Military Engineer Services-MES has published Repair Maintenance And Replacement Of Unsv Various Items Of Lt Capacitor Bank Panels Including Repair Of Dg Set At Afs Chakeri Kanpur. Submission Date for this Tender is 18-04-2020. Diesel Generators Tenders in GE (AF) E/M CHAKERI KANPUR Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

24060448
Corrigendum : Repair Maintenance And Replacement Of Unsv Various Items Of Lt Capacitor Bank Panels Including Repair Of Dg Set At Afs Chakeri Kanpur
Open Tender
Indian
Uttar Pradesh
GE (AF) E/M CHAKERI KANPUR
18-04-2020

Tender Details

Repair Maintenance And Replacement Of Unsv Various Items Of Lt Capacitor Bank Panels Including Repair Of Dg Set At Afs Chakeri Kanpur

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 25-Mar-2020 CORRIGENDUM NO 01 Date 16-04-2020
2 15-Apr-2020 CORRIGENDUM NO 02 Date 18-04-2020

Key Value

Document Fees
INR 500 /-
EMD
INR 56000.0 /-
Tender Value
INR 28 Lakhs /-

BOQ Items

Name of Work: REPAIR / MAINT AND REPLACEMENT OF UNSV VARIOUS ITEMS OF LT CAPACITOR BANK PANELS INCLUDING REPAIR OF DG SET AT AFS CHAKERI, KANPUR
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Disconnecting of LT supply from APFC panel any type and size. Maintenance & servicing of complete capacitor bank panel of capacity upto 825KVAR including cleaning of all contacts, decarbonising of contactor contacts with petrol/CRC, checking & tightening of all cable/Bus bar connection, CT connections & replacement of worn out parts such as capacitors, capacitor lugs, MOC, CT's, indicators, Rotary switchs, APFC relays, fuses & measuring meters etc including setting of power factor 0.98 to 0.99 and testing after repair complete all as specified and directed.\nNote- Parts replace of APFC panel shall be measured and paid under respective item. Extra capacitors of suitable size required for maintaining PF fixed in existing panel complete with wiring & accessories and Minor spares are deemed to be included in the quoted rate. 26 Each job
2 2 M & L in repair of MPP heavy duty capacitor bank cylindrical type , 3 phase 440 volts of capacity 1 KVAR including necessary copper lead copper lugs of suitable size complete all as specified and directed.\nMake : L&T/Schnieder/ BCH/EPCOS as approved by GE 15 Each
3 3 All as item No 2 above but capacity 3 KVAR 15 Each
4 4 All as item No 2 above but capacity 5 KVAR 25 Each
5 5 All as item No 2 above but capacity 7.5 KVAR 3 Each
6 6 All as item No 2 above but capacity 10 KVAR 17 Each
7 7 All as item No 2 above but capacity 12.5 KVAR 2 Each
8 8 All as item No 2 above but capacity 15 KVAR 25 Each
9 9 All as item No 2 above but capacity 20 KVAR 25 Each
10 10 All as item No 2 above but capacity 25 KVAR 30 Each
11 11 All as item No 2 above but capacity 50 KVAR 15 Each
12 12 All as item No 2 above but capacity 100 KVAR 4 Each
13 13 All as item No 2 above but capacity 200 KVAR 2 Each
14 14 Supply & fix in repair of 3 pole Capacitor duty Contactor type MOC suitable for 1 to 5 KVAR capacitor comprising of built-in-auxiliary contacts , 50 Hz AC rating 415 volts in replacement in existing LT panel complete all as specified and directed.. \nMake : L&T / Siemens/ Schnieder as approved by GE 25 Each
15 15 All as item No 14 above but type MOC suitable for 7.5 to 12.5 KVAR capacitor.\n\n 25 Each
16 16 All as item No 14 above but type MOC suitable for 15 to 25 KVAR capacitor.\n\n 30 Each
17 17 All as item No 14 above but type MOC suitable for 50KVAR capacitor.\n\n 10 Each
18 18 All as item No 14 above but type MOC suitable for 100KVAR capacitor.\n\n 5 Each
19 19 All as item No 14 above but type MOC suitable for 200KVAR capacitor.\n\n 2 Each
20 20 Supply & fix in repair of power factor controller relay 7 steps suitable for operation at 415 V power and Auxiliary both ans 5 amp as current measurement. The relay shall be improve the PF at least 0.98. The relay shall be microprocessor based with self diagnostic and setting complete all as specified and directed. \nMake : L& T /Schnieder as approved by GE 5 Each
21 21 All as item No 20 above but relay 8 steps\n\n 8 Each
22 22 All as item No 20 above but relay 12 steps\n\n 10 Each
23 23 All as item No 20 above but relay 16 steps\n\n 1 Each
24 24 Supply and fix in repair of MCCB 250 Amps breaking capacity 36 KA, 3 pole load adjustable type in existing panel including necessary incoming/ outgoing including addition & alteration as required at site connections and testing complete all as specified and directed.\nMake -Legrand/L&T/Siemens or as approved by GE 6 Each
25 25 All as item No 24 above but MCCB capacity 200 amp, 25KA.\n\n 4 Each
26 26 All as item No 24 above but MCCB capacity 160 amp, 25KA.\n\n 5 Each
27 27 All as item No 24 above but MCCB capacity 100 amp, 25KA.\n\n 5 Each
28 28 All as item No 24 above but MCCB capacity 63 amp, 25KA.\n\n 8 Each
