Military Engineer Services-MES has published Special Repairs/Replacement Of Electric Meter In Jcos/Or Md Accn And Provn Of Ac Points In Offrs Md Accn Automation Of Street Lights And Special Repairs For Replacement Of Oh Lines With Ug Cables And Street Lights At Ajmer Under Ge Nasirabad Special Re. Submission Date for this Tender is 24-08-2020. Energy Meter Tenders in NASIRABAD Rajasthan. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 06-Mar-2020 | Corrigendum No 01 | Date | 19-03-2020 |
2 | 13-Mar-2020 | Corrigendum no 02 | Date | 26-03-2020 |
3 | 19-Mar-2020 | Corrigendum no 03 | Date | 07-04-2020 |
4 | 24-Mar-2020 | Corrigendum No 04 | Date | 14-04-2020 |
5 | 04-Apr-2020 | Corrigendum No 05 | Date | 23-04-2020 |
6 | 15-Apr-2020 | CORRIGENDUM NO 6 | Date | 18-05-2020 |
7 | 11-May-2020 | CORRIGENDUM NO 7 | Date | 04-06-2020 |
8 | 26-May-2020 | CORRIGENDUM NO 08 | Date | 15-06-2020 |
9 | 09-Jun-2020 | Corrigendum No 09 | Date | 24-06-2020 |
10 | 19-Jun-2020 | Corrigendum NO 10 | Date | 01-07-2020 |
11 | 26-Jun-2020 | Corrigendum No 11 | Date | 08-07-2020 |
12 | 03-Jul-2020 | Date Corrigendum | Date | 20-07-2020 |
13 | 13-Jul-2020 | Dates Corrigendum | Date | 04-08-2020 |
14 | 27-Jul-2020 | Date Corrigendums | Date | 24-08-2020 |
Name of Work: SPECIAL REPAIRS/REPLACEMENT OF ELECTRIC METER IN JCO'S/OR MD ACCN & PROVN OF AC POINTS IN OFFRS MD ACCN, AUTOMATION OF STREET LIGHTS AT NASIRABAD & SPECIAL REPAIRS FOR REPLACEMENT OF OH LINES WITH UG CABLES & STREET LIGHTS AT AJMER UNDER GE NASIRABAD. | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Taking down carefully copper / aluminium point wiring complete with concealed/surface conduit/casing caping wiring & removing from site and making good the disturbed surface of walls/ceiling etc & M & L for point wiring with 4 sqmm single core multi stranded copper conductor PVC insulated unsheathed (FRLS) cable 1100 volts grade drawn through and including non metallic rigid PVC concealed conduit 20mm dia or higher with all PVC conduit accessories with earth continuity conductor of size 4 sqmm single core copper conductor multistranded cable connected to common earth dolly for AC point complete all as specified and directed. | BI01010001010000000000000515BI0100001112 | 200 | POINT |
2 | 2 | taking out old unserviceable sub main wiring & M & L for submain wiring with two single core PVC insulated, unsheathed multistranded (FRLS) copper conductor cable of size 6 Sqmm LT, 1100 volts grade, drawn through and including 25mm dia or higher PVC on metatic concealed conduit with accessories such as socket, elbow, junction box, bell mouth, reducer, bend and flexible conduit etc and fittings and one run of 6 sqmm single core multistranded copper conductor cable green colour as earth continuity conductor with suitable lugs made of copper connected to earth dolly complete all as specified and directed. \nNote :- Two run of single core cable, one run of earth continuity conductor and 1m of conduit shall be measured as one unit length. | BI01010001010000000000000515BI0100001113 | 1040 | RM |
3 | 3 | S&F of sheet metal board box made out of 1.6mm thick M.S sheet complete with locking arrangement and painted with two coats of synthetic enamel paint over a coat of red oxide primer concealed in wall of size 75x105 cm including provision of suitable opening with glass cover to be provided for recording electric meters reading and fiber sheet 10mm thick for fixing meter complete all as specified & directed (for housing MCB distribution board & electric meters etc). | BI01010001010000000000000515BI0100001114 | 20 | EACH |
4 | 4 | S & F in repair sheet metal enclosure, 240 volts, single pole and neutral with a two pin and earth plug and socket complete with one single pole MCB 25 Amps, 10 kA, 'C' curve complete all as specified & directed. | BI01010001010000000000000515BI0100001115 | 200 | EACH |
5 | 5 | S&F in repair distribution board triple pole & neutral 4 way, 415 volts with 200 Amps rated bus bar, double door, IP-43, DB's made out of sheet steel enclosure, recessed type, factory made powder coated suitable for housing MCB's and isolator's complete all as specified and directed. \nMake:Legrand/Siemens/Schneider Note : MCB DB and MCB will be of same make. | BI01010001010000000000000515BI0100001116 | 10 | EACH |
