the DG Set sump of various DG Set cleaning the oil sump throughly supply & filling new engine oil of Make : Servo super 20W 40 of Indian Oil or Equilent grade of Hindustan Petrolium all as per directed by EIC. 50 Ltr
11 4 Repair overhalling of self starter 12 Volt including replacement of worn out clutch assembly bush, spring, plunger assembly ,solenide switch, corbon brushs, spring etc for the following DG set.
12 4.01 Ditto but for 63 KVA 2 Each
13 5 M & L for topping up of water coolent in radiotor of DG set TVS Girling/volvo line or of equivelent make all as directed by EIC. 30 Ltr
14 6 Cleaning of the fuel tank of DG sets of following capacity after decaning the diesel, after through cleaning with kerosene oil including replacement of level indicator pipe complete all as directed by EIC.
15 6.01 Ditto but for 30/63/100 KVA 1 Each job
16 7 Dismantling and removing of water pump assesmbly complete from the engine repair/overhauling the same by replacing worn components like bearing,impeller,bushes,oil seal,water seal,gasket etc. reassembling,refixing and testing complete for the following :-
17 7.01 Ditto but for 63 KVA 1 Each
18 7.02 Ditto but for 100 KVA 1 Each
19 8 M & L for replacement of oil pressure metallic pipe suitable for Genset of capacity 20 KVA to 100 KVA complete all as specified & directed . 6 Each
20 9 Supply and Laying only including jointing and testing only electric under ground LT cable PVC/XLPE insulated armoured aluminium conductor cable 1100 volts grade in trenches ducts, pipe on walls, poles including taking out existing UNSV LT under ground cable of following sizes :-
21 9.01 50 Sqmm 3.5 core 60 RM
22 10 S & F wall security light 25 W ,LED type complete with GI bend 1.2 mtr and fixing on wall/pole with clamp, nut & bolt complete all as directed and specified by Engr-In-Charge. ENDURACITYLITEPLATSL25WLED757SASYBOPC of Make Havells or its equivalent in Phillips/Wipro/CG. 8 Each
23 11 S & F wall security light 35 W, LED type complete with GI bend 1.2 mtr and fixing on wall/pole with clamp, nut & bolt complete all as directed and specified by Engr-In-Charge.. Similar to cat part No. ENDURACITYLITEPLATPLUSSL35WLED757SASYBOPC, Make- Havells or Equivalent From Phillips/Wipro/CG 6 EACH
24 12 Supply, installing, testing and commissioning factory made and tested LT panel indoor type,cubical ,floor mounted CPRI Aprroved suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system all as specified and directed having bus bar installed on DMC/Epoxy insulators,with busbar chamber. The panel shall be dust and vermin proof, IP 54 made of 2.00 mm CRCA MS sheet with front and rear opening type with shutters and locking arrangement , powder coated finish (over a coat of red oxide), primer on outside and two coats of red oxide primer on inside surface supported on and including ISMC 75x40 mm fixed upto 70 cm above ground level with suitable foundation as directed by Engr in Charge. The TPN copper bus bar Epoxy insulated of rating not less than the 1.5 times the rated capacity of the incomer MCCB with following accessaries For Pump house no 6 Note: The cost of foundation ,necessary excavation, earth work and PCC deemed to be included in the unit rate quoted againt this item. \n(i) I/C -MCCB 4 pole 35 kA 160 Amp with thermal magnetic release and thermal settiing 80-100% - 01 No \n(ii) O/G - MCCB 4 pole 16 kA 63 Amp - 03 No (iii) Phase indiacting lamps (R-Y-B) - 01 set (iv) Internal wiring with PVC insulated, multi stranded copper conductor cable, 1100 V grade, IS 694 marked of appropriate size but not less than 1.5 sqmm. (v) Ammeter digital, 96x96mm, with suitable ratio CTs with built in selector switch 0-200 Amp -1 No. \n(vi) Volt meter of range 0-500 Volts, 96x96mm with built in selector switch -1 No (vii) Spare compartment for future expansion - 01 Nos,\n(VIII)Supply and fix fully automatic star delta starter fitted inside panel withVolt meter, ameter and frequency meter digital type complete of 40 to 70 amp for 40 HP Induction Motor capacity with all as directed by engineer-in-charge(a) motor protection circuit.(b)moisture protection circuit (c)automtice liquid leval controller with probes of high and low levels to avoid dry running of pump Make L&T,ABB,Siemens -03 Nos \n \n 1 EACH
