Military Engineer Services-MES has published Repair To Old Vintage Lt Panels And Other Connected Works , Provision Of Electric Panel Near Gate No-04 And Provn Of Electric Connection For Arboriculture Near A Mess At Awc Under Ge ( Awc ) Mhow .. Submission Date for this Tender is 21-02-2020. Electrical Panel Tenders in GE AWC MHOW Madhya Pradesh. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 07-Feb-2020 | Corrigendum2 | Date | 17-02-2020 |
2 | 18-Feb-2020 | Corrigendum3 | Date | 21-02-2020 |
Name of Work : REPAIR TO OLD VINTAGE LT PANELS AND OTHER CONNECTED WORKS, PROVN OF ELECTRIC PANEL NEAR GATE NO-04 AND PROVN OF ELECTRIC CONNECTION FOR ARBORICULTURE NEAR ‘A’ MESS AT AWC UNDER GE (AWC) MHOW. | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Excavation in trenches in any type of soil not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth for laying of cable and fixing pole, stays etc and getting out complete all as specified and directed. | 410 | Cum | |
2 | 2 | Returning, filling in, including spreading, levelling watering and well ramming in layers not exceeding 25 cm thick excavated soil complete all as specified and directed. | 185 | Cum | |
3 | 3 | Removing excavated material not exceeding 50 m and depositing where directed at a level not exceeding 1.5m above the starting point Soils complete all as specified and directed..\n | 225 | Cum | |
4 | 4 | M&L river washed and screened dry fine sand filling in trenches below and above / around under ground cable for cable protection, in duct under & abobe the cables including punning around cable complete all as specified and directed. \nNote :- Punned thickness shall be measured for payment. | 118 | Cum | |
5 | 5 | M & L for unreinforced PCC Cable protection cover , Class LV ,Type1 flat ,size 250x150x40mm as cable protection laid flat width wise complete all as specified and directed. | 11520 | Each | |
6 | 6 | Supply and laying galvanised iron pipe 'light Grade' 50 mm in trenches , under floors, roads, along poles for protection of cables with all necessary fittings, including sealing ends complete all as specified and directed . Make:- Jindal /Prakash Surya /Tata | 30 | RM | |
7 | 7 | Supply and laying galvanised iron pipe 'light Grade' 80 mm in trenches , under floors, roads, along poles for protection of cables with all necessary fittings, including sealing ends complete all as specified and directed . Make:- Jindal /Prakash Surya /Tata | 20 | RM | |
8 | 8 | Drilling (Horizontally) existing road (Maximum 10 mtr wide ) suitable for passing GI tubing 80 mm complete all as specified and directed.( GI tubing light grade measured and paid under respected item) | 25 | RM | |
9 | 9 | Supply, laying or fixing, jointing and testing LT under ground electric power cable of size 120 sqmm, 3.5 core. Crossed linked polyethylene (XLPE Cable ) insulated, galvanised steel strip or wire armoured, ISI -7098 Marked. With aluminium conductor multi stranded , heavy duty 1100 Volts grade complete all as specified laid in tenches / laid under floor or fixed with walls/ on poles/ in ducts/ in GI pipes etc including taking down existing complete all as directed at site. Make:- Polycab, Havells, Gloster | 150 | RM | |
10 | 10 | Description same all as per item No 09.00 here in before but 70 Sqmm, 3.5 core | 120 | RM | |
11 | 11 | Description same all as per item No 09.00 here in before but 50 Sqmm, 3.5 core | 150 | RM | |
12 | 12 | M&L for painting for LT panel two coat of approved paint including prepration of existing surfaces and one coat of red oxide including panel frame angle iron complete all as specified and directed by Engr-in-Charge. | 20 | Each Job | |
13 | 13 | M & L for repair of LT panel including welding of hang , door and back side cover including disconnecting of cable connection and replacement of lugs, insulation of burnt wire, nut bollts with washer etc complete all as specified and directed by Engr-in-Charge. | 20 | Each Job | |