6 | 6 | S&F of distribution board triple pole & neutral 6 way, 415 volts with 200 Amps rated bus bar, double door, IP-43, DB's made out of sheet steel enclosure, recessed type, factory made powder coated suitable for housing MCB's and isolator's complete all as specified and directed. \nMake:Legrand/Siemens/Schneider Note : MCB DB and MCB will be of same make. | BI01010001010000000000000515BI0100001117 | 12 | EACH |
7 | 7 | S&F in repair distribution board single pole & neutral, 8 way, 240 volts with 200 Amps rated bus bar, double door, IP-43, DB's made out of sheet steel enclosure, recessed type, factory made powder coated suitable for housing MCB's and isolator's complete all as specified and directed. \nMake:Legrand/Siemens/Schneider Note : MCB DB and MCB will be of same make. | BI01010001010000000000000515BI0100001118 | 100 | EACH |
8 | 8 | S&F in repair MCB triple pole and neutral 240 Volt 10 KA 63Amp conforming to IS 8828 of 1996, Curve 'C' complete all as specified & directed.\nMake : Legrand/ Siemens/ Schneider | BI01010001010000000000000515BI0100001119 | 10 | EACH |
9 | 9 | S&F in repair MCB single pole and neutral 240 Volt 10 KA 40Amp conforming to IS 8828 of 1996, Curve 'C' complete all as specified & directed.\nMake : Legrand/ Siemens/ Schneider | BI01010001010000000000000515BI0100001120 | 100 | EACH |
10 | 10 | S&F in repair MCB single pole 240 volt 10 KA 5 to 32 Amp conforming to IS 8828 of 1996, Curve 'C' complete all as specified & directed. \nMake : Legrand/ Siemens/ Schneider | BI01010001010000000000000515BI0100001121 | 640 | EACH |
11 | 11 | Takin out old unserviceable earthing & M & L for earthing complete with GI earth plate electrode 60 cm x 60 cm x 6.00mm thick, buried directly in ground (earth pit not less than 2.25mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtrs below normal ground level connected to GI lead wire 4.00mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electric plate No 3 of SSR Part-I connected to continuous earth wire on main switch board all as specified or indicated and testing on completion including provision of earth wire protection by 15mm dia medium grade GI pipe and watering pipe shall be 20mm bore, medium grade including excavation & earth work in any type of soil & disposal of sil chamber in mix 1:3:6 type C-1 with 40mm thick RCC 1:2:4 type B-1 cover, reinforced with 8mm TMT bars 100mm C/C both ways with life hook made out of 8mm dia bars, watering arrangement with funnel and wire mesh completed all as specified and directed. | BI01010001010000000000000515BI0100001122 | 22 | EACH\nJOB |
12 | 12 | M & L for earthing complete with GI earth plate electrode 60 cm x 60 cm x 6.00mm thick, buried directly in ground (earth pit not less than 2.25mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtrs below normal ground level connected to GI earth lead strip 30 x 6mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electric plate No 3 of SSR Part-I connected to continuous earth wire on main switch board all as specified or indicated and testing on completion including provision of earth wire protection by 15mm dia medium grade GI pipe and watering pipe shall be 20mm bore, medium grade including excavation & earth work in any type of soil & disposal of sil chamber in mix 1:3:6 type C-1 with 40mm thick RCC 1:2:4 type B-1 cover, reinforced with 8mm TMT bars 100mm C/C both ways with life hook made out of 8mm dia bars, watering arrangement with funnel and wire mesh completed all as specified and directed. | BI01010001010000000000000515BI0100001123 | 6 | EACH\nJOB |
13 | 13 | Disconnecting & taking out old unservicable electric meter & deposited in E/M storeyard and S&F single phase tamper proof electronic meter , LCD display with polycarbonate tamper proof cover, 230/240V, 10-60 Amp, accuracy class I, 50 Hz, conforming to IS 13779, IP 54, (with parameters to show date, time, current reading, Load, PF, Voltage and KWH ) with optional optical port and sealing of meter first quality of size 250 mm x 300 mm and making elctric connections complete all as directed specifed and directed.\nMake : Secure Meters (Model -Saral) or eqivelent in L&T/HPL | BI01010001010000000000000515BI0100001124 | 100 | EACH |