25 13 Supply, installing, testing and commissioning factory made and tested LT panel indoor type,cubical ,floor mounted CPRI Aprroved suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system all as specified and directed having bus bar installed on DMC/Epoxy insulators,with busbar chamber. The panel shall be dust and vermin proof, IP 54 made of 2.00 mm CRCA MS sheet with front and rear opening type with shutters and locking arrangement , powder coated finish (over a coat of red oxide), primer on outside and two coats of red oxide primer on inside surface supported on and including ISMC 75x40 mm fixed upto 70 cm above ground level with suitable foundation as directed by Engr in Charge. The TPN copper bus bar Epoxy insulated of rating not less than the 1.5 times the rated capacity of the incomer MCCB with the following accessoriesFor Varun Vihar pump house Note: The cost of foundation ,necessary excavation, earth work and PCC deemed to be included in the unit rate quoted againt this item. \n(i) I/C -MCCB 4 pole 35 kA 160 Amp with thermal magnetic release and thermal settiing 80-100% - 01 No (ii) O/G - MCCB 4 pole 16 kA 63 Amp - 02 No (iii) Phase indiacting lamps (R-Y-B) - 01 set (iv) Internal wiring with PVC insulated, multi stranded copper conductor cable, 1100 V grade, IS 694 marked of appropriate size but not less than 1.5 sqmm. (v) Ammeter digital, 96x96mm, with suitable ratio CTs with built in selector switch 0-200 Amp -1 No. (vi) Volt meter of range 0-500 Volts, 96x96mm with built in selector switch -1 No (vii) Spare compartment for future expansion - 01 Nos, \n(VIII)Supply and fix fully automatic star delta starter fitted inside panel with Volt meter, ameter and frequency meter digital type complete of 40 to 70 amp for 40 HP Induction Motor capacity with all as directed by engineer-in-charge(a) motor protection circuit.(b)moisture protection circuit (c)automtice liquid leval controller with probes of high and low levels to avoid dry running of pump Make L&T,ABB,Siemens-02 Nos . \n \n 1 Each Job
26 14 M & L for replacement of on load change over switch 4 Pole, 415 Volt, 63 Amps complete with sheet steel enclosure Make-L&T/HPL/Schneider complete all as specified & directed . 2 EACH
27 15 M & L for replacement of on load change over switch 4 Pole, 415 Volt, 100 Amps complete with sheet steel enclosure Make-L&T/HPL/Schneider complete all as specified & directed . 2 EACH
28 16 M & L for replacement of on load change over switch 4 Pole, 415 Volt, 200 Amps complete with sheet steel enclosure Make-L&T/HPL/Schneider complete all as specified & directed . 1 EACH
29 17 S&F fabricated glow sign board with frame of angle iron of size 50x50x5mm and 25x25x3mm,PGI sheet 20 SWG and flex sheet blue colour of size 3 1/2’X 12 1/2’ x 8” including depicting the letter with white colour fluorescent tape on flex sheet one side of the board as directed, including LED tube light fitting - 02 Nos 1 x18 watt with LED tube rod 18 watts fixed inside the glow sign board using suitable size 3 core flexible cable 23/.00076 from ceiling rose to tube fitting connection all as directed. Make of LED fitting- Crompton Greaves/Bajaj/Havells 5 EACH
30 18 S & F Post top lantern light LED type 25W complete with GI pipe 1.0 mtr fixing/grouted on Gate piller complete all as directed and specified by Engr-In-Charge. CAT Part No.RUBYPT25WLED757PSYMTOPC of Make- Havells or its equivalent in Phillips/Wipro/CG 6 EACH
31 19 S&F sluice valve cast iron both ends flanged class PN – 1.6 conforming to IS-14846 with SS Spindle & wheel including jointing materials Rubber gasket, Nut Bolt and Washer etc. complete all as directed Make: Kartar/Zoloto/ Upadaya/Kirloskar
32 19.01 150 mm bore 2 EACH
33 19.02 100 mm bore 2 EACH
34 19.03 80 mm bore 3 EACH
35 20 S & F in repair Gun metal gate valve iron wheel head screwed both ends for GI steel tubing suitable for following bore of pipe
36 20.01 50 mm bore 2 EACH
37 20.02 40 mm bore 2 EACH
38 20.03 25 mm bore 5 EACH
39 20.04 20 mm bore 5 EACH