14 | 14 | Material and laobour for earthing in repair complete with galvanized steel earth plate electrode 600mm x600mm x 6mm buried directly in ground vertically to a depth not less than 2.25 meter below normal ground level (with top edge of earth plate not less than 1.5 meter below ground level) connected to GI strip 32mm x 6mm main earthing lead by means of galvanised bolts, nuts and washer all as shown in electrical plate No 3 SSR Part-I with connected to earth test point & to main switch board etc with & including adequate quantity of charcoal dust and common salt alround earth plate, PCC (1:3:6) type C-1 (using 20mm graded black trap/granite/Basalt stone aggregate) for earth pit with 40x40x6mm mild steel angle iron frame for cover, pre cast RCC (1:2:4) type B-1 (using 20mm graded black trap/granite/Basalt stone aggregate) 40mm thick cover reinforced with 6mm dia bars 3 Nos both way with 12mm dia round bar handle, GI light grade watering pipe 20mm dia with funnel and wire mesh, and 40mm dia GI light grade lead protection pipe, complete all as specified and directed. | 7 | Each | |
15 | 15 | Description same all as per item No 14.00 here in before but using galvanised earth lead wire 4.0 mm dia earthing lead. | 7 | Each | |
16 | 16 | S&F in replacement of unserviceable MCCB 63 Amps , 16 KA, tripple pole, breaking cap 415 Volts, 50Hz fixed type complete all as directed by Engineer-in-Charge. \nMake :- Schneider, Legrand, ABB,C&S, L&T | 10 | Each | |
17 | 17 | S&F in replacement of unserviceable MCCB 100 Amps , 16 KA, tripple pole, breaking cap 415 Volts, 50Hz fixed type complete all as directed by Engineer-in-Charge. \nMake :- Schneider, Legrand, ABB,C&S, L&T | 11 | Each | |
18 | 18 | S&F in replacement of unserviceable MCCB 125 Amps , 16 KA, tripple pole, breaking cap 415 Volts, 50Hz fixed type complete all as directed by Engineer-in-Charge. \nMake :- Schneider, Legrand, ABB,C&S, L&T | 10 | Each | |
19 | 19 | S&F in replacement of unserviceable MCCB 160 Amps , 36 KA, tripple pole, breaking cap 415 Volts, 50Hz fixed type complete all as directed by Engineer-in-Charge. \nMake :- Schneider, Legrand, ABB,C&S, L&T | 10 | Each | |
20 | 20 | S&F in replacement of unserviceable MCCB 200 Amps , 36 KA, tripple pole, breaking cap 415 Volts, 50Hz fixed type complete all as directed by Engineer-in-Charge. \nMake :- Schneider, Legrand, ABB,C&S, L&T | 4 | Each | |
21 | 21 | S&F in replacement of unserviceable MCCB 250 Amps , 36 KA, tripple pole, breaking cap 415 Volts, 50Hz fixed type complete all as directed by Engineer-in-Charge. \nMake :- Schneider, Legrand, ABB,C&S, L&T | 4 | Each | |
22 | 22 | S&F in replacement of unserviceable MCCB 400 Amps , 36 KA, tripple pole, breaking cap 415 Volts, 50Hz fixed type complete all as directed by Engineer-in-Charge. \nMake :- Schneider, Legrand, ABB,C&S, L&T | 4 | Each | |
23 | 23 | Supply, laying or fixing, jointing and testing LT under ground electric power cable of size 150 sqmm, 3.5 core. Crossed linked polyethylene (XLPE Cable ) insulated, galvanised steel strip or wire armoured, ISI -7098 Marked. With aluminium conductor multi stranded , heavy duty 1100 Volts grade complete all as specified laid in tenches / laid under floor or fixed with walls/ on poles/ in ducts/ in GI pipes etc including taking down existing complete all as directed at site. \nMake:- Polycab, RR Kabel, Gloster | 500 | RM | |
24 | 24 | Supply, laying or fixing, jointing and testing LT under ground electric power cable of size 95 sqmm, 3.5 core. Crossed linked polyethylene (XLPE Cable ) insulated, galvanised steel strip or wire armoured, ISI -7098 Marked. With aluminium conductor multi stranded , heavy duty 1100 Volts grade complete all as specified laid in tenches / laid under floor or fixed with walls/ on poles/ in ducts/ in GI pipes etc including taking down existing complete all as directed at site. \nMake:- Polycab, RR Kabel, Gloster | 300 | RM | |
25 | 25 | Supply and ix in replacement of sleeve for suitable cable of size upto 35 sqmm, length upto one mtr complete all as directed by Engineer-in-Charge. | 40 | Set of 4 | |
26 | 26 | Supply and ix in replacement of sleeve for suitable cable of size upto 50 to 70 sqmm, length upto one mtr complete all as directed by Engineer-in-Charge. | 35 | Set of 3 | |
27 | 27 | Supply and ix in replacement of sleeve for suitable cable of size upto 95 to 120 sqmm, length upto one mtr complete all as directed by Engineer-in-Charge. | 25 | Set of 3 | |