14 | 14 | Excavating in trenches, not exceeding 1.5m wide and not exceeding 1.5m in depth for pole foundation, cable trench, etc and getting out in soft/loose soil complete all as specified and directed. | BI01010001010000000000000515BI0100001125 | 473 | CUM |
15 | 15 | Excavating in trenches, not exceeding 1.5m wide and exceeding 1.5m but not exceeding 3m in depth for pole foundation, cable trench, etc and getting out in soft/loose soil complete all as specified and directed. | BI01010001010000000000000515BI0100001126 | 2.5 | CUM |
16 | 16 | Returning, filling in with excavated approved soil, including spreading, leveling, watering and well ramming in layers not exceeding 25cm each complete all as specified and directed. | BI01010001010000000000000515BI0100001127 | 322 | CUM |
17 | 17 | Removing excavated soil not exceeding 50m and depositing where directed. at a level not exceeding 1.5m above the starting point complete all as specified and directed. | BI01010001010000000000000515BI0100001128 | 153.5 | CUM |
18 | 18 | Supply and laying for sand filling with clean dry fine sand unwashed including gently punning around cables in trenches for cable protection complete all as specified and directed. \nNote:-Compacted/punned thickness shall be measured & paid separetely. | BI01010001010000000000000515BI0100001129 | 151 | CUM |
19 | 19 | Supply and laying brick protection over to LT underground cable with old size sub class 'B' bricks locally availabie dry laid flat across of the length of trench as in cable protection complete all as specified and directed. | BI01010001010000000000000515BI0100001130 | 15 | PER 1000 Nos |
20 | 20 | S&F in repair 80mm GI tubing light grade with all fittings as required for passing through cables under floors, along the wall or along the pole, etc with suitable size M.S.flat iron clamps incl nut,bolt and washer complete all as specified and directed. | BI01010001010000000000000515BI0100001131 | 20 | RM |
21 | 21 | S&F in repair 50mm GI tubing light grade with all fittings as required for passing through cables under floors, along the wall or along the pole, etc with suitable size M.S.flat iron clamps incl nut,bolt and washer complete all as specified and directed. | BI01010001010000000000000515BI0100001132 | 30 | RM |
22 | 22 | S&F in repair 40mm GI tubing light grade with all fittings as required for passing through cables under floors, along the wall or along the pole, etc with suitable size M.S.flat iron clamps incl nut,bolt and washer complete all as specified and directed. | BI01010001010000000000000515BI0100001133 | 40 | RM |
23 | 23 | S&F in repair 25mm GI tubing light grade with all fittings as required for passing through cables under floors, along the wall or along the pole, etc with suitable size M.S.flat iron clamps incl nut,bolt and washer complete all as specified and directed. | BI01010001010000000000000515BI0100001134 | 90 | RM |
24 | 24 | S&F 40mm GI tubing light grade with all fittings as required for passing through cables under floors, along the wall or along the pole, etc with suitable size M.S.flat iron clamps incl nut,bolt and washer complete all as specified and directed. | BI01010001010000000000000515BI0100001135 | 42 | RM |
25 | 25 | Supply, laying, connecting and testing LT XLPE insulated, screened, PVC bedded, armoured, heavy duty cable with aluminium stranded conductor of size 185 sqmm, 3.5 core, 1100 volts grade, laid in trenches, passing through pipes/ducts, etc complete all as specified and directed. | BI01010001010000000000000515BI0100001136 | 80 | RM |
26 | 26 | Supply, laying, connecting and testing LT XLPE insulated, screened, PVC bedded, armoured, heavy duty cable with aluminium cstranded conductor of size 95 sqmm, 3.5 core, 1100 volts grade, laid in trenches, passing through pipes/ducts, etc complete all as specified and directed. | BI01010001010000000000000515BI0100001137 | 100 | RM |
27 | 27 | Supply, laying, connecting and testing LT XLPE insulated, screened, PVC bedded, armoured, heavy duty cable with aluminium stranded conductor of size 70 sqmm, 3.5 core, 1100 volts grade, laid in trenches, passing through pipes/ducts, etc complete all as specified and directed. | BI01010001010000000000000515BI0100001138 | 80 | RM |