29 29 Supply and fix in repair switch disconnector fuse with HRC fuse 100 Amps 4 pole 415 V ,panel mouting type without enclosure,including labour for alterration in panel etc complete all as specified and directed.\nMake : L&T / Schnieder /C&S 8 Each
30 30 Supply and fix in repair switch disconnector fuse with HRC fuse 250 Amps 4 pole 415 V,panel mouting type without enclosure,including labour for alterration in panel etc complete all as specified and directed. \nMake : L&T / Schnieder /C&S 4 Each
31 31 Supply and fix in repair switch disconnector fuse with HRC fuse 400 Amps 4 pole 415 V, panel mouting type without enclosure,including labour for alterration in panel etc complete all as specified and directed. \nMake :L&T / Schnieder /C&S 4 Each
32 32 Supply and fix in repair digital ammeter flush type 96X96 Sqmm,3 Phase, 5A, Class1 in existing LT panel with suitable fixing arrangement and repair to wiring as required complete all as specified and directed.\nMake : L&T/ HPL/ Conserve as approved by GE 12 Each
33 33 Supply and fix in repair digital volt meter flush type 96X96 Sqmm, 0-500 volts,3 Phase,Class I in existing LT panel with suitable fixing and repair to wiring as required at site complete all as specified and directed.\nMake : L&T/ HPL/ Conserve as approved by GE 10 Each Job
34 34 Supply and fix of indicator lamp LED type (R,Y,B in colour) suitable 110/220 volts AC or 30 volt DC for in existing LT panel with suitable wiring as required at site complete all as specified and directed.\nMake : L&T/SCS/SB as approved by GE 15 Set of Three
35 35 Supply and fix of indicator lamp LED type (Red colour) suitable 110/220 volts AC or 30 volt DC for in existing LT panel with suitable wiring as required at site complete all as specified and directed.\nMake : L&T/SCS/SB as approved by GE 30 Each
36 36 Supply and fix in repair LT RG tape wounded current transformer in existing panel in replacement 300/5, 10 VA with suitable wiring complete all as specified and directed.\nMake : AE/ KAPPA 15 Each
37 37 Supply and fix in repair LT RG tape wounded current transformer in existing panel in replacement 500/5, 15 VA with suitable wiring complete all as specified and directed.\nMake : AE /Kappa 10 Each
38 38 Material & Labour in repair of selector switch 3 way and off type suitable for ammeter / voltmeter including repair to wiring complete all as specified and directed. \nMake : L&T/HPL/ Conserve as approved by GE 12 Each
39 39 Material & Labour in repair of copper wire for control circuit in capacitor bank of size 2 x 2.5 sqmm 1100 volts grade complete all as specified and directed.\n 90 RM
40 40 Material & Labour in repair of copper wire for control circuit in capacitor bank of size 2 x 4 sqmm 1100 volts grade complete all as specified and directed.\n 90 RM
41 41 Supply & fix of MCB single pole 6 to 10 amps of 10 KA in existing panel with incoming and outgoing connection complete all as specified and directed.\nMake : Legrand/L&T/Siemens as approved by GE 15 Each
42 42 Supply & fix of MCB TP 63 amps of 10 KA in existing panel with incoming and outgoing connection c complete all as specified and directed.\nMake : Legrand/L&T/Siemens as approved by GE 12 Each
43 43 Supply & fix of MCB TP 32 amps of 10 KA in existing panel with incoming and outgoing connection complete all as specified and directed.\nMake : Legrand/L&T/Siemens as approved by GE 14 Each
44 44 Supply and fix in repair digital multifunctional meter flush type 3 Phase,Class I in existing LT panel with suitable fixing and repair to wiring as required at site complete all as specified and directed.\nMake : L&T/ HPL/ Conserve as approved by GE 8 Each
45 45 Supply and fix in repair digital PF meter flush type 96X96 Sqmm, fixed in existing LT panel with suitable wiring and repair as required at site complete all as specified and directed.\nMake : L&T/ HPL/ Conserve as approved by GE 15 Each
46 46 M&L for repair, welding of LT feeder pillar box/APFC panel front/ rear door and locking arrengement with lock & key including minor parts such as hingeg, screw, nuts & bolts, gaskets etc including paint patch work making good as per existing colour and complete all as specified and directed. 15 Each Job
47 47 Supply & fix of front and rear door of LT feeder pillar box according to existing feeder pillar box size. Door made of 3.15 mm thick MS sheet with two coat of existing feeder pillar box colour paint over one coat of red oxide primer complete all as specified and directed. 10 Each
48 48 M & L for Scrapping, cleaning, and preparation of old painted surface of LT feeder pillar box/ APFC panel out door/indoor type of surface and painting with one coat of synthetic enamel paint of approved colour by spray gun complete all as specified and directed. 10 Each Job
49 49 Supply & fix LT feeder pillar box door handles of suitable size complete all as specified and directed. 40 Each