28 | 28 | Supply , installation , testing and commissioning in replacement LT Panel board outdoor type of size 800 x 800 x 450 mm, Kiosk type factory assembled fabricated (CPRI APPROVED) and of suitablesize angle iron, channel and MS sheet 3 mm thick (inner compartment is 2.0mm thick) double door type , front and rear openable with locking arrangement and indepent duly prewired with colour code three phases and netural for 415 volts, 50 Hz electric supply with and including suitable sizes of cable glands for incoming and outgoing cables , aluminium bus bar 800 Amps , cubical type duly powder coated over a coat of primer , grouting of panel 60 cm above the ground level by provisind 90 cm long angle iron frame bottom of panel 40x40x5 mm thick , welded on all four corners , embedded in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate upto 30 cm and,grouting the panel board on and including suitable size foundation structure with the following components. \nMake of MCCB:-Havells, L&T, Legerend And Make of panel;- Universal switch gear control, M/S power control and equipment,” or any equivalent CPRI approved make as approved by GE.\n(a) MCCB 630 amps 4 pole Fixed type 50KA 415 volts (incoming) – 01No \n(b) MCCB 400 Amps 4 pole ,Fixed type, 25 KA 415 Volts (out going ) -03 Nos\n(c) MCCB TPN 63Amps 3phase and neutral -03 No.\n(c) Aluminium Bus bar of capacity 800 Amps 3phase and neutral -1 set.\n(d)Digital type voltmeer 0-500 volts.\n(e) Digital type Ammeter with CT of suitable ratio for reading upto 800 amps load-01 No\n(f) Indicating lamps R,Y& B -01 set | 1 | Each Job | |
29 | 29 | Supply,installation, commissioning and testing, LT out door type Lt panel board (in repair) of size not less than 1400mmx1200mm x 600mm, kiosk type factory assembled fabricated (CPRI APPROVED) and of suitable size angle iron, channel and MS sheet 3 mm thick (Inner compartment is 2.0 mm thick), double door type, front and rear openable with locking arrangement, duly powder coated painted with locking arrangement and independently housing for each control switch gear duly prewired with colour coading for three phasres and neytral, for 415 volts, 50 Hz electric supply with and including suitable sizes of cable glands for incoming and outgoing cables, grouting the panel board on and including suitable size foundation structure made out if equale angle iron as mentioned mentioned below installation, comissioning and testing complete with the following switch gears/ accessories :- \nMake of MCCB:-Havells, L&T, Legerend And Make of panel;- Universal switch gear control, M/S power control and equipment,” or any equivalent CPRI approved make as approved by GE.\nIncoming :- \n(a) MCCB 400 Amps , 50 KA, 415 Volts - 01 No \n(b) Digital Ammeters 0-400 Amps suitable ratio CT rating and selector switch- 01 No\n(c) Digital Voltmeter with selector switch 0-500 volts(e) Digital type Voltmeter 0 - 500 V,- 01 No\n(c) Aluminium Bus bar of capacity 800 Amps 3phase and neutral -1 set.\n(d) Indicating LED lamps (RYB)-01 Set \nOutgoing :- \n(a) MCCB TPN 160Amps, 25KA ,415 Volts - 03 nos\n(b) MCCB TPN 63 Amps , 415 Volts - 02 nos\n(c) MCB TPN32 Amps , 415 Volts- 3nos\n(d) Time Switch 415 V three phase of 20 Amp rating Contactor fitted - 01 No | 18.56 | Sqm | |
30 | 30 | Supply and erection of HOT DIPP Galvanized galvanisig coating thickness & with internal dimension. cable, the tray of sizes 600x100mm of 16 guage including Coupler 100 mm and nut bolt etc of the trey and dia of the wire should be equal or more than the specified. | 25 | RM | |
31 | 31 | Supply and erection of HOT DIPP Galvanized galvanisig coating thickness & with internal dimension. cable, the tray of sizes 450x100mm of 16 guage including Coupler 100 mm and nut bolt etc of the trey and dia of the wire should be equal or more than the specified. | 25 | RM | |
32 | 32 | Supply and erection of HOT DIPP Galvanized galvanisig coating thickness & with internal dimension. cable, the tray of sizes 300x100mm of 16 guage including Coupler 100 mm and nut bolt etc of the trey and dia of the wire should be equal or more than the specified. | 25 | RM | |
33 | 33 | Supply and erection of HOT DIPP Galvanized galvanisig coating thickness & with internal dimension. cable, the tray of sizes 150x100mm of 16 guage including Coupler 100 mm and nut bolt etc of the trey and dia of the wire should be equal or more than the specified. | 25 | RM | |