28 | 28 | Supply, laying, connecting and testing LT XLPE insulated, screened, PVC bedded, armoured, heavy duty cable with aluminium cstranded conductor of size 50 sqmm, 3.5 core, 1100 volts grade, laid in trenches, passing through pipes/ducts, etc complete all as specified and directed. | BI01010001010000000000000515BI0100001139 | 150 | RM |
29 | 29 | Supply, laying, connecting and testing LT XLPE insulated, screened, PVC bedded, armoured, heavy duty cable with aluminium stranded conductor of size 25 sqmm, 3.5 core, 1100 volts grade, laid in trenches, passing through pipes/ducts, etc complete all as specified and directed. | BI01010001010000000000000515BI0100001140 | 120 | RM |
30 | 30 | Supply, laying, connecting and testing LT XLPE insulated, screened, PVC bedded, armoured, heavy duty cable with aluminium cstranded conductor of size 16 sqmm, 4 core, 1100 volts grade, laid in trenches, passing through pipes/ducts, etc complete all as specified and directed. | BI01010001010000000000000515BI0100001141 | 1100 | RM |
31 | 31 | Supply, laying, connecting and testing LT XLPE insulated, screened, PVC bedded, armoured, heavy duty cable with aluminium stranded conductor of size 10 sqmm, 2 core, 1100 volts grade, laid in trenches, passing through pipes/ducts, etc complete all as specified and directed. | BI01010001010000000000000515BI0100001142 | 670 | RM |
32 | 32 | Supply, laying, connecting and testing LT XLPE insulated, screened, PVC bedded, armoured, heavy duty cable with aluminium cstranded conductor of size 10 sqmm, 4 core, 1100 volts grade, laid in trenches, passing through pipes/ducts, etc complete all as specified and directed. | BI01010001010000000000000515BI0100001143 | 30 | RM |
33 | 33 | Supply, laying, connecting and testing LT XLPE insulated, screened, PVC bedded, armoured, heavy duty cable with aluminium stranded conductor of size 6 sqmm, 2 core, 1100 volts grade, laid in trenches, passing through pipes/ducts, etc complete all as specified and directed. | BI01010001010000000000000515BI0100001144 | 200 | RM |
34 | 34 | Disconnecting and carefully taking down existing old/ unserviceable ACSR conductor complete with PVC spacers from LT/HT steel tubular pole/RCC pole and removing from site complete all as specified and directed. | BI01010001010000000000000515BI0100001145 | 4 | QTL |
35 | 35 | Disconnecting and carefully taking down old / unserviceable insulator, any type, any size from the LT/HT poles and removing from site complete all as specified and directed. | BI01010001010000000000000515BI0100001146 | 100 | EACH |
36 | 36 | Dismantling of cross arms of MS channel or angle section and removing from site or setting aside for reuse complete specified and directed. | BI01010001010000000000000515BI0100001147 | 1.2 | QTL |
37 | 37 | Dismantling stay assembly complete, any type any size complete making good disturbed surfaces and removing from site all as specified and directed | BI01010001010000000000000515BI0100001148 | 10 | EACH\nSET |
38 | 38 | Dismantling of old unserviceable LT concrete pole, any size and removing from site complete all as directed. | BI01010001010000000000000515BI0100001149 | 15 | EACH |
39 | 39 | Disconnecting and taking down of 8 SWG galvanized steel wire for earth continuity conductor main guard wire/stay wire etc complete all as specified and directed | BI01010001010000000000000515BI0100001150 | 1 | QTL |
40 | 40 | Taking out old unserviceable UG cable of any size and core & removing from site complete all as specified and directed. | BI01010001010000000000000515BI0100001151 | 250 | RM |
41 | 41 | M & L for boring holes of size 80mm dia & 2mtr deep in soil for laying of UG cables complete all as specified and directed. | BI01010001010000000000000515BI0100001152 | 50 | RM |
42 | 42 | M&L for PCC 1:4:8 type D-2 using 40mm graded stone aggregate in foundations, filling and mass concrete complete all as specified and directed. | BI01010001010000000000000515BI0100001153 | 15 | CUM |