50 50 Surface dressing/levelling/ cleaning of surrounding area of 2/4 pole/ plinth mounted transformer structure/ E&M sub station including removing of tree branches small tree plants tarbushes etc complete all as specified and directed. 4000 Sqm
51 51 Supply, installing, testing and commissioning, factory made and tested, automatic power factor control panel (APFC Panel), outdoor type , floor mounted, cubical front/rear opening type. The panel shall be of protection class IP-54 and made of 3.15 CRCA MS sheet and MS angle 40x40x6mm thick, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, including internal wiring with PVC insulated solid copper conductor cables, IS – 694 marked, 1100 volts grade of appropriate size but not less than 2.5 sqmm including Godrej pattern 65mm pad lock with two keys complete all as specified and directed and comprising of the following :- \n(a) Incoming MCCB, LT, 4 pole, 400 Amp rating, 36 KA rupturing capacity : 01 Nos .\n(b) Capacitors type as per IS 13585/ hot I / 1994 / IS 13340/ 1993, for 300 KVAR. \n(c) Microprocessor based, modular type , Intelligent APFC relay capable of having self adjustment to any capacitor value suitable to maintain power factor between 0.95 to 0.99 with digital indication of power factor, preset parameters and having in built capability of indication and elimination of defective capacitor steps. 1 Each Job
52 52 Earthing complete with galvanised MS earth plate of size 600 x 600 x 6mm thick burried directly in ground not less than 2.25 Mtr below ground level, earth plate paced on all side with charcoal mixed with salt to a thickness of 150mm in layers, connected by GI earth strip of size 32 x 6mm thick, soldered and revetted to earth plate. GI earth strip will be protected by using 40mm bore GI pipe (light grade) from test point to main board. The earthing includes PCC pit chamber, RCC pit cover and frame, watering pipe 20mm bore, funnel with wire mess with necessary earth work including disposal of surplus soil to a distance not less than 50 Mtr etc as shown in electrical plate No 3 of SSR Part-I complete all as specified and directed . 2 Each
53 53 M&L for overhauling of complete diesel engine by opening top head, cleaning of engine of Generator and replace worned out parts of engine, checking and setting right the alignment of Engine & Alternator, servicing of engine for smooth running, observing & setting correctly the unusual sound & color of smoke from exhaust (if any), repairing the leakage of fuel, lubricating oil & coolant, repairing of accessories drive, turbocharger and crankshaft endplay, rewinding of burnt armature of rotor / stator, greasing, cleaning, removal of carbon deposits and other unwanted reminants, re-assembling the complete engine by nuts, bolts, washers etc., lathe machining work incl. fixing it in position and testing on load complete all as specified and directed.\nCapacity of DG Set :- 180 KVA.\nEngine Make & Model:- Greaves Cotton, TBD3V6\nMake of Alternator:- Stamford\nNote:- All damaged / unserviceable / worn out / broken parts shall be replaced and paid for separately under respective items of BOQ. 1 Each Job
54 54 Supply only Engine Block of existing make and size complete all as specified and directed. 1 Each
55 55 Supply only Pistons ring set of existing make and size complete all as specified and directed. 6 Each Set
56 56 Supply only Cylinder liner ‘O’ ring kit of existing make and size complete all as specified and directed. 6 Each Set
57 57 Supply only Main bearings kit of existing make and size complete all as specified and directed.\n 3 Each Set
58 58 Supply only Connecting Rod bearings kit of existing make and size complete all as specified and directed. 6 Each Set
59 59 Supply only Connecting Rod bushings kit of existing make and size complete all as specified and directed. 6 Each Set
60 60 Supply only Connecting Rod of existing make and size complete all as specified and directed. 1 Each
61 61 Supply only Piston lock of existing make and size complete all as specified and directed. 12 Each Set
62 62 Supply only Head gaskets kit of existing make and size complete all as specified and directed. 6 Each Set
63 63 Supply only Crank shaft Assembly of existing make and size complete all as specified and directed. 1 Each Set
64 64 Supply only Oil Seals Kit of existing make and size complete all as specified and directed. 1 Each Set
65 65 Supply only Packing Kit of existing make and size complete all as specified and directed. 1 Each Set
66 66 Supply only Self Starter and accessories of existing make and size complete all as specified and directed. 1 Each Set
67 67 Topping up of Engine Oil of 15W40 grade complete all as specified and directed. 15 Litre
68 68 Topping up of Coolant for radiator complete all as specified and directed. 15 Litre