34 | 34 | Supply , installation , testing and commissioning in replacement LT Panel board outdoor type of size 800 x 800 x 450 mm, Kiosk type factory assembled fabricated (CPRI APPROVED) and of suitablesize angle iron, channel and MS sheet 3 mm thick (inner compartment is 2.0mm thick) double door type , front and rear openable with locking arrangement and indepent duly prewired with colour code three phases and netural for 415 volts, 50 Hz electric supply with and including suitable sizes of cable glands for incoming and outgoing cables , aluminium bus bar 800 Amps , cubical type duly powder coated over a coat of primer , grouting of panel 60 cm above the ground level by provisind 90 cm long angle iron frame bottom of panel 40x40x5 mm thick , welded on all four corners , embedded in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate upto 30 cm and,grouting the panel board on and including suitable size foundation structure with the following components.\nMake of MCCB:-Havells, L&T, Legerend And Make of panel;- Universal switch gear control, M/S power control and equipment,” or any equivalent CPRI approved make as approved by GE.\n(a) MCCB 160 amps 4 pole Fixed type 36KA 415 volts (incoming) – 01No \n(b) MCCB 63Amps 4 pole ,Fixed type, 25 KA 415 Volts (out going ) -04 Nos\n(c) MCB TPN 63Amps 3phase and neutral -03 No.\n(d) Aluminium Bus bar of capacity 400 Amps 3phase and neutral -1 set.\n(e)Digital type voltmeer 0-500 volts.\n(f) Digital type Ammeter with CT of suitable ratio for reading upto 400 amps load-01 No\n(g) Indicating lamps R,Y& B -01 set | 1 | Each Job | |
35 | 35 | Supply , installation , testing and commissioning in replacement APFC LT PANEL board indoor type of Suitable size type factory assembled fabricated and of suitablesize angle iron, channel and MS sheet 2 mm thick double door type , front and rear openable with locking arrangement and indepent duly prewired with colour code three phases and netural for 415 volts, 50 Hz electric supply with and including suitable sizes of cable glands for incoming and outgoing cables , cubical type duly powder coated over a coat of primer , grouting of panel 60 cm above the ground level by provisind 90 cm long angle iron frame bottom of panel 40x40x5 mm thick , welded on all four corners , embedded in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate upto 30 cm and,grouting the panel board on and including suitable size foundation structure with the following components. \nMake of panel;- Universal switch gear control, M/S power control and equipment,” or any equivalent CPRI approved make as approved by GE.\n1. TP MCCB, 25KA, TM O/L & S/C Trip Release Havells 125A - 01 no. , 2. Control MCB, C Curve Havells 6A- 01 no.\n3. Indication Lights, 230V AC Rep. R/Y/B- set of 3- 01 no , 4. Digital APFC Relay,1 CT, MPBased, 230V Aux. Supply Havells 8 Stage -01 no.\n5 .A/M Selector Switch for Auto & Manual-01 No.\na). Capacitor Bank 20KVAR- 02 Set\n6. TP MCB,32A 10KA, C Curve- 02 no (mk-Havells), 7. TP Power Contactor, AC -3 Duty, 230V AC with inrush current damping L&T 25A -2 no (mk-L&T)\n8. Capacitor Bank, MPP Type, Cyl. Heavy duty Capacitor, 440V AC 20 kVAr - 2no.(mk-Havells)\n9. Illuminated Switch For Manual Switching & Step Indication - 2no.\nb). Capacitor Bank 10KVAR- 01 Set\n10 TP MCB,32A 10KA, C Curve- 02 no (mk-Havells) , 11. TP Power Contactor, AC -3 Duty, 230V AC with inrush current damping L&T 25A -1 no (mk-L&T)\n12. Capacitor Bank, MPP Type, Cyl. Heavy duty Capacitor, 440V AC 20 kVAr - 1no.(mk-Havells)\n13 Illuminated Switch For Manual Switching & Step Indication - 1.no.\nc). Capacitor Bank 10KVAR- 01 Set\n14 TP MCB,20A 10KA, C Curve- 02 no (mk-Havells) , 15. TP Power Contactor, AC -3 Duty, 230V AC with inrush current damping L&T 25A -1 no (mk-L&T)\n16. Capacitor Bank, MPP Type, Cyl. Heavy duty Capacitor, 440V AC 5 kVAr - 1no.(mk-Havells)\n17. Illuminated Switch For Manual Switching & Step Indication - 1.no.\nd). Capacitor Bank 3KVAR- 01 Set\n18 TP MCB,20A 10KA, C Curve- 02 no (mk-Havells) , 19. TP Power Contactor, AC -3 Duty, 230V AC with inrush current damping L&T 12A -1 no (mk-L&T)\n20. Capacitor Bank, MPP Type, Cyl. Heavy duty Capacitor, 440V AC 5 kVAr - 1no.(mk-Havells)\n21. Illuminated Switch For Manual Switching & Step Indication - 1.no.\ne). Capacitor Bank 3KVAR- 01 Set\n22 TP MCB,20A 10KA, C Curve- 02 no (mk-Havells) , 23. TP Power Contactor, AC -3 Duty, 230V AC with inrush current damping L&T 12A -1 no (mk-L&T)\n24 Capacitor Bank, MPP Type, Cyl. Heavy duty Capacitor, 440V AC 5 kVAr - 1no.(mk-Havells)\n25. Illuminated Switch For Manual Switching & Step Indication - 1no.\n26. Illuminated Switch For Manual Switching & Step Indication - 2no. | 1 | Each Job |