43 | 43 | M&L for PCC 1:2:4 type B-1 using 20mm graded stone aggregate in copings to poles & the like, etc including weathering, slightly rounded or chamfered angles and throating as directed. including necessary form work complete all as specified and directed. | BI01010001010000000000000515BI0100001154 | 4 | CUM |
44 | 44 | Supply and fix stay assembly comprising of stay bow galvanized 14 mm dia x 400 mm long, stay rod 20 mm 180 mm long with nuts, bolt, washer, MS stay plate,two Nos thimble clamps complete all as specified in electrical Plate No 1 of SSR Part-I complete all as specified and directed | BI01010001010000000000000515BI0100001155 | 1 | EACH\nSET |
45 | 45 | M & L for galvanized steel stranded stay wire of size 7/4mm, grade 4 for stay of poles incl necessary clamps of 50 x 6 mm FI and bolts nuts of suitable size complete all as specified and directed. | BI01010001010000000000000515BI0100001156 | 0.4 | QTL |
46 | 46 | M & L for cross arms, bracings, supports, back plate & clamps fabricated from structural steel section including nuts, bolts, washers cuttings, welding bending cold or hot, drilling holes for bolts in any shape or size inclusive of painting with 2 coats of aluminum paint over a coat of primer complete all as specified and directed | BI01010001010000000000000515BI0100001157 | 1 | QTL |
47 | 47 | Supply, transportation, commissioning and erection of steel tubular swaged pole complete with cast iron base plate, finial taper plug, bolt nut & screw size as specified type 410 SP-31, 9 mtr long conforming to IS- 1678 and including marking alternate white and black strips 30 cm height- total-5Nos with two coats of synthetic enamel paint over a coat of primer complete all as specified \n( Excavation and earth work and PCC for foundation to be measured and paid for separately). | BI01010001010000000000000515BI0100001158 | 15 | EACH |
48 | 48 | S&F in repair three core core PVC insulated, unsheathed, copper conductor cable FRLS, 1100 volts grade 2.5 Sqmm multi stranded copper conductor cable for coonnecting garden light fittings complete all as specified and directed. | BI01010001010000000000000515BI0100001159 | 275 | RM |
49 | 49 | Supply, fixing and testing Street light automatic Nature switch of capacity 3 KW single phase complete with high and low voltage and overload protection, degree of protection confirm to IP-55 AC, SP complete with MCB and power contactor fixed in & nincluding suitable size of HDPE box fixed on pole with 25 X 3mm MS strip clamp complete all as specified and directed.\nMake - Kakatiya Energy system Model SWADEEP-02 EC 3KW IP or equivalent as approved by GE. | BI01010001010000000000000515BI0100001160 | 2 | EACH |
50 | 50 | Taking out old unsv light fitting and refixing energy saving LED street lighting integral LED street light luminaire comprising of epoxy powder coated housing, enclosed with glass cover in frame 60 X 1.2W mounted on MCPCB connecting to the conductor all as specified and directed by Engineer-in-Charge. | BI01010001010000000000000515BI0100001161 | 30 | EACH |
51 | 51 | Taking out old unsv light fitting and Supply, fixing testing and commissioning energy saving LED street lighting "pressure die cast aluminium housing LED street light luminaire" comprising of epoxy powder coated housing, enclosed with glass cover in frame 72 W mounted on MCPCB complete with fixing bracket all as directed.\nMake : Cat Part No BRTFG 72 LED of Bajaj or equivalent makes as specified in Appendix 'B'. | BI01010001010000000000000515BI0100001162 | 10 | EACH |
52 | 52 | S&F control box for street light made of HDPE comprising of MCB 6 Amps double pole -01 No, bus bar of 63 Amps rating aluminium for phase and netural on porcelain based insulators with locking arrangement fixed to pole with MS clamp of size 25x3 mm, nuts bolts and washers complete all as specified & directed. Make : Sintex/ Hensel/ SHI/BRITE | BI01010001010000000000000515BI0100001163 | 40 | EACH |
53 | 53 | Taking out old unserviceable GI bracket & S & F bracket of GI pipe, 40mm bore, light grade 1.20 mtr long, cut to length and bent to shape and mild steel clamp of 40 x 6 mm size, (2 Nos) nuts, bolts of required size and length complete all as specified & directed. | BI01010001010000000000000515BI0100001164 | 40 | EACH |