40 21 Supply TCCA 90 (Trichloroisocyanuric Acid) in containers. 100 Kg
41 22 Supply Alumn sulphate 50 Kg
42 23 Supply copper sulphate 50 KG
43 24 Supply Bleaching powder 100 KG
44 25 Supply and laying 3 core multi round PVC insulated and FR PVC Round Sheathed, Copper Conductor (flexible) industrial cable, 1100 Volts, conforming to IS: 694 16 Sqmm 200 RM
45 26 Supply & fixing air termination, single pointed aluminium rod, 12 mm dia, 300 mm long complete all as specified and directed. 10 Each
46 27 S & F Aluminium strip 25 mm x 3 mm fixed on epoxy insulator/saddles and fixing screws etc. for roof conductors and down conductors above ground complete all as specified and directed. 10 RM
47 28 S&F Test point terminal block made of gun metal or phosphorus bronze 75x75x25 mm, drilled and screwed including 3 Nos, 8mm dia 25mm long hexagonal head brass screws including necessary MS box with locking arrangements complete all as specified and directed 10 Each
48 29 Supply, fixing, testing & commissioning of exhaust fan 300 mm sweep 1400 RPM with minimum airflow/air delivery 1710 Cmh, totally enclosed heavy duty motor, die cast aluminium rotor mounted on double ball bearing, IP-55, polarity-4, 230 Volt AC supply (single phase), rated power input not more that 90watt, with louvers and connecting up including provison of PVC insulated overall PVC sheathed copper conductor cable from ceiling rose to fan. Make : CG/Bajaj/Havells or equivalent. Similar to Crompton Greaves model No EXHD300-4-1\nNote: Old UNSV ceiling fans will be deposited to AGE E/M office 4 Each
49 30 Supply only calcium based high strength chlorination chemical for water disinfection in granular form in factory sealed HDPE container (45/50 Kg Each) having chlorine concentration level 70%. Make _- Declibac (Brand Name- Altoch GP) or equivalent make as approved by E-in-C complete all as directed . 100 Kg
50 31 M&L for cover (brick masonry valve pit chamber) made of MS angle iron frame work (Angle Iron size 50mm x 50mm x 6mm) & 3.20 mm MS sheet top cover openable through hinges including neccesory locking arrangement rendering complete and painting with two coat of black bituminous paint over a one coat red oxide primer. 30 Sqm
51 32 S/F Fire extinguisherABC powder based MAP 50 ISI marked ,9 Kg capacity , make BURHAN SAFETY /EXTINTEC/LIFE GUARD/NIMIT 4 Each
52 33 S/F Fire extinguisher CO2 type AFFF Foam ISI marked ,9 Kg capacity , make BURHAN SAFETY /EXTINTEC/LIFE GUARD/NIMIT 4 Each
53 34 S/F Fire bucket 15 Ltrs capacity iron body ISI marked, make BURHAN SAFETY /EXTINTEC/LIFE GUARD/NIMIT 4 Each
54 35 S/F Fire Axe with suitable handle ISI marked , make BURHAN SAFETY /EXTINTEC/LIFE GUARD 2 Each
55 36 S/F Fire bucket stand suitable to accommodate four bucket iron made ISI marked, make BURHAN SAFETY /EXTINTEC/LIFE GUARD 2 Each
56 37 Fire extinguisher ball ABC Type 1 kg capacity make NIMIT,LIFE GUARD 4 Each
57 38 S/F Fire beater with suitable MS handle ISI marked, make BURHAN SAFETY /EXTINTEC/LIFE GUARD/NIMIT 2 Each
58 39 M&L for KAPITRODE Earthing complete with Cast Iron pipe electrode, 75mm bore, 3.50mm wall thickness , 2.9 metres length,with GI Clamp & funnel, buried directly and preferably vertically in ground with top edge not less than 2.9 metres below ground level connected with earthing lead of 25x5mm dia galvanised iron strip all as specified including testing on completion including the material and labour of the following, Make -Kapilansh Dhatu Udyog (P) Ltd : -\n(a) Excavation and earth work for drilling hole for electrode in any type of Soil.\n(b) PCC pit in cement concrete 1:2:4 type B-1 of size 450x450x450mm with Cast iron cover with suitable handle .\n(c) 40 mm nominal bore medium grade GI protection pipe 5 meter long for protection of earthing lead complete all as specified and directed.\n(d) Requisite quantity of BFC Compound (bentonide powder) and black cotton soil.\n(e) Testing of earthing. \nNOTE :- On testing after completion of earthing, if the desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engineer-in-charge.\n 6 Each
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy