Replacement Of Different Old & Obsolete 220 Kv & 132 Kv Feeder/Trnasformer Control Panel By New Panels At 220 Kv S/S Sarojininagar, Lucknow, 220 KV S/S SAROJININAGAR-Uttar Pradesh

Uttar Pradesh Power Transmission Corporation Limited-UPPTCL has published Replacement Of Different Old & Obsolete 220 Kv & 132 Kv Feeder/Trnasformer Control Panel By New Panels At 220 Kv S/S Sarojininagar, Lucknow. Submission Date for this Tender is 14-04-2020. Feeder Pillar Tenders in 220 KV S/S SAROJININAGAR Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

24071703
Replacement Of Different Old & Obsolete 220 Kv & 132 Kv Feeder/Trnasformer Control Panel By New Panels At 220 Kv S/S Sarojininagar, Lucknow
Open Tender
Indian
Uttar Pradesh
220 KV S/S SAROJININAGAR
14-04-2020

Tender Details

Replacement Of Different Old & Obsolete 220 Kv & 132 Kv Feeder / Trnasformer Control Panel By New Panels At 220 Kv S / S Sarojininagar, Lucknow

Key Value

Document Fees
INR 590 /-
EMD
INR 5000.0 /-
Tender Value
INR 4.56 Lakhs /-

BOQ Items

Name of Work : REPLACEMENT OF DIFFERENT OLD & OBSOLETE 220 KV & 132 KV FEEDER/TRNASFORMER CONTROL PANEL BY NEW PANELS AT 220 KV S/S SAROJININAGAR, LUCKNOW.
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Following works are to be done at 220 KV Sub-Station Sarojininagar, Lucknow for replacement of different old & obsolete 220 & 132 KV Feeder/Transformer Control Panel by New Panels with al cost of man, T&P and miscellaneous consumable items as per direction of supervising engineer/incharge as per detail given below :-
2 1.1 Dismantling of following old control panels installed in control room by opening of cable connections, earthing flats, nuts bolts etc. including safe disconnection of Bus Bar protection scheme, synchronizing scheme & TBC scheme and cable loop panel to panel cables connection etc. & making of new loop connection (temporary) for other healthyness of running control panels as required. The work also includes identification of the control cables by providing suitable ferrules etc. for later use and safe shifting of the panels from control room to designated place/site store at S/S.
3 1.2 220 KV Control Panels (One Job per Feeder/Transformer) :-\n220 KV Sarojininagar-Bacchrawan Feeder\n220 KV Sarojininagar-Gomti Nagar Feeder\n220 KV Sarojininagar-Kanpur Road Feeder\n 3 Job
4 1.3 220/132 KV 200 MVA T/F-II, both HV & LV side. 1 Job
5 1.4 132 KV Control Panels (One Job per Feeder) :-\n132 KV Sarojininagar-SGPGI-I Feeder\n132 KV Sarojininagar-Railway Feeder\n132 KV Sarojininagar-Rahimabad Feeder\n132 KV Sarojininagar-Kundan Road Feeder\n132 KV Sarojininagar-TRT-1 Feeder\n132 KV Sarojininagar-TRT-2 Feeder\n132 KV Bus Coupler Bay\n 7 Job
6 2 Installation of following New Control Panels in Control Room after shifting from storage place to first floor of control room, its grouting & earthing and termination of control cables in control and relay panels as per cable schedule including providing and fixing of cable glands of appropriate sizes and ferrules etc. with all other associated works as per technical specification including dafe reconnection of Bus Bar protection scheme, Syncronizing scheme & TBC scheme and panel to panel cables connection etc. The work also includes control cables connection as required between control panel to looping. The commissioning of the control panel shall be done jointly with T&C wing including trouble shooting as needed/necessary, Also inter-connection diagram as per new control panel shall be submitted and got approved by the concerned supervising engineer/incharge before start of work. After completion of work schedule shall be provided as executed mentioning TB No. & ferrules for each control panel on A4 size 100gsm with clear print :-
7 2.1 220 KV Control Panels (One Job per Feeder/Transformer) :-\n220 KV Sarojininagar-Bacchrawan Feeder\n220 KV Sarojininagar-Gomti Nagar Feeder\n220 KV Sarojininagar-Kanpur Road Feeder\n 3 Job
8 2.2 220/132 KV 200 MVA T/F-II, both HV & LV side. (one job for both sides) 1 Job
9 2.3 132 KV Control Panels (One Job per Feeder) :-\n132 KV Sarojininagar-SGPGI-I Feeder\n132 KV Sarojininagar-Railway Feeder\n132 KV Sarojininagar-Rahimabad Feeder\n132 KV Sarojininagar-Kundan Road Feeder\n132 KV Sarojininagar-TRT-1 Feeder\n132 KV Sarojininagar-TRT-2 Feeder\n132 KV Bus Coupler Bay\n 7 Job
10 3 Laying of following size PVC copper control cable between different control panel/relay panel to different equipment/marshalling box/junction box in switchyard, control panel to relay panel/bus bar protection panel as per drawing with proper tagging, ferruling and dressing, binding with clamp/cable tie on cable rack in tunnel and trench. The cable shall be passing through cable hall cable rack & tunnels rack and trench. The work also includes opening of trench covers and re-fixing them from trench after completion of work satisfactorily. Note :- Control cable shall be laid as per actual requirement at site and may vary +/- 20%
11 3.1 4 Core X 2.5Sq.mm 7500 RMT
12 3.2 7 Core X 2.5Sq.mm 3000 RMT
13 3.3 10 Core X 2.5Sq.mm 2900 RMT
14 4 Dismantling & removing of following size old and unused/damaged/ defective/burnet PVC control cable from different cable rack in tunnel and trench. These cables are passing through cable hall cable rack & tunnels rack and trench etc. included opening of its binding, collecting, making rolls & opening of trench cover and re-covering from trench cover after completion of work satisfactorily :-
15 4.1 Old & Used 4 Core X 2.5Sq.mm 7000 RMT
16 4.2 Old & Used 7 Core X 2.5Sq.mm 1500 RMT
17 4.3 Old & Used 10 Core X 2.5Sq.mm 1500 RMT