54 | 54 | S&F in repairs MCCB, 200 Amp, 4 Pole, 35 KA, 415 V, thermal magnetic release type, Ics=100 % Icu, with adjustable overload setting and adjustable short circuit setting , with thermal release range 160-200 Amp including spreader terminals and phase barriersincluding taking down old unserviceable MCCB complete all as specified and directed. \nMake L&T (d - sine) Cat No. CM90642OONO or equivelent in Schinder/ Legrand as approved by GE | BI01010001010000000000000515BI0100001165 | 1 | EACH |
55 | 55 | S&F in repair MCB triple pole and neutral 240 Volt 10 KA 63Amp conforming to IS 8828 of 1996, Curve 'C' complete all as specified & directed.\nMake : Legrand/ Siemens/ Schneider | BI01010001010000000000000515BI0100001166 | 2 | EACH |
56 | 56 | S & F copper bus 300 amp on existing panel complete all as per specified and directed. | BI01010001010000000000000515BI0100001167 | 32 | RM |
57 | 57 | Taking down old unserviceable electric panel & Supply, install, testing and commissioning of electric panel board outdoor type suitable for LT 415 volts 3 phase 4 wire system factory made cubical complete materialised dust and vermin proof (protection class IP 54), made out of 3.15mm thick MS sheet (CRCA) including factory made (CPRI approved) hinged type double door both side opening with locking arrangement with handle (godrej type) duly painted with seimens grey powder coated finish over a coat of zinc chrome primer including carry out internal connection with suitable bus bar including cable alley for incoming and outgoing cable complete all as specified and directed by Engineer-In-Charge. The panel board shall be comprising of the following accessories.\n(a) Copper bus bar cap 400 Amp-04\n(b) MCCB four pole with thermal magnetic release adjustable type with breaking capacity 35 KA 250 Amp (In coming)- 01 No\n(c) MCCB four pole with thermal magnetic release adjustable type with breaking capacity 35 KA 200 Amp (out going)- 01 No\n(d) MCCB four pole with thermal magnetic release adjustable type with breaking capacity 25 KA 100 Amp (out going)- 01 No\n(e) Isolator TPN 63 amp (out going)- 02 No\n(f) Isolator DP 32 amp (out going)- 06 No | BI01010001010000000000000515BI0100001168 | 1 | EACH |
58 | 57.01 | contd item No. 57.00 (g) Digital multi-Function meter of size 96x96 mm, display to measure - voltage,current ,frequency,power factor in 03 line LED backlight display having programmable CT ratio(all as per incommer MCCB) and build in selecter switch - 01 No\n(h) RYB neon indicating lamp set of three- 01 set | BI01010001010000000000000515BI0100001169 | ||
59 | 58 | Taking down old unserviceable electric panel & Supply, install, testing and commissioning of electric panel board outdoor type suitable for LT 415 volts 3 phase 4 wire system factory made cubical complete materialised dust and vermin proof (protection class IP 54), made out of 3.15mm thick MS sheet (CRCA) including factory made (CPRI approved) hinged type double door both side opening with locking arrangement with handle (godrej type) duly painted with seimens grey powder coated finish over a coat of zinc chrome primer including carry out internal connection with suitable bus bar including cable alley for incoming and outgoing cable complete all as specified and directed by Engineer-In-Charge. The panel board shall be comprising of the following accessories.\n(a) Copper bus bar cap 300 Amp-04\n(b) MCCB four pole with thermal magnetic release adjustable type with breaking capacity 35 KA 200 Amp (In coming)- 01 No\n(c) MCCB four pole with thermal magnetic release adjustable type with breaking capacity 25 KA 100 Amp (out going)- 01 No\n(d) MCCB four pole with thermal magnetic release adjustable type with breaking capacity 25 KA 63 Amp (out going)- 01 No\n(e) Isolator TPN 63 amp (out going)- 02 No\n(f) Isolator DP 40 amp (out going)- 04 No | BI01010001010000000000000515BI0100001170 | 1 | EACH |
60 | 58.01 | contd item No. 58.00 (g) Digital multi-Function meter of size 96x96 mm, display to measure - voltage,current ,frequency,power factor in 03 line LED backlight display having programmable CT ratio(all as per incommer MCCB) and build in selecter switch - 01 No\n(h) RYB neon indicating lamp set of three- 01 set | BI01010001010000000000000515BI0100001171 | ||
61 | 59 | Taking down old unserviceable electric panel & Supply, install, testing and commissioning of electric panel board outdoor type suitable for LT 415 volts 3 phase 4 wire system factory made cubical complete materialised dust and vermin proof (protection class IP 54), made out of 3.15mm thick MS sheet (CRCA) including factory made (CPRI approved) hinged type double door both side opening with locking arrangement with handle (godrej type) duly painted with seimens grey powder coated finish over a coat of zinc chrome primer including carry out internal connection with suitable bus bar including cable alley for incoming and outgoing cable complete all as specified and directed by Engineer-In-Charge. The panel board shall be comprising of the following accessories.\n(a) Copper bus bar cap 200 Amp-04\n(b) MCCB four pole with thermal magnetic release adjustable type with breaking capacity 25 KA 100 Amp (In coming)- 01 No\n(c) MCCB four pole with thermal magnetic release adjustable type with breaking capacity 25 KA 63 Amp (out going)- 01 No\n(d) Isolator DP 40 amp (out going)- 06 No\n(e) Digital multi-Function meter of size 96x96 mm, display to measure - voltage,current ,frequency,power factor in 03 line LED backlight display having programmable CT ratio(all as per incommer MCCB) and build in selecter switch - 01 No\n(h) RYB neon indicating lamp set of three- 01 set | BI01010001010000000000000515BI0100001172 | 1 | EACH |
62 | 59.01 | Notes for item No 57.00 to 59.00 :- \n(i) Rates are deemed to be inclusive of PCC platform of suitable size and 45cm height and 4 Nos legs of 50mmx50mmx6mm and 60 cm in height for fixing the panel / bus bar chamber \n(ii) MCCB shall be fixed in suitable sheet metal enclouser \n(iii) Danger notice plate (02 Nos) LT size 20cmx 15cm shall be fixed on the panel / bus bar chamber \n(iv) Contractor provided powder coated finish paint on panel.\n | BI01010001010000000000000515BI0100001173 | ||
63 | 60 | Supply and installation of three phase intelligent feeder pillars with the following specifications :-\n\n(i) Ground mounted with bottom supply including civil work with existing base mounting\n(ii) CRCA with 2mm thickness for lad bearing and 1.6mm for other sections with IP 55 Protection\n(iii) Incoming MCCB 100 Amp 16KA 4 Pole with thermal magnetic release\n(iv) 110A, single phase coil operated, 3 pole contactor conforming to IS/IEC 60947-4-1 Make : L&T or equivalent \n(v) 96mm flush type multifunction meter communication, Make : L&T or or equivalent\n(vi) A set of 3 CT for 100/5 Amp\n(vii) LED indication lamp RYB with fuse fitting\n(viii) 6 Amp multi step three way selection switch with auto manual and remote\n(ix) Astro timer, Make : L&T or equivalent\n(x) GPRS modem for two way communication, Make : wired-in or equivalent | BI01010001010000000000000515BI0100001174 | 12 | EACH |
64 | 61 | Supply and installation of single phase intelligent feeder pillars with the following specifications :-\n\n(i) Pole mounted with bottom supply \n(ii) CRCA with 2mm thickness for lad bearing and 1.6mm for other sections with IP 55 Protection\n(iii) Incoming 16A/32A MCB and natural link, Make : L&T or equivalent\n(iv) 16A/32A, power contactor, Make : L&T or equivalent \n(v) 96mm flush type multifunction meter data communication, Make : L&T or or equivalent\n(vi) A set of 3 CT for 100/5 Amp\n(vii) LED indication lamp RYB with fuse fitting\n(viii) 6 Amp multi step three way selection switch with auto manual and remote\n(ix) Astro timer, Make : L&T or equivalent\n(x) GPRS modem for two way communication, Make : wired-in or equivalent | BI01010001010000000000000515BI0100001175 | 11 | EACH |
65 | 62 | Supply and configuration of energy monitoring wef based cloud hosted software with the following features :-\n(a) Data collection for parameters such as KWH, KW, Amp meter, Volt meter, Power factor every 30 minutes or less\n(b) Counting/setting of connected lights, active lights working status (approximate) \n(c) Online disconnection of streetlights\n(d) Daily/Monthly consumptions monitoring, Make : Innoligis, Wire-in, L&T | BI01010001010000000000000515BI0100001176 | 23 | EACH